Article

Exergoeconomic Assessment of Solar Absorption and Absorption–Compression Hybrid Refrigeration in Building Cooling

1
School of Electric Power, South China University of Technology, Guangzhou 510640, China
2
Guangdong Province Key Laboratory of High Efficient and Clean Energy Utilization, South China University of Technology, Guangzhou 510640, China
3
Guangdong Province Engineering Research Center of High Efficient and Low pollution Energy Conversion, South China University of Technology, Guangzhou, 510640, China
*
Author to whom correspondence should be addressed.
Submission received: 19 January 2018 / Revised: 12 February 2018 / Accepted: 14 February 2018 / Published: 17 February 2018
(This article belongs to the Special Issue Work Availability and Exergy Analysis)

Abstract

:
The paper mainly deals with the match of solar refrigeration, i.e., solar/natural gas-driven absorption chiller (SNGDAC), solar vapor compression–absorption integrated refrigeration system with parallel configuration (SVCAIRSPC), and solar absorption-subcooled compression hybrid cooling system (SASCHCS), and building cooling based on the exergoeconomics. Three types of building cooling are considered: Type 1 is the single-story building, type 2 includes the two-story and three-story buildings, and type 3 is the multi-story buildings. Besides this, two Chinese cities, Guangzhou and Turpan, are taken into account as well. The product cost flow rate is employed as the primary decision variable. The result exhibits that SNGDAC is considered as a suitable solution for type 1 buildings in Turpan, owing to its negligible natural gas consumption and lowest product cost flow rate. SVCAIRSPC is more applicable for type 2 buildings in Turpan because of its higher actual cooling capacity of absorption subsystem and lower fuel and product cost flow rate. Additionally, SASCHCS shows the most extensive cost-effectiveness, namely, its exergy destruction and product cost flow rate are both the lowest when used in all types of buildings in Guangzhou or type 3 buildings in Turpan. This paper is helpful to promote the application of solar cooling.

1. Introduction

Solar absorption chillers present potential for utilizing sustainable fuels to reduce air conditioning energy consumption and greenhouse gas emission [1]. The fact that collectors are usually installed at the roof of buildings leads to that the maximum cooling output of an individual solar absorption chiller cannot meet the entire building cooling demand, especially for the high-rise buildings [2]. Since natural gas is cheaper and cleaner than oil, solar/natural gas-driven absorption chiller (SNGDAC) is commonly used to increase the total cooling output. Although its investment cost increment mainly coming from the auxiliary heat machine is little compare with single-effect solar absorption chiller, its operational cost increment caused by the consumption of natural gas is high especially when applied on the high-rise buildings [3]. Therefore, the economic performance of SNGDAC is determined by the quantity of natural gas consumption, and moreover, the scale of buildings.
Besides this, types of compression–absorption hybrid systems were put forward recently, such as solar vapor compression–absorption integrated refrigeration system with parallel configuration (SVCAIRSPC) [4] and solar absorption-subcooled compression hybrid cooling system (SASCHCS) [5]. Compared with SNGDAC, the operational cost of compression–absorption hybrid system is lower but the investment cost is higher. In SVCAIRSPC, the chilled water flows through the evaporators of the absorption subsystem and compression subsystem successively to output the cooling. However, in SASCHCS, the cooling output of absorption subsystem does not directly cool the chilled water but subcools the refrigerant of the compression subsystem. Consequently, not only can its exergy destruction of throttling valve in the compression chiller be decreased, but its evaporator temperature of the absorption chiller can also be improved compared with SVCAIRSPC [5]. Nevertheless, the advantage of SASCHCS becomes weaker with the growth of cooling capacity in the absorption subsystem because of the significant decline of evaporator temperature in the absorption subsystem [6]. Even the evaporator temperature of the absorption subsystem can be lower than 0 °C only if the size of absorption chiller is great enough. In this case, the thermodynamic performance of SASCHCS is obviously poorer than SVCAIRSPC. To sum up, the strength of SNGDAC benefits to its lower investment cost compared with the other two hybrid systems, and for the two hybrid systems, which configuration has the better thermodynamic performance depends on the required cooling output of the absorption subsystem. Consequently, in order to provide a suitable solar absorption cooling for those buildings requiring different cooling demands and located under different solar irradiance, it is essential to compare the performance of the above three configurations based on a proper method in which the trade-off of system investment and operation cost is contained.
The exergoeconomic analysis combining both thermodynamics and economics is helpful to perform the comprehensive comparison of the above three configurations [7]. In exergoeconomics, exergy is used instead of energy as thermodynamic criteria to analysis the energy transfer in different components [8]. The exergoeconomic analysis has been used in many absorption refrigeration systems. Preliminarily, this method was applied to the optimization of a single-effect LiBr–H2O absorption system, aiming at minimizing its overall operation and amortization cost [9]. In addition, exergoeconomic analysis was used to design a phase-change material (PCM) storage system of single-effect absorption chiller [10], but the result showed that the payback period increases caused by the auxiliary storage system. Subsequently, a double-effect LiBr–H2O absorption system was optimized by a simplified cost minimization methodology based on exergoeconomics [11]. In order to investigate the effect of different thermodynamic parameters on thermoeconomic performance, a deeper exergoeconomic analysis of three types of LiBr–H2O double-effect absorption refrigeration systems were performed [12]. Besides this, a combined ejector double-effect system was also included [13]. In that research, series flow double-effect system and combined ejector double-effect system were compared, and the influences of various operating parameters on investment cost and product cost flow rate were analyzed. The result showed that the combined cycle operates more economically than the double effect system. In addition, this method was extended to an NH3–H2O vapor-absorption refrigeration system [14]. A contrast study of NH3–H2O absorption chiller and LiBr–H2O absorption chiller was done from the exergoeconomic viewpoint [15]. It was shown that the NH3–H2O absorption chiller had the highest exergy destruction cost rate, and the LiBr–H2O absorption chiller had the lowest one.
The exergoeconomic analysis was also used to the hybrid refrigeration systems. For a cascade absorption–compression refrigeration system, cooling set and solution heat exchanger should be designed carefully according to the exergoeconomic factor values [16]. And the multi-objective optimization of a cascade hybrid system was performed based on the NSGA-II technique, which combines both thermodynamics and total product cost flow rate [17]. For hybrid generator–absorber heat exchange (GAX) refrigeration absorption cycle, its coefficient of performance (COP) and exergy efficiency was higher than standard GAX cycle, but its product cost per exergy unit was higher, too [18]. Also, it was found that the cooling capacity of the absorption subsystem, the condenser2 temperature, the evaporator temperature, and the isentropic efficiency of compressor in the absorption-subcooled compression hybrid cooling system should be designed carefully from the exergoeconomic viewpoint [6]. Apart from refrigeration systems, exergoeconomics was also used to analysis multi-effect evaporation-absorption heat pump and vapor-compression refrigeration [19]. It was found that the system with two refrigerant compressors was flexible in order to allocate different energy sources, and the parameter optimizations were done later [20]. Besides this, the exergoeconomic analysis was used to reduce the fuel cost flow rate and the exergy destruction cost of a novel solar-trigeneration system for heating, cooling, and power production [21]. Also, the exergoeconomic analysis based on a novel combined SCRB–ARC (supercritical CO2 recompression Brayton–absorption refrigeration cycle) showed that the largest exergy destruction rate belongs to the reactor, while the components in the ARC have less exergy destruction [22]. Furthermore, the comprehensive exergoeconomic comparison of three types of absorption power and cooling cogeneration cycles based on Kalina revealed that the first configuration of simple ammonia-water absorption refrigeration/Kalina co- generation cycle has the lowest cost of products and payback period [23]. A novel solar-based combined system containing a concentrated photovoltaic thermal (CPVT), a single effect LiBr–H2O absorption chiller, and proton exchange membrane electrolyzer (PEM) was also analyzed in detail by exergoeconomics, and it was found that the maximum exergy destruction occurs in the CPVT followed by absorption chiller unit and PEM electrolyzer [24].
SNGDAC, SVCAIRSPC, and SASCHCS are three typical promising solar absorption chillers to solve building cooling. However, the optimal match of above-mentioned facility and different types of buildings based on a comprehensive consideration of thermodynamic and economic performance is still not clear. It was found that exergoeconomics is a powerful method to present the exergoeconomic comparison of SNGDAC, SVCAIRSPC, and SASCHCS thermodynamically and economically. Consequently, this paper aims to obtain the appropriate solution for different types of buildings cooling based on the exergoeconomic comparison. Three types of buildings and two Chinese cities with different solar irradiance, Guangzhou and Turpan, are taken into account. The product cost flow rate is employed as the primary decision variable. Besides, the match of three solar refrigeration systems and building cooling is analyzed and explained thoroughly by the exergy and cost. The novelty of paper is the presentation of appropriate solar refrigeration system for different types of building cooling. The paper is helpful to promote the application of solar cooling.

2. System Description

In each solar absorption refrigeration system, the solar system consists of the evacuated tube collectors (ETC) and a hot water storage tank. The working fluids of collectors, absorption chillers, and compression chillers are pressurized water, LiBr–H2O, and R410A, respectively. Besides this, the cooling capacity of absorption chillers in SVCAIRSPC and SASCHCS are restricted by both the installation area of collectors and the intensity of solar irradiance. Several structural features of three systems are described as follows:
  • Solar/Natural Gas-Driven Absorption Chiller (SNGDAC)
The schematic of SNGDAC is shown in Figure 1. This plant consists of a solar system, an auxiliary heat system, a single-effect absorption chiller equipped with a cooling tower, liquid pipelines, and valves. In this machine, a natural gas burner is used as auxiliary device in case that the cooling output of absorption chiller cannot satisfy the maximum cooling demand of buildings. Moreover, when the solar irradiance cannot meet the required demand of generator, the auxiliary heater is switched on to fulfill the entire energy requirement of absorption chiller.
  • Solar Vapor Compression–Absorption Integrated Refrigeration System with Parallel Configuration (SVCAIRSPC)
The schematic of SVCAIRSPC is shown in Figure 2. This plant consists of a solar system, a single-effect absorption chiller, a vapor compression chiller, liquid pipelines, and valves. In SVCAIRSPC, the cooling load of buildings are shared by two subsystems, and the chilled water is cooled in the evaporators of absorption subsystem and compression subsystem successively [4].
  • Solar Absorption-subcooled Compression Hybrid Cooling System (SASCHCS)
The schematic of SASCHCS is shown in Figure 3. Similar with SVCAIRSPC, this machine consists of an absorption section and a compression section. Nevertheless, the evaporator of absorption section also works as the subcooler of the compression section. That is, the cooling capacity of the absorption chiller directly subcools the refrigerant of the compression subsystem instead of cooling the chilled water. Consequently, the exergy destruction of the throttling valve in the compression section is decreased and the consumption of the compressor is saved [5].

3. Building Description

The buildings simulated by Hongye program [25] in this paper are divided into three types: type 1 is the single-story building, type 2 includes the two-story and three-story buildings, and type 3 is the multi-story building (its number of floor is from four to ten). The design parameters of three types of buildings are the same except the number of floors. The area of each floor is 360 m2 containing ten rooms, and the daily ventilation rate is taken as 30 m3/h/person. The window-to-wall ratio equals to 0.3 (the windows are uniformly distributed on the lateral surfaces). In the whole operational period, the room temperature is controlled between 22 °C and 26 °C. In particular, the cooling ventilation is considered when the outdoor surrounding temperature is lower than 22 °C. The heat transfer coefficient of windows, doors, walls, and roofs are 2.7 W/(m2·K), 2.7 W/(m2·K), 1.081 W/(m2·K), and 0.812 W/(m2·K), respectively.

4. Model

4.1. Thermodynamic Model

The thermodynamic models of three solar absorption systems are based on following assumptions:
  • The systems are operated under steady state.
  • The states of working fluid at the exit of condensers, evaporators, and absorbers are saturated.
  • The pressure and heat loss in pipelines and components are neglected.
  • The components of cooling systems are adiabatic.
  • The cooling water is 25 °C and 100 kPa.
The balances of mass and energy conservation are formulated as follows:
Mass   balance : m i = m o
Material   balance : m i x i = m o x o
Energy   balance : Q = m i h i m o h o .
The efficiency of ETC is evaluated as follows [26]:
η e t c = 0.612 1.98 ( T i T a ) / I .
Prior to calculating the heat transfer coefficient, the types of heat exchangers are introduced. The generator is a falling film vertical tube heat exchanger. In generator, the hot water and the LiBr–H2O solution fluid flow inside and outside the tubes respectively. The condensers are taken as the horizontal tube heat exchanger. The R410A–H2O is condensed on the outside surface of the tubes and the cooling water flows inside the tubes. The absorber is a falling film vertical tube heat exchanger. The solution flows downward on the outside surface of the tubes so that the water vapor from the evaporator can be absorbed totally, and the cooling water flows inside the tubes. The evaporator is a horizontal tube heat exchanger. The working fluid (R410A–H2O) is evaporated on the outside surface of the tubes and the chilled water flows inside the tubes. The subcooler in SASCHCS is a falling film horizontal tube heat exchanger. The water vapor is evaporated on the outside surface of the tubes and the refrigerant (R410A) flows inside the tubes. Besides this, the solution heat exchanger is a double-pipe heat exchanger. The strong LiBr solution flows inside the inner pipes, and the weak LiBr solution flows outside the pipes.
The correlations referred to the calculation of the heat transfer coefficients in the heat exchanges are summarized in Table 1. Besides, the inner diameter, the thickness, the length, and the fouling factors of tubes are taken as 25 mm, 2 mm, 1 m, and 0.09 m2·°C/kW, respectively [13].
The area of heat exchange is calculated as:
A = Q U L M T D .
U is the heat transfer coefficient of overall system:
U = 1 1 h o + F o + d o d i F i + d o d i 1 h i .
LMTD is the mean temperature difference between the hot and the cold fluid that is expressed as:
L M T D = Δ T 0 Δ T L ln Δ T 0 Δ T L .

4.2. Exergoeconomic Model

Prior to exergoeconomic analysis, it is essential to establish the exergy model. In order to analyze the performance of a system from the second law point of view, the Fuel-Product-Loss (F-P-L) model of exergy flow rate is established. The fuel represents the exergy input to obtain the product and is not restricted into actual energy such as solar or natural gas [33]. The product represents the required result of components or total systems. Based on the F-P-L model, SNGDAC is divided into the following components: collectors, store tank, auxiliary heat device, generator, solution heat exchange, pump, and cooling set (enclosed by dash line in Figure 1). The other two hybrid systems are divided into collectors, store tank, generator, solution heat exchange, pump, compressor, and cooling set (enclosed by dash line in Figure 2 and Figure 3). The definitions of the fuel, product, and loss of exergy for each component are summarized in Table 2.
The exergy of each point is calculated as:
E = m e = m [ ( h h 0 ) T 0 ( s s 0 ) ] .
The exergy destruction is calculated by the exergy balances of the components:
E D = E i E o .
Besides, the exergy destruction can be calculated based on the F-P-L model as well:
E D = E F E P E L .
To calculate the investment costs of heat exchange, solution pump and compressor, a power law related is used, such as [34]:
Z H E = Z R , H E ( A A R , H E ) α
Z S P = Z R , S P ( W S P W R , S P ) m 1 ( 1 η s p η s p ) n 1
Z C O M = Z R , C O M ( W C O M W R , C O M ) m 1 ( η s , C O M 0.9 η s , C O M ) n 2
Here, the powers in the equations take on the following values:
α = 0.6, m1 = 0.26, n1 = 0.5, m2 = 1.0, n2 = 0.5
The other values of corresponding parameters are listed on Table 3.
In order to update the investment cost to year 2018, the chemical engineering plant cost index (CEPCI) [35] is defined as follow:
Z = Z oy C E P C I C E P C I oy .
In order to convert the investment cost of a component into the cost flow rate, the levelized investment cost is gotten by the multiplication of capital investment cost and capital recovery factor (CRF). The CRF is determined as follows:
C R F = i ( 1 + i ) N ( 1 + i ) N 1 .
Here, i represents the 2018 Chinese interest rate and is equal to 0.0435. N is the operational period of systems and it is considered as 20 years [13].
In order to calculate the cost flow rate of each working fluid, it is essential to formulate some equations of component based on the F-P-L model. The corresponding auxiliary equations are shown in Table 4. The exergoeconomic analysis is mainly based on the fuel cost per exergy unit, the product cost per exergy unit, the exergy destruction cost flow rate, and the loss cost flow rate. The corresponding parameters are defined as follows:
c F = C F / E F
c P = C P / E P
C D = c F E D
C L = c F E L

4.3. Model Validation and Case Study

In order to validate the thermodynamic model of SNGDAC, the experimental results reported by Reference [36] are considered. The input data are Tcond = 33 °C, Ta = 33 °C, Teva = 4/10 °C, and εshx = 0.7. The comparison of COP of SVCAIRSPC with Reference [33] is shown in Figure 4. It was found that the error in the computation of COP is less than 3.89%.
The SVCAIRSPC is validated with corresponding numerical results presented by Reference [4]. The following input data are used for comparison: Qe = 170 kW, Tcond = 37 °C, Tg = 90 °C, Ta = 37 °C, Teva-a = 6 °C, and Teva-c = 1 °C. The comparison of performance data of SVCAIRSPC with Reference [4] is shown in Table 5. It was found that the error in the calculated values is less than 2.48%.
Besides this, the validation of SASCHCS has been done in our previous research [6].
A case study associated with the exergy and exergoeconomic analysis of SNGDAC, SVCAIRSPC, and SASCHCS is carried out. The corresponding design conditions are shown in Table 6. The meteorological data of the base case is collected from the subtropical Guangzhou [5,6]. The annual operational period of air conditioning is from April to October and assumed to be 2100 h. The mean solar irradiance and the average surrounding temperature is 500 W/m2 and 30.2 °C [6]. Calculated by Hongye program, the average daily cooling demand of this building is 158 kW. The unit prices of electric energy, storage tank, and ETC are considered as 0.136 $/kWh, 234.45 $/m3, and 93.8 $/m2 based on the Chinese current price. In addition, the exergoeconomic models are established by FORTRAN program. The thermodynamic parameters of working fluids are calculated by the correlation of Pάtek and Klomfar [37] and the software Refprop9 [38].
According to the distribution of solar energy resources in China released by the China Association for Science and Technology [39], the summer cooling demand of Guangzhou is great but its summer solar irradiance is weak, and Turpan is the region with strong summer cooling demand as well as solar irradiance. Consequently, in the further research of this paper, we selected Guangzhou and Turpan as the sources of case meteorological parameters to study the comparison of the cost effectiveness of SNGDAC, SVCAIRSPC, and SASCHCS in different regions. Besides this, the summer average cooling demands of type 1 to type 3 buildings are contained to obtain the better cost effective solar absorption chillers for different types of buildings. The summer average cooling demands of office buildings located in Guangzhou and Turpan are shown in Table 7.

5. Results and Discussions

5.1. Comparison Based on Exergy and Exergoeconomics Analysis

The state property of each point in three chillers is listed in Table 8, and the results of exergy analysis of SNGDAC, SVCAIRSPC, and SASCHCS are demonstrated in Table 9. According to Table 9, the maximum value of ED in SNGDAC belongs to the cooling set involving 47.63% of E D t o t , and the generator and the solution heat exchanger are in the next ranking containing 28.85% and 23.52% of E D t o t , respectively. For the other two hybrid systems, the cooling sets in both SVCAIRSPC with 51.71% of E D t o t and SASCHCS with 53.80% of E D t o t are dominant. The exergy efficiency of SASCHCS is the highest (23%) and that of SNGDAC is the lowest (17%) in the base case. Besides this, the total system fuel exergy of SNGDAC and SVCAIRSPC is 32.94% and 12.25% higher than SASCHCS, respectively, to produce the same cooling power.
Further results obtained from the exergoeconomic analysis are listed in Table 10. It implies that the cooling sets of SNGDAC have the maximum C D + C L + Z with 69.95% of C D t o t + C L t o t + Z t o t , followed by the generator and the solution heat exchanger containing 15.63% and 13.78% of C D t o t + C L t o t + Z t o t . The cooling sets in both SVCAIRSPC with 71.80% of C D t o t + C L t o t + Z t o t and SASCHCS with 70.91% of C D t o t + C L t o t + Z t o t are remarkable. It is obvious that SNGDAC has the highest C D t o t + C L t o t + Z t o t and SASCHCS has the lowest one. Besides, both the c F t o t and c P t o t of SNGDAC are obviously the highest, and the c F t o t of SVCAIRSPC and SASCHCS are almost the same while the c P t o t of SASCHCS is slightly lower. As shown in Table 10, in the base case, the r of SNGDAC is the lowest, owing to the smaller difference between its c F t o t and c P t o t , and the r of SVCAIRSPC and SASCHCS are 67.72% and 18.99% higher, respectively, than that of SNGDAC.

5.2. Comparison Based on Guangzhou

The product cost flow rate obtained simply by replacing the exergy rate by cost rate is an important criterion to evaluate the cost-effectiveness of a system. According to chapter 8 in Reference [33], the product cost flow rate is strongly influenced by the fuel cost flow rate and the exergy efficiency or the exergy destruction. Accordingly, this section mainly compares the total product cost flow rates of three types of absorption chillers, i.e., SNGDAC, SVCAIRSPC, and SASCHCS, to determine the best cost-effective system in different conditions, and besides this, the total fuel cost flow rate and the total exergy destruction are taken as the auxiliary criteria to understand the cost-effectiveness of the three chillers.
The exergy destruction of the three chillers used in three types of buildings located in Guangzhou is shown in Figure 5. It is demonstrated that SASCHCS has the lowest exergy destruction and SNGDAC has the highest one, and such result of comparison is independent to the number of floors of the buildings. It can be explained by that the compressor in the vapor compression chiller is replaced by the generator, the solution heat exchange, and the absorber, but the thermodynamic efficiency of the compressor is obviously better than such replacement. Consequently, the exergy destruction of SNGDAC is around 17%–19% higher than SASCHCS and 13%–16% higher than SVCAIRSPC for all types of buildings. Besides this, in SASCHCS, the cooling output of the absorption subsystem does not directly cool the chilled water but subcools the refrigerant of compression subsystem to decrease the input enthalpy of the throttling valve. Therefore, its exergy destruction of the throttling valve in the compression subsystem is decreased, which results in that the exergy destruction of total system in SASCHCS is less than that in SVCAIRSPC.
The total fuel cost flow rates of the three chillers and the cooling capacities of the absorption subsystem of the two hybrid chillers are shown in Figure 6. It was found that the fuel cost flow rate of SNGDAC is always the highest for the single-story to ten-story office buildings located in Guangzhou. That is attributed to its low COP caused by the large natural gas consumption. Besides this, based on the fundaments of exergoeconomics, the total fuel cost flow rate of a solar absorption–compression hybrid system is mainly derived from the investment cost of the solar system and the consumption of the compressor. In this section, the cooling capacity of the absorption subsystem in the two hybrid systems is restricted by both the maximum installation area of collectors (cannot exceed 270 m2) and the evaporator temperature in the absorption chiller (cannot be below 4 °C). For the hybrid systems applied to the low-rise buildings, the decline of evaporator temperature in absorption chiller with the rise of cooling capacity of absorption subsystem in SASCHCS is much more notable than the decline in SVCAIRSPC. Therefore, as shown in Figure 7, the actual cooling capacity of the absorption subsystem in SASCHCS is obviously lower than that in SVCAIRSPC for the type 1 and type 2 buildings, and its compressor consumption and total fuel cost flow rate is higher. However, for SASCHCS, the limit of evaporator temperature in absorption chiller on the cooling capacity of absorption becomes negligible when used in the high-rise buildings. Meanwhile, the evaporator temperature in absorption chiller of SASCHCS is even higher than that of SVCAIRSPC because of its better thermodynamic performance [5]. Accordingly, the actual cooling capacity of absorption subsystem in SASCHCS is slightly higher than that in SVCAIRSPC when applied to the type 3 buildings, as observed in Figure 7, and its compressor consumption and total fuel cost flow rate are lower. However, the difference of the fuel cost flow rate of SASCHCS and SVCAIRSPC is within ±3% for all three types of buildings.
The results of the comparison of three chillers based on the total product cost flow rate are shown in Figure 7. It is seen that the product cost flow rate of SASCHCS is the least for all three types buildings (1–10 floors) located in Guangzhou. That is attributed to its obviously lowest exergy destruction even though its fuel cost flow rate for the type 1 and type 2 buildings is slightly higher than SVCAIRSPC. Besides this, the product cost flow rate of SNGDAC is always the highest because of its highest exergy destruction as well as fuel cost flow rate. Such product cost flow rate is within 10% higher for the single-story building, but even exceeds 90% higher when the number of floors exceeds eight.

5.3. Comparison Based on Turpan

The total exergy destruction of the three chillers for the types of buildings located in Turpan is shown in Figure 8. It was found that the result of comparison based on the exergy destruction is independent of the region (or the solar irradiance) as well as type of building. That is, the SNGDAC has the highest exergy destruction while the SASCHCS has the lowest one for all buildings, and the excessive exergy destruction of SNGDAC is around 12%–19% higher than the other two hybrid systems.
The total fuel cost flow rates of the three chillers and the cooling capacities of the absorption subsystem of the two hybrid chillers are shown in Figure 9. According to Reference [39], the summer mean solar irradiance of Turpan (around 780 W/m2) is stronger than that of Guangzhou (around 500 W/m2), which results in its higher efficiency of collectors. As a result, in the absorption subsystem of SASCHCS, the limit of evaporator temperature on its actual cooling output is more obvious. That leads to the result that for the single-story to six-story buildings, the actual cooling capacities of absorption subsystem in SASCHCS are lower than those in SVCAIRSPC, and consequently its total fuel cost flow rates are higher, as shown in Figure 10. Besides, the total fuel cost flow rate of SASCHCS is slightly higher than that of SVCAIRSPC for the buildings that exceed six floors because of its higher cooling capacity of the absorption subsystem, which is similar with the result of comparison for buildings that exceed three floors located in Guangzhou. However, the difference of total fuel cost flow rate of SASCHCS and SVCAIRSPC is negligible when the number of floors exceeds four. In addition, the total fuel cost flow rate of SNGDAC is still the highest regardless of the number of floors or the intensity of local mean solar irradiance, and such superfluity becomes significant especially for the mid-rise and high-rise buildings.
As shown in Table 7, the cooling demand of a type 1 building located in Turpan is about 48 kW. It is obvious that the cooling output of a single-effect absorption chiller with 270 m2 collectors can almost meet its cooling demand. In this case, for the type 1 buildings, the natural gas consumption of SNGDAC is negligible and its total fuel cost per exergy unit mainly depends on the investment cost of solar collectors. Meanwhile, the fuel costs per exergy unit of SASCHCS or SVCAIRSPC are determined by both the investment cost of solar collectors and the consumption of the compressor. It has been found that the fuel cost per exergy unit that relies on the investment cost of solar collectors is less than that which relies on the consumption of the compressor [13]. Consequently, for the type 1 buildings located in Turpan, the fuel cost per exergy unit of SNGDAC is less than that of SASCHCS or SVCAIRSPC (Figure 10). Actually, the fuel costs per exergy unit of SNGDAC, SASCHCS, and SVCAIRSPC used in the type 1 buildings located in Turpan are 30.559 $/GJ, 34.748 $/GJ, and 33.457 $/GJ, respectively in this paper. Furthermore, the low fuel cost per exergy unit of SNGDAC leads to the low product cost per exergy unit as well as product cost flow rate when applied to the type 1 buildings, as shown in Figure 10. Besides this, for the type 2 buildings, the product cost flow rate of SVCAIRSPC is the lowest across the three chillers due to its lowest fuel cost flow rate. Moreover, SASCHCS has the lowest product cost flow rate because of its lowest exergy destruction when used in the four-story to six-story buildings located in Turpan, even though its fuel cost flow rate is slightly higher. For the office buildings above six floors, SASCHCS still has the lowest product cost flow rate, and its lowest fuel cost flow rate and exergy destruction are responsible for that. Namely, SASCHCS is more cost-effective for all type 3 buildings located in Turpan, and its total product cost flow rate is around 9% and 50% lower than SVCAIRSPC and SNGDAC, respectively.

6. Conclusions

In this paper, the exergoeconomic evaluation of SNGDAC, SVCAIRSPC, and SASCHCS for different types of buildings cooling is performed. Three types of buildings cooling and two Chinese cities, Guangzhou and Turpan, are considered. The corresponding conclusions are summarized as follows:
  • For all three types of buildings (1–10 floors) located in Guangzhou, SASCHCS shows the best cost-effectiveness, owing to its lowest total fuel and product cost flow rate as well as the least exergy destruction.
  • For the type 1 buildings (1 floor) located in Turpan, SNGDAC is considered as a suitable solution because of its negligible natural gas consumption and lowest total product cost flow rate.
  • For the type 2 buildings (2–3 floors) located in Turpan, SVCAIRSPC is more cost effective than the others, and that is attributed to its higher actual cooling capacity of absorption subsystem and the lowest fuel and product cost flow rate.
  • For the type 3 buildings (4–10 floors) located in Turpan, SASCHCS has the lowest exergy destruction and product cost flow rate, namely, the optimum cost effectiveness.

Acknowledgments

This work is supported by: (1) National Natural Science Foundation of China under contract No. 51206056, (2) Natural Science Foundation of Guangdong Province under contract No. 2015A030313226, (3) Fundamental Research Funds for the Central Universities under contract No. 2017ZD023, and (4) Key Laboratory of Efficient and Clean Energy Utilization of Guangdong Higher Education Institutes under contract No. KLB10004.

Author Contributions

Zeyu Li constructed the thermodynamic model and guided this research; Yue Jing applied the exergoeconomic method, analyzed the data and wrote the paper; Liming Liu collected the meteorological and building parameters; Shengzi Lu directed and corredted the language expression. All authors have read and approved the final manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Aarea (m2)
ArArchimedes number based on tube diameter
ccost per exergy unit ($/GJ)
cpspecific heat (kJ/kg·°C)
Ccost flow rate ($/s)
CEPCIchemical engineering plant cost index
COPcoefficient of performance
CRFcapital recovery factor
especific exergy (kJ/kg)
Eexergy rate (kW)
ddiameter (m)
Ffouling factor (m2·°C/kW)
gacceleration of gravity (m/s2)
hspecific enthalpy (kJ/kg), heat transfer coefficient (W/m2·°C)
iChinese interest rate
Isolar irradiance (W/m2)
LMTDlogarithmic mean temperature difference
mmass flow rate (kg/s)
Noperational period
NuNusselt number
PrPrandtl number
Qheat flux (kW/m2), heat load (kW)
rlatent heat (kJ/kg)
ReReynolds number
sspecific entropy (kJ/kg)
Ttemperature (°C)
Uheat transfer coefficient
Wwork (kW)
WeWeber number
xconcentration of solution
XLockhart-Martinelli parameter
Zinvestment cost

Greek symbols

ρdensity (kg/m3)
ηefficiency
λthermal conductivity (kW/m·°C)
μviscosity (kg/m3)
σsurface tension (N/m)
Гmass flow rate per wetted perimeter (kg/m3)
εncorrection factor of tube bundle

Subscripts

0environmental state
asurrounding, absorption chiller
COMcompressor
colcollector
Dexergy destruction
exexergy
Eevaporator
etcevacuated tube collector
Ffuel
ggenerator
HEheat exchanger
hybhybrid system
iinlet
lliquid
Lloss
oOutlet
oyoriginal year
poolpool boiling
Pproduct
Rreference state
sisentropic
satsaturation
syssystem
SPsolution pump
STstorage tank
vvapour
wwall

References

  1. Lake, A.; Rezaie, B.; Beyerlein, S. Use of exergy analysis to quantify the effect of lithium bromide concentration in an absorption chiller. Entropy 2017, 19, 156. [Google Scholar] [CrossRef]
  2. Fong, K.F.; Chow, T.T.; Lee, C.K.; Lin, Z.; Chan, L.S. Comparative study of different solar cooling systems for buildings in subtropical city. Sol. Energy 2010, 84, 227–244. [Google Scholar] [CrossRef]
  3. Noro, M.; Lazzarin, R.M. Solar cooling between thermal and photovoltaic: An energy and economic comparative study in the Mediterranean conditions. Energy 2014, 73, 453–464. [Google Scholar] [CrossRef]
  4. Jain, V.; Sachdeva, G.; Kachhwaha, S.S. Energy, exergy, economic and environmental (4E) analyses based comparative performance study and optimization of vapor compression-absorption integrated refrigeration system. Energy 2015, 91, 816–832. [Google Scholar] [CrossRef]
  5. Li, Z.; Jing, Y.; Liu, J. Thermodynamic study of a novel solar LiBr/H2O absorption chiller. Energy Build. 2016, 133, 565–576. [Google Scholar] [CrossRef]
  6. Li, Z.; Liu, L.; Jing, Y. Exergoeconomic analysis of solar absorption-subcooled compression hybrid cooling system. Energy Convers. Manag. 2017, 144, 205–216. [Google Scholar] [CrossRef]
  7. Misra, R.D.; Sahoo, P.K.; Gupta, A. Application of the exergetic cost theory to the LiBr/H2O vapour absorption system. Energy 2002, 27, 1009–1025. [Google Scholar] [CrossRef]
  8. Tsatsaronis, G. Thermoeconomic analysis and optimization of energy systems. Prog. Energy Combust. Sci. 1993, 19, 227–257. [Google Scholar] [CrossRef]
  9. Misra, R.D.; Sahoo, P.K.; Sahoo, S.; Gupta, A. Thermoeconomic otimization of a single effect water/LiBr vapour absorption refrigeration system. Int. J. Refrig. 2003, 26, 158–169. [Google Scholar] [CrossRef]
  10. Godarzi, A.A.; Jalilian, M.; Samimi, J.; Jokar, A.; Vesaghi, M.A. Design of a PCM storage system for a solar absorption chiller based on exergoeconomic analysis and genetic algorithm. Int. J. Refrig. 2013, 36, 88–101. [Google Scholar] [CrossRef]
  11. Misra, R.D.; Sahoo, P.K.; Gupta, A. Thermoeconomic evaluation and optimization of a double-effect H2O/LiBr vapour-absorption refrigeration system. Int. J. Refrig. 2005, 28, 331–343. [Google Scholar] [CrossRef]
  12. Garousi Farshi, L.; Mahmoudi, S.M.S.; Rosen, M.A.; Yari, M.; Amidpour, M. Exergoeconomic analysis of double effect absorption refrigeration systems. Energy Convers. Manag. 2013, 65, 13–25. [Google Scholar] [CrossRef]
  13. Garousi Farshi, L.; Mahmoudi, S.M.S.; Rosen, M.A. Exergoeconomic comparison of double effect and combined ejector-double effect absorption refrigeration systems. Appl. Energy 2013, 103, 700–711. [Google Scholar] [CrossRef]
  14. Misra, R.D.; Sahoo, P.K.; Gupta, A. Thermoeconomic evaluation and optimization of an aqua-ammonia vapour-absorption refrigeration system. Int. J. Refrig. 2006, 29, 47–59. [Google Scholar] [CrossRef]
  15. Shokati, N.; Ranjbar, F.; Yari, M. A comparative analysis of rankine and absorption power cycles from exergoeconomic viewpoint. Energy Convers. Manag. 2014, 88, 657–668. [Google Scholar] [CrossRef]
  16. Cimsit, C.; Ozturk, I.T.; Kincay, O. Thermoeconomic optimization of LiBr/H2O-R134a compression-absorption cascade refrigeration cycle. Appl. Therm. Eng. 2015, 76, 105–115. [Google Scholar] [CrossRef]
  17. Jain, V.; Sachdeva, G.; Kachhwaha, S.S.; Patel, B. Thermo-economic and environmental analyses based multi-objective optimization of vapor compression-absorption cascaded refrigeration system using NSGA-II technique. Energy Convers. Manag. 2016, 113, 230–242. [Google Scholar] [CrossRef]
  18. Mehr, A.S.; Zare, V.; Mahmoudi, S.M.S. Standard GAX versus hybrid GAX absorption refrigeration cycle: From the view point of thermoeconomics. Energy Convers. Manag. 2013, 76, 68–82. [Google Scholar] [CrossRef]
  19. Esfahani, I.J.; Kang, Y.T.; Yoo, C. A high efficient combined multi-effect evaporation-absorption heat pump and vapor-compression refrigeration part 1: Energy and economic modeling and analysis. Energy 2014, 75, 312–326. [Google Scholar] [CrossRef]
  20. Janghorban Esfahani, I.; Lee, S.C.; Yoo, C.K. Evaluation and optimization of a multi-effect evaporation-absorption heat pump desalination based conventional and advanced exergy and exergoeconomic analyses. Desalination 2015, 359, 92–107. [Google Scholar] [CrossRef]
  21. Baghernejad, A.; Yaghoubi, M.; Jafarpur, K. Exergoeconomic optimization and environmental analysis of a novel solar-trigeneration system for heating, cooling and power production purpose. Sol. Energy 2016, 134, 165–179. [Google Scholar] [CrossRef]
  22. Wu, C.; Wang, S.; Feng, X.; Li, J. Energy, exergy and exergoeconomic analyses of a combined supercritical CO2 recompression Brayton/absorption refrigeration cycle. Energy Convers. Manag. 2017, 148, 360–377. [Google Scholar] [CrossRef]
  23. Shokati, N.; Ranjbar, F.; Yari, M. A comprehensive exergoeconomic analysis of absorption power and cooling cogeneration cycles based on Kalina, part 1: Simulation. Energy Convers. Manag. 2018, 158, 437–459. [Google Scholar] [CrossRef]
  24. Akrami, E.; Nemati, A.; Nami, H.; Ranjbar, F. ScienceDirect Exergy and exergoeconomic assessment of hydrogen and cooling production from concentrated PVT equipped with PEM electrolyzer and LiBr–H2O absorption chiller. Int. J. Hydrogen Energy 2017, 43, 622–633. [Google Scholar] [CrossRef]
  25. Hongye. Available online: http://bim.hongye.com.cn (accessed on 16 February 2018).
  26. Liu, Y.L.; Wang, R.Z. Performance prediction of a solar/gas driving double effect LiBr–H2O absorption system. Renew. Energy 2004, 29, 1677–1695. [Google Scholar] [CrossRef]
  27. Shi, C.; Chen, Q.; Jen, T.-C.; Yang, W. Heat transfer performance of lithium bromide solution in falling film generator. Int. J. Heat Mass Transf. 2010, 53, 3372–3376. [Google Scholar] [CrossRef]
  28. Grimson, E.D. Correlation and utilization of new data on flow resistance and heat transfer for cross flow of gases over tube banks. Trans. ASME. 1937, 59, 583–594. [Google Scholar]
  29. Yang, S.M.; Tao, W.Q. Heat Transfer; Higher Education Press: Beijing, China, 2000. (In Chinese) [Google Scholar]
  30. Florides, G.A.; Kalogirou, S.A.; Tassou, S.A.; Wrobel, L.C. Design and construction of a LiBr-water absorption machine. Energy Convers. Manag. 2003, 44, 2483–2508. [Google Scholar] [CrossRef]
  31. Saitoh, S.; Daiguji, H.; Hihara, E. Correlation for boiling heat transfer of R-134a in horizontal tubes including effect of tube diameter. Int. J. Heat Mass Transf. 2007, 50, 5215–5225. [Google Scholar] [CrossRef]
  32. Ribatski, G.; Jacobi, A.M. Falling-film evaporation on horizontal tubes - A critical review. Int. J. Refrig. 2005, 28, 635–653. [Google Scholar] [CrossRef]
  33. Bejan, A.; Tsatsaronis, G.; Moran, M. Thermal Design and Optimization; John Wiley: New York, NY, USA, 1996. [Google Scholar]
  34. D’Accadia, M.D.; de Rossi, F. Thermoeconomic optimization of a refrigeration plant. Int. J. Refrig. 1998, 21, 42–54. [Google Scholar] [CrossRef]
  35. Mignard, D. Correlating the chemical engineering plant cost index with macro-economic indicators. Chem. Eng. Res. Des. 2014, 92, 285–294. [Google Scholar] [CrossRef]
  36. Gomri, R. Second law comparison of single effect and double effect vapour absorption refrigeration systems. Energy Convers. Manag. 2009, 50, 1279–1287. [Google Scholar] [CrossRef]
  37. Pátek, J.; Klomfar, J. A computationally effective formulation of the thermodynamic properties of LiBr–H2O solutions from 273 to 500 K over full composition range. Int. J. Refrig. 2006, 29, 566–578. [Google Scholar] [CrossRef]
  38. NIST Reference Fluid Thermodynamic and Transport Properties Database (REFPROP): Version 9.1. Available online: http://www.nist.gov/srd/nist23.cfm (accessed on 16 February 2018).
  39. The Distribution of Solar Energy Resources in China. Available online: http://news.xinhuanet.com/science/2015-04/04/c_134123280.htm (accessed on 16 February 2018).
Figure 1. Schematic of Solar/Natural Gas-Driven Absorption Chiller (SNGDAC).
Figure 1. Schematic of Solar/Natural Gas-Driven Absorption Chiller (SNGDAC).
Entropy 20 00130 g001
Figure 2. Schematic of Solar Vapor Compression–Absorption Integrated Refrigeration System with Parallel Configuration (SVCAIRSPC).
Figure 2. Schematic of Solar Vapor Compression–Absorption Integrated Refrigeration System with Parallel Configuration (SVCAIRSPC).
Entropy 20 00130 g002
Figure 3. Schematic of Solar Absorption-Subcooled Compression Hybrid Cooling System (SASCHCS).
Figure 3. Schematic of Solar Absorption-Subcooled Compression Hybrid Cooling System (SASCHCS).
Entropy 20 00130 g003
Figure 4. Comparison of COP of SNGDAC with Reference [36].
Figure 4. Comparison of COP of SNGDAC with Reference [36].
Entropy 20 00130 g004
Figure 5. Exergy destruction based on Guangzhou.
Figure 5. Exergy destruction based on Guangzhou.
Entropy 20 00130 g005
Figure 6. Fuel cost flow rate and cooling capacity of the absorption system based on Guangzhou.
Figure 6. Fuel cost flow rate and cooling capacity of the absorption system based on Guangzhou.
Entropy 20 00130 g006
Figure 7. Product cost flow rate based on Guangzhou.
Figure 7. Product cost flow rate based on Guangzhou.
Entropy 20 00130 g007
Figure 8. Exergy destruction based on Turpan.
Figure 8. Exergy destruction based on Turpan.
Entropy 20 00130 g008
Figure 9. Fuel cost flow rate and cooling capacity of absorption system based on Turpan.
Figure 9. Fuel cost flow rate and cooling capacity of absorption system based on Turpan.
Entropy 20 00130 g009
Figure 10. Product cost flow rate based on Turpan.
Figure 10. Product cost flow rate based on Turpan.
Entropy 20 00130 g010
Table 1. Heat transfer coefficients.
Table 1. Heat transfer coefficients.
ComponentApplicationHeat Transfer Coefficient
GeneratorInside [27] h = 129.7712 x i 0.8058 q w 0.2422 Re 0.0856
Outside [28] N u = 0.348 ε n Re 0.592
CondenserInside [13] { h = 0.555 [ g ρ l ( ρ l ρ v ) λ l 3 r μ l ( T s a t T w ) ] 1 4 r = r + 3 8 c p , l ( T s a t T w )
OutsideSimilar to the generator
AbsorberInside [29] N u = 0.023 Re 0.8 Pr n
Outside [30] { h = λ δ 0.029 Re 0.53 Pr 0.344 δ = ( 3 μ Γ / ρ 2 g ) 1 / 3 Re = 4 Γ / μ Γ = m / μ d
EvaporatorInside [31] { h = F h l + S h p o o l F = 1 + ( 1 / X ) 1.05 1 + W e g 0.4 S = 1 1 + 0.4 ( Re × 10 4 ) 1 / 4 h p o o l = 207 λ l d b ( q d b λ l T l ) 0.745 ( ρ v ρ l ) 0.581 Pr l 0.533 d b = 0.51 [ 2 σ / g ( ρ l ρ v ) ] 0.5
OutsideSimilar to the generator
SubcoolerInsideSimilar to the absorber
Outside [32] N u = 0.041 Re 0.03 Pr l A r 0.04
Solution heat exchange [29] N u = 0.012 ( Re 0.87 280 ) Pr 0.4 ( 1 + d / l ) 2 / 3 ( Pr / Pr w ) 0.11
Table 2. Definition of fuel, product, and loss exergy flow rate of the three systems.
Table 2. Definition of fuel, product, and loss exergy flow rate of the three systems.
ComponentFuelProductLoss
SNGDAC
CollectorIE21E22-
Auxiliary heatE21E22E19E20-
Storage tankE19E20E17E18
GeneratorE17E18E1 + E8E7-
Solution heat exchangeE8E9E7E6-
PumpWspE6E5-
Cooling setE1 + E9E5E14E13E15E16 + E11E12
Overall cooling systemE17E18 + WspE14E13E15E16 + E11E12
SVCAIRSPC
CollectorIE26E27-
Storage tankE26E27E24E25-
GeneratorE24E25E1 + E8E7-
Solution heat exchangeE8E9E7E6-
PumpWspE6E5-
CompressorWcomE11E14-
Cooling setE1 + E9 + E11E5E14E15E17E19E18 + E21E20 + E23E22
Overall cooling systemE24E25 + Wsp + WcomE15E17E19E18 + E21E20 + E23E22
SASCHCS
CollectorIE26E27-
Storage tankE26E27E24E25-
GeneratorE24E25E1 + E8E7-
Solution heat exchangeE8E9E7E6-
PumpWspE6E5-
CompressorWcomE11E15-
Cooling setE1 + E9 + E11E5E15E16E17E19E18 + E21E20 + E23E22
Overall cooling systemE24E25 + Wsp + WcomE16E17E18+E21E20+E23E22
Table 3. Parameters of the investment cost.
Table 3. Parameters of the investment cost.
AR = 100 m2, WR,SP = 10 kW, WR,COM = 100 kW
ComponentValue ($)
Generator17,500
Condenser8000
Evaporator/Subcooler16,000
Absorber16,500
Solution heat exchange12,000
Solution pump2100
Compressor12,000
Valve300
Table 4. Auxiliary equations of the cost flow rate for different components in the three systems.
Table 4. Auxiliary equations of the cost flow rate for different components in the three systems.
ComponentSNGDACSVCAIRSPCSASCHCS
Generator C 1 C 7 E 1 E 7 = C 8 C 7 E 8 E 7 C 1 C 7 E 1 E 7 = C 8 C 7 E 8 E 7 C 1 C 7 E 1 E 7 = C 8 C 7 E 8 E 7
Solution heat exchange C 8 / E 8 = C 9 / E 9 C 8 / E 8 = C 9 / E 9 C 8 / E 8 = C 9 / E 9
Absorber (include the valve) C 4 + C 10 E 4 + E 10 = C 5 E 5 C 4 + C 10 E 4 + E 10 = C 5 E 5 C 4 + C 10 E 4 + E 10 = C 5 E 5
C 9 / E 9 = C 10 / E 10 C 9 / E 9 = C 10 / E 10 C 9 / E 9 = C 10 / E 10
Evaporator1/Subcooler C 3 / E 3 = C 4 / E 4 C 3 / E 3 = C 4 / E 4 C 3 / E 3 = C 4 / E 4
(include the valve1) C 2 / E 2 = C 3 / E 3 C 2 / E 2 = C 3 / E 3 C 2 / E 2 = C 3 / E 3
Condenser1 C 1 / E 1 = C 2 / E 2 C 1 / E 1 = C 2 / E 2 C 1 / E 1 = C 2 / E 2
Evaporator2 C 13 / E 13 = C 14 / E 14 C 11 / E 11 = C 12 / E 12
(include the valve2) C 12 / E 12 = C 13 / E 13 C 14 / E 14 = C 15 / E 15
Table 5. Comparisons of performance data of SVCAIRSPC with Reference [4].
Table 5. Comparisons of performance data of SVCAIRSPC with Reference [4].
ItemModelReference [4]Difference (%)
Heat load of condenser of absorption subsystem (kW)90.6690.650.01
Heat load of condenser of compression subsystem (kW)107.04107.020.02
Heat load of absorber (kW)105.83108.522.48
Heat load of generator (kW)111.49114.182.36
Work of compressor (kW)22.0422.020.09
COP of absorption subsystem0.7620.7442.42
COP of compression subsystem3.8563.860.10
Table 6. Design conditions of the three systems.
Table 6. Design conditions of the three systems.
ParametersSNGDACSVCAIRSPCSASCHCS
Maximal installation area of collector array (m2)270270270
Volume of storage tank (m3)1.81.81.8
Inlet/outlet temperature of hot water in evacuated tube collectors (ETC) (°C)100/105100/105100/105
Inlet/outlet temperature of hot water in storage tank (°C)100/90100/90100/90
Effectiveness of solution heat exchange0.70.70.7
Isentropic efficiency of compressor0.70.70.7
Efficiency of solution pump0.950.950.95
Inlet/outlet temperature of cooling water in condenser1 (°C)32/3732/3732/37
Inlet/outlet temperature of cooling water in absorber (°C)32/3732/3732/37
Inlet/outlet temperature of chilled water in evaporator1 (°C)12/712/--
Degree of overlap in subcooler (°C)--9
Generator temperature of absorption system (°C)858585
Condenser temperature of absorption system (°C)404040
Absorber temperature of absorption system (°C)404040
Evaporator temperature of absorption system (°C)5-5
Inlet/outlet temperature of cooling water in condenser2 (°C)-32/3732/37
Inlet/outlet temperature of chilled water in evaporator2 (°C)--/712/7
Condenser temperature of compression subsystem (°C)-4040
Evaporator temperature of compression subsystem (°C)--5
Table 7. Summer cooling demands of office buildings located in Guangzhou and Turpan.
Table 7. Summer cooling demands of office buildings located in Guangzhou and Turpan.
Number of Floors12345678910
Cooling demand (kW)Guangzhou47111158204251197344390437483
Turpan48115162208255301348394441487
Table 8. State property of the three chillers at base case (Qtotal = 158 kW).
Table 8. State property of the three chillers at base case (Qtotal = 158 kW).
pointp (kpa)T (℃)m (kg/s)xe (kJ/kg)c ($/GJ)
SNGDAC
17.326850.0674-126.32204.101
27.326400.0674-1.435204.101
30.86450.0674-−7.699204.101
40.86450.0674-−176.39204.101
50.864402.9410.57942.126118.129
67.326402.9410.57942.133118.189
77.32670.52.9410.57947.559125.887
87.326852.8730.59250.468124.898
97.32653.52.8730.59252.542124.898
100.86453.52.8730.59252.542124.898
SVCAIRSPC
17.326850.0139-126.3260.124
27.326400.0139-1.43560.124
31.13490.0139-−5.62560.124
41.13490.0139-−139.460.124
51.134400.2240.55829.7337.311
67.326400.2240.55829.7337.582
77.32667.450.2240.55834.8542.273
87.326850.2380.59260.4742.512
97.32653.50.2380.59252.5442.512
101.13453.50.2380.59252.5442.512
112416.8463.50.8-−102.64868.724
122416.84400.8-−112.88868.724
13931.9350.8-−118.04866.632
14931.9350.8-−129.29966.632
SASCHCS
17.326850.0136-126.3259.531
27.326400.0136-1.43559.531
31.0718.10.0136-−6.03759.531
41.0718.10.0136-−147.26759.531
51.071400.2560.56232.40536.172
67.326400.2560.56232.40936.245
77.32668.940.2560.56237.58740.966
87.326850.2690.59260.46839.656
97.32653.50.2690.59252.54239.656
101.07153.50.2690.59252.54239.656
112416.8463.50.805-−102.64866.405
122416.84400.805-−112.88866.405
132416.8417.10.805-−113.92364.563
14931.9350.805-−115.19364.563
15931.9350.805-−129.29964.563
Table 9. Exergy analysis results of the three chillers at base case (Qtotal = 158 kW).
Table 9. Exergy analysis results of the three chillers at base case (Qtotal = 158 kW).
ComponentEF (kW)EP (kW)EL (kW)ED (kW)ηexYDYLYD* (%)
SNGDAC
Generator50.7642.370.008.360.840.170.0028.85
SHE22.7715.950.006.820.700.130.0023.52
Pump0.030.030.000.001.000.000.000.00
Cooling set35.668.6713.1213.810.240.270.2647.63
System50.788.6713.1228.990.170.580.26100.00
SVCAIRSPC
Generator8.657.060.001.600.820.040.005.56
SHE1.791.230.000.560.690.010.001.96
Pump0.000.000.000.001.000.000.000.00
Compressor37.1226.900.0010.230.730.220.0035.69
Cooling set30.508.678.5513.270.280.360.1956.80
System42.888.678.5525.660.200.630.19100.00
SASCHCS
Generator8.607.060.001.530.820.040.006.87
SHE2.211.400.000.630.690.020.002.83
Pump0.000.000.000.001.000.000.000.00
Compressor29.6021.450.008.160.730.210.0036.51
Cooling set27.888.677.1912.020.310.320.1953.80
System38.208.677.1922.340.230.590.19100.00
Table 10. Exergoeconomic analysis results of the three chillers at base case (Qtotal = 158 kW).
Table 10. Exergoeconomic analysis results of the three chillers at base case (Qtotal = 158 kW).
ComponentcF ($/GJ)cP ($/GJ)CD ($/yr)CL ($/yr)Z ($/yr)CD + CL + Z ($/yr)rf
SNGDAC
Generator108.783132.9406878.9450.000863.8407742.7850.2220.116
SHE121.104178.1456242.7200.000637.0416879.7610.4710.093
Pump38.056323.2260.0000.00049.14549.1457.4941.000
Cooling set160.890280.68516795.8115956.52118.18734654.5370.7450.061
System108.751280.68529917.4815956.543668.21249326.23 1.5810.074
SVCAIRSPC
Generator30.46 41.71 366.94 0.00 233.13 600.07 0.37 0.39
SHE39.35 69.15 166.83 0.00 109.89 276.72 0.76 0.40
Pump38.06 605.53 0.00 0.00 4.13 4.13 14.91 1.00
Compressor38.06 56.62 2942.00 0.00 832.05 3774.05 0.49 0.22
Cooling set54.87 133.76 6750.36 3503.97 1597.92 11852.26 1.44 0.14
System36.62 133.76 10226.13 3503.97 2777.12 16507.22 2.65 0.11
SASCHCS
Generator30.47141.496353.2510.000235.433588.6840.3620.400
SHE38.78467.082185.5300.000112.969298.4990.7300.378
Pump38.055556.7740.0000.0004.2584.25813.631.000
Compressor38.05556.6172346.1490.000663.5343009.6830.4880.220
Cooling set54.627104.6764963.0802968.2271579.3689510.6750.9160.166
System36.349104.6767848.0092968.2272595.56113411.7971.8800.194

Share and Cite

MDPI and ACS Style

Jing, Y.; Li, Z.; Liu, L.; Lu, S. Exergoeconomic Assessment of Solar Absorption and Absorption–Compression Hybrid Refrigeration in Building Cooling. Entropy 2018, 20, 130. https://0-doi-org.brum.beds.ac.uk/10.3390/e20020130

AMA Style

Jing Y, Li Z, Liu L, Lu S. Exergoeconomic Assessment of Solar Absorption and Absorption–Compression Hybrid Refrigeration in Building Cooling. Entropy. 2018; 20(2):130. https://0-doi-org.brum.beds.ac.uk/10.3390/e20020130

Chicago/Turabian Style

Jing, Yue, Zeyu Li, Liming Liu, and Shengzi Lu. 2018. "Exergoeconomic Assessment of Solar Absorption and Absorption–Compression Hybrid Refrigeration in Building Cooling" Entropy 20, no. 2: 130. https://0-doi-org.brum.beds.ac.uk/10.3390/e20020130

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop