Article

Adaptive Curtailment Plan with Energy Storage for AC/DC Combined Distribution Systems

1
School of Electrical Engineering, Korea University, Seoul 136-713, Korea
2
Department of Electrical & Computer Engineering, Seoul National University, Gwanakero 599, Gwanakegu, Seoul 151-742, Korea
*
Author to whom correspondence should be addressed.
Sustainability 2016, 8(8), 818; https://0-doi-org.brum.beds.ac.uk/10.3390/su8080818
Submission received: 30 June 2016 / Revised: 8 August 2016 / Accepted: 17 August 2016 / Published: 19 August 2016

Abstract

:
For developing a large-scale combined system with a number of distributed resources, an appropriate compensation strategy based on the system components and changeable condition must be configured to handle the characteristics of the internal systems. Since renewable sources generate various fluctuations, the compensation plans for the storage device connected along with the sources should be supported by a precise expectation method. A cooperative strategy involving the sharing of the DC section with environmentally sensitive generators, like photovoltaic system (PVs) or waves, demands appropriate ESS compensation solutions, owing to its complexity. An active power-control algorithm with voltage-expectation based on the DC power flow is introduced in this paper and is applied in the designed case studies performed on the electromagnetic transient simulation. DC based multi-generation system is composed by applying tidal generator and super capacitor. To utilize wind energy, an offshore wind–wave generation system was utilized in the verification process.

1. Introduction

It is expected that the next-generation farm based on renewable generators will be developed from clusters of various distribution sources collaborating with compensation-device applications, which could be performed in sequence by the grid operator to enhance the power-supply capability [1,2]. Among the various applications, an energy storage system (ESS) has been consistently utilized for handling the supply and demand issues caused by renewable sources that have unique fluctuation features [3]. The increasing storage demand in several industrial sections has led to the development of improved features for not only a fast response capability but also for ensuring sufficient sizes for the applicable devices [4,5]. Furthermore, with many grids planning to configure highly penetrated wind generators, which could exceed the maximum system load, the challenges and demands of the high-end ESS applications will increase.
Since the distributed farm generation systems demonstrate variations in their characteristics owing to the unpredictable natural conditions, despite the inbuilt smoothing effect, the power profile from the farm generates considerable uncertainty in the grid operation. In the standard deviation, farm based system can achieve 50% reduction of uncertainty due to smoothing effect [6], but further advanced solutions are still discussed with various aspect. To cooperate with even individual wind turbine, a plan for smoothing the output power of the wind power system using a BESS at the DC control section has been recently considered [7]. The main enhancement target of the management system under study is the cooperation among connected generators, which can reliably improve the response capability when order is applied [8]. The superiority of ESS in the electricity market has been described in terms of the smoothing effect that makes the renewable output power relatively stable in [9,10]. Real power management solutions for the support of active power curtailment, mainly based on pitch control to follow the order induced by the transmission and system operator (TSO), are necessary for an electrically sensitive grid. Normally, a generic controllable wind system considers only the pitch angles of the blades to handle the fluctuating and excessive power profiles. However, mechanical stress accrues in the blade if the pitch-angle control operates at a rate fast enough to mitigate short-term fluctuations [11,12]. These power curtailment abilities, in terms of response accordance, are expected to be improved by the support from the storage received through appropriate operation strategies. Several energy storages (including batteries) are composed with inbuilt complementary modes to respond to grid requirements by focusing on the power fluctuations of renewable sources [13]. Most importantly, in the case of implementing both limit options (curtailment and compensation) along with renewable generators, storage devices have to be integrated with appropriate specifications. In order to maintain these combined systems, electrical approaches based on both system order and appropriate ESS design are required.
Conventional applications for grid support have focused on the frequency responses of traditional pumped hydroelectric or compressed-air energy storages [14]. However, due to the geographical constraints at specific sites, large-scale ESSs have been developed and utilized in several microgrid systems. To achieve advanced frequency management within a microgrid, a number of control schemes including hierarchical control were introduced in [15,16,17]. These studies suggested the possibility of using ESS configurations for frequency control in small-scale power systems requiring management of multiple distributed generators and active loads. In previous researches, however, the ESSs were generally composed separately, which meant that there was an AC section between two different power-conversion systems (PCS) for ESS-renewable sources and that the utilized topologies were focused fully on their own independent DC sections behind inverter devices [18,19]. These plans could support reactive power for the rate voltage level at the connection point and it helped the ESSs perform power handling processes with stable operating conditions [20]. In case of DC-integration based on multi-sources, however, previous predictive control methods could not provide a solid ESS response owing to the voltage variations caused by the power flows from various sources. In particular, since DC-based renewable generators could impose unpredictable profiles on the ESS operation processes, specific supporting strategies to manage the transient situation of the power system were demanded to cover these issues.
Typical DC based sources, PV and tidal, have currently been designed to be cluster with some wind generators as described in [21,22]. Lately, offshore systems for increasing electrical generation efficiency, by composing many generators at designated geographical areas, have been continuously studied and efforts have been made to improve the availability of integrated electrical subsystem for power transmission [23]. The interests in researching the existing distributed sources and composing a combined generator system that is suitable to reduce the building cost at the offshore region have been increasing. The wave–offshore hybrid generation system, which is currently designed as a single system, is composed to easily integrate various sources and have possibilities to improve the electrical generation capacity using additional wave generators. The designed structure currently obtains a certification regarding the reliability issues of structural composition [24]. In the current state of the mentioned generation system, wind turbines which are based on permanent magnetic synchronous generator (PMSG) and grouped wave generation system which is based on permanent magnetic synchronous linear generator (PMSLG) have been considered as main power sources and equipped on one offshore platform, sharing required electrical equipment. As the electrical system has to be focused on operator’s demand, additional controllable applications have been studied. However, the specialized application has not been progressed.
In this paper, a voltage considered ESS compensating plan is proposed to perform the output determination for a megawatt (MW) class AC/DC combined generation system by focusing on the demands of the utility grid. The whole management process is formed based on power flow analysis for DC system and it deals with controllable elements that can reflect connected devices. The verification process for designed method is progressed with the electromagnetic transients with DC analysis (EMTDC) software tool. The ESS model composition including control topologies is implemented in case studies. The designed simulation case studies are focused on appropriate operation of an active power-control scheme in accordance with the reference signal from the TSO.

2. System Description

When developing an ESS-combined system utilizing a common DC link with a number of generators, a relevant compensation strategy based on the electrical composition should be formulated to consider the internal voltage conditions—the offshore-based combined generator structures normally have DC sections that are almost 150 m long [25,26].
Figure 1 shows the conceptual control plan of the proposed method. The profiles from the DC-based resources are transferred to the connected power system via an internal conversion device. The ESS, as a compensation device, will be integrated in the common DC link with its own DC/DC converter. The power flow from the DC-based generators (PV or wave) has to be passed through the connection point of the ESS because such compensation devices should be located at the front of the PCS [27]. This flow makes the integrated storage device directly affected by electrical condition in terms of voltage level, which is one of the main reference values in the control process. In this study, the main topology is consist of a system that stores the excess output power (over the reference signal) and a bidirectional PCS that is composed for handling the entire output power of combined generation system. The power-control algorithm deals with both mechanical pitch control for the wind system and electrical control for the ESS device. By calculating the order for ESS accurately, the operational load of pitch control can be mitigated and an option for further power saving can be composed. Including utilized DC network characteristics, DC power flow analysis will be discussed in this section. Before that, basic system descriptions will be treated in the following sections.

2.1. AC/DC Combined Resources

The existing voltage source converter (VSC) based farm structure is usually established on an AC generation system which means the generated AC power has to be passed DC section by utilizing own conversion device. Therefore, the profile can be involved a large switching loss compared with other DC based distribution network as described in [28,29]. Due to this issue, there are several studies for DC farm topologies to reduce the efficiency problem in power supply [30]. In addition, conventional DC based sources have extended available farm scale in terms of the number and level of the classified voltage. These trends build a hybrid concept in terms of operation environment which has an advantage of not only the structural efficiency of transmission system but also the power utilization [31]. When composing a combine system with the wind-energy systems in the offshore regions, in particular, the tidal linear generator is being aggressively considered as a suitable cooperating device owing to their effectiveness and popularity [32].
The proposed scheme in this paper is focused on previously composed wave–offshore generating structure. The shared platform is currently being composed and has an AC/DC hybrid electrical structure as it is based on several wind and wave generators. The platform has been evaluated as suitable for ESS application because it has sufficient place for handling various sources. When the ESS is attached to the structure, the device will be located in central subsystem, and have to be managed to improve the reliability of following the orders of the grid operator. To manage the order with ESS, the DC structure of the system is a major consideration because each generator in this section is not utilized as a controllable unit by operator. The power control plan except for tripping units for supporting previous mechanical controller can be tested by dynamic movement of wave system (it can be hired in other hybrid generation form such as PV-wind).
The total capacity of the wave–offshore combined generation system can be improved than that of the single renewable source, and it demands an advanced curtailment scheme for maintaining the grid stability which is a main consideration of TSO [33]. Therefore, such systems should first consider mechanical curtailment scheme with the pitch-controller for the wind system but additional applications are still required. The ESS application, which is normally applied in DC section, is also being taken into account due to its usability; however, the generated power flow through the long DC section could lead to an unstable voltage condition at the interconnection point. As a various power generation including compensating device is expected in this common DC link, advanced technology will be required based on DC network analysis for maintaining the system performance.

2.2. DC-Link Characteristics

2.2.1. Bipolar-Type DC Network

Conventional DC-integrated sections are composed using the unipolar-type or bipolar-type inverters as described in [34,35]. Since every component in the unipolar-type is connected directly between the “positive” and “negative” conductors, the number of power electronic devices utilized can be reduced considerably. In the previous configurations, therefore, unipolar-type DC sections were composed to reduce the electrical configuration cost. However, nowadays, the power-conversion capacity is higher than that of the previous electrical transfer systems; therefore, the preference for bipolar-type inverters is increasing. The transmission capacity of the bipolar-type is greater than that of the unipolar-type at the same voltage level, and it can provide a wider range of voltage levels. As the required transmission capacity has been growth comparing with that of previous electrical grid, this topology has further advantages as described in [36], and also seems to bring benefits for low voltage based distribution network [37,38]. Furthermore, the cost reduction of the power electronic devices derives the bipolar-type configuration because the system offers larger transmission capacity and has many advantages [39]. In terms of voltage stability, VSC based converter devices with high capacity also have strong point of extracting demanded reactive power to support connected utility grid [26]. A bipolar-type DC distribution network is being considered in composing and analyzing process of the DC based wave-ESS application.

2.2.2. DC-Based Generators

Since a few of the renewable sources utilizing multifeed systems for reducing construction costs use directly integrated capacitor devices, dynamic performance according to the generated current flow causes continuous voltage variations. This paper mainly considers the full-converter-type wind generator and the PMSLG for the wave system as the main devices for the proposed verification process. It generates active current according to the applied environmental factor and the generated profile will be transferred to the utility grid by utilizing own conversion devices [40,41]. The wave generators composed at the combined system, as mentioned above, are designed to adapt a multifeed topology [42]. Generic generation capacity in the wave-generation system is slightly lower than that of the wind turbine, and it allows an electrically shared section in the point of interconnection for several generators. Owing to its capacity, in addition, the wave system does not consider additional curtailment methods in the general state and normally follows the maximum power point tracking (MPPT) option. If we consider other controllable devices like variable resistance or storage system, the DC link is suitable for those combined systems. When estimating the PCS for composed system, the demanded capacity calculation can consider optimized power control pattern in the DC network. Therefore, the required PCS capacity for combined system can be reduced by focusing on the expected peak supply profile of the subsystem (the PCS for AC subsystem should consider aggregate value of connected devices) [43]. This method can derive the optimized PCS utilization for the combined generation system in order to replace the inverters in each connection points. Furthermore, these results can contribute to the reduction of the number of power electronic devices, which can affect the total capacity and cost of the rectifiers required in the DC generation system. Therefore, the proposed scheme will discuss the profile management plan while maintaining the voltage level for each DC section to ensure that all combined sources can follow both the charging and discharging orders from the operator.
Figure 2 presents the integrated devices in the target combined system with DC power. In this system, each PMSLG that extracts power from offshore is interlinked with a common integrated part. Through DC voltage control of the grid-side inverter, the entire system can transfer the generated power to the utility grid. As described in the figure, general ESS topologies are composed based on a single connection. Therefore, the DC voltage can be directly utilized in the reference-generation processes. The proposed combined system considers equipping a supercapacitor-based ESS with the previous DC network, and a fast calculation for the real-time control signal is required. Before handling the voltage signal, a general power-flow analysis should be conducted. The injected power flow, which is highlighted with the red arrow in the figure, can be represented by the sum of each generator’s profile and the incurred sectional loss as follows:
P wave = n = 1 N P n n = 1 N P loss ( n )
where Pwave is the total output power of the wave generators, Pn is the output power of the nth wave generator, Ploss is the loss in the cable components, and N is the total number of wave generators in the farm. The sectional loss can be defined as follows:
P loss = r n n + 1 P n n + 1 2 V n 2
where Pnn+1 is the real power that flows from bus n to bus n + 1, rnn+1 is the resistance between bus n and bus n + 1, and Vn is the bus voltage magnitude.
The PMSLG-based wave generator extracts real power according to the magnetic variation generated due to the vertical movement of connected buoy. Similar to the power production by wind turbine, the applied converter utilizes the designed curve for power coefficient. The linear generator chooses the power point within the operational range to extract maximum available power. There is no curtailment option in the linear-based generator, and every integrated generator has to follow the MPPT control mode if it is not utilizing additional compensation solutions. This paper considers the ESS application in the DC link as a power suppliable device. If the extracted output power of the combined generation system exceeds the designated order by the operator, the ESS is activated to support the pitch controller based on the previously designed mutual curtailment plan. Therefore, we have to set the total DC flow as a fixed value and utilize it in the entire circuit-analysis plan for the process designed by expecting voltage fluctuations as described in Equation (3). The DC current flow also has to be set, by using the ordered quantity, for utilization in the voltage-analysis process, as shown in Equation (4):
P dc = P w a v e + P E S S , | P E S S | S d c d c
i dc = g eq · P order
where Pdc is the real power reference for the DC system, PESS is the referred quantity for storage, Sdc–dc is the capacity of the DC converter for the storage system, idc is the current flow at the inverter, and geq is the equivalent admittance of the PCS.
As a number of generators are expected to be composed into a single system, the DC-side voltage variation will be completely dependent on the output profile of the wave generators. When the operator has to handle the applied ESS for charging or discharging, the consideration about induced voltage variation have to be precise.

2.2.3. ESS Application

An ESS utilization for renewable energy sources should not only consider the voltage conditions at the connection point but also restrain the output profile in accordance with the order from the system operator. In general, the ESS in an industrial power system has a standardized system design, which is connected to a point of common coupling (PCC). It is composed for supplying stored energy to connected utility through individually composed converter, which is for converting DC power. The voltage-focused solutions in previous research utilized the specified voltage value as a limitation signal, which was used to decide whether the ESS was attached or detached to the target network. Figure 3 describes these concepts with a flywheel-based ESS solution, which employs a superconducting rotational mass [41]. This application usually depends on a bidirectional controller to control the flow and decide whether to charge or discharge by sensing the DC-section voltage. The controller operates the ESS at voltages outside a designated range of voltage. That is, the ESS absorbs energy when the voltage is higher than the upper limit and stores energy when it is lower than the lower limit. Within this topology, the controller manages the voltage level strictly with in the designated range but the transferred power at the ESS cannot be defined as a specified value as illustrated in the figure. On the other hand, the proposed plan stores the accurate real power quantity by using it as a reference value rather than the voltage signal. A bidirectional power-conversion system is utilized into the ESS topology with focused on designated power and related modified values.
The ESS has to consider measured generation profile, and limit based on the applied PCS power capacity. The output profiles of each system can be represented as shown in Equations (5) by using power flow at PCC.
P P C C = P W T + P d c
where PPCC is the power flows at the PCC, and PWT is the wind power output. The constraint in the limit process can be defined as follows:
max P d c S p c s 2 Q p c s 2
where Spcs is the power-conversion capacity of the main PCS, and Qpcs is the reactive power profile of the main PCS.
The designed ESS operation is focused on allocating the stored surplus power on the power demand situation, which is predicted by state analysis. Both charging and discharging condition can be represented with a single equation as follows:
P E S S ( t ) = P r e f P W T ( t ) P w a v e ( t )
where Pref is the designated order of the entire generation system. Under the constraint section, the ESS compensating operation is required, and the induced control signal depends on the previous state. Both charging and discharging signals have to consider utilized capacity as a constraint, as shown in Equation (8).
P E S S ( t + 1 ) = P r e f P W T ( t ) P w a v e ( t ) ( 0 < P E S S S E S S )
where SESS is the power-conversion capacity of the converter for ESS. The ESS mainly responds to the real power gap between the generated power and the demanded order. To confirm the power consumption, the state of charge (SOC) of the ESS should be checked during the simulation process. The pre-phase SOC should be considered at every second. The SOC of the ESS is described as follows:
S O C ( t + 1 ) = { S O C ( t ) E E S S ( t ) η E max ( P E S S ( t ) 0 ) S O C ( t ) + η E E S S ( t ) E max ( P E S S ( t ) < 0 )
where EESS is the electrical energy calculated by PESS(t), and Emax is the maximum electrical energy of the ESS. The ESS control scheme is applied according to the presence of power profile, and the SOC is used as the main control value in the scheme.
In summary, the wind turbines basically follow the MPPT. However, in the case of excess active power in comparison with the load demand, active pitch control is used for sufficient wind velocity to shed off the aerodynamic energy by turning off the blades. When the power from wind turbines must be curtailed using pitch angle control, the amount of charging quantity is firstly calculated to modify the pitch angle control. The discharge condition does not help the pitch controller directly. Nevertheless, to handle the operating condition of ESS continuously, it should be considered while system operation.

2.3. PCS Control

2.3.1. Real Power Control Scheme

The natural power captured by the generator depends on its power coefficient, which is given by the statistical data. The mechanical systems of a PMSG and PMSLG are composed considering previous discussions [44]. The real power in a PMSG is obtained by differentiating the power coefficient, which is a function of both the tip-speed ratio and the blade pitch angle. Within the available range of pitch angles, the generator-side converter for turbine selects specified power point as a control signal to extract the most of an available power. When the rotor speed goes beyond the rated speed of the wind turbine, the pitch controller is activated to reduce the power extracted from wind. As mentioned above, the PMSLG extracts the profile for each environmental factor and the power has to be transferred to the utility grid through common DC cable. Both generation systems utilize a three-level neutral point clamped (NPC) voltage-source converter [45]. Each rotor-side convertor follows the MPPT control independently, and the DC voltage controller that is located in the grid-side convertor for transferring real power can be represented as a single equivalent circuit for system modeling including the pulse-width modulated (PWM) conversion process.
The aim of this paper is an appropriate power compensation process that can generate a positive effect in the transient response of the power curtailment-compensation processes. The DC current can be represented by dividing the generated power with the DC voltage, as shown in Equation (10).
i d c 1 = P d c v d c
where idc1 is the calculated DC current at the rotor side, vdc is the DC voltage in the capacitor bank. The grid-side DC current can also be obtained in the same manner, and the voltage-variation signal is generated by an integrator using the differential value between the DC currents on both sides, which is adopted as shown in Equation (11).
d v d c d t = 1 C d c ( i d c 1 i d c 2 )
where vdc is the DC-link voltage, Cdc is the value of the DC capacitor, idc2 is the calculated DC current at the grid side. The power controller of each PCS should deal with the follow-up control structure for the reference current. In order to extract the current reference signal correctly, the proposed ESS controller adopts an additional control block to improve the signal-generation accuracy.

2.3.2. DC Controller for Wave System

A detailed switching analysis of the ESS-combined generation farm has been studied in this research. Figure 4 shows the DC-section structure of the generation farm and the related control scheme. A supercapacitor (SC) storage system is described in the structure and is expected to be connected to the grid through the power-conversion system including the boost chopper devices (The SC in this paper was designed by based on equivalent sources to have general characteristics in the aspect of the power, and response time). Along with the DC–DC converter for the storage system, the composed wave system is also directly attached to the DC link. A parallel current flow will be imposed in this section, and the autonomously measured values are used for the voltage predictor as highlighted in the figure.
The measured DC voltage is used in the grid-side converter controller, and the grid side controller (real power control for PCS) is independent from the real power control flow for the DC power profile management section (including ESS). These control flows are caused by composing the grid-side converter with a rotor-side convertor separately to follow the MPPT processes. Since the ESS has been composed based on single system, the real power command for the ESS can ignore the voltage-change prediction process. The real power controller, including the ESS-management system, directly uses the calculated voltage value to decide the final reference signal for the current controller. Finally, the supervisory system can receive the modified value as an electrically controllable quantity and handle the mechanical curtailment value for responding with the system operator.
The modification process mainly applied in the reference-calculation process is included (highlighted blocks in gray) in Figure 4. In summary, the final modified controller updates the real power order and exchanges the modified value with the upper management system. The figure describes the d–q transform of the three-phase variables and applies the decoupled double-synchronous reference-frame phase-locked loop (PLL) method, which extracts the positive sequences at the measured values [46].

3. Power Control Theory

3.1. Circuit Analysis

The grid-side voltage at the front of the inverter is maintained at a designated level. However, the electrical conditions at each connection point fluctuate between unexpected ranges according to the induced generating profiles. This variation can be expected by performing a circuit analysis of the current flow. The simplified circuit about composed DC section can be represented through equivalent component as illustrated in Figure 5.
The DC section would be composed with several rectifiers for wave generator, main PCS for subsystem, and DC/DC convertor for introduced storage device. The rectifiers can be located by composing a number of arrays in the floating structure. Therefore, the wave generation system should be expressed by dividing into some different groups in the circuit analysis. Each connection point including the collector can be represented as a node for analyzing the output profiles of the wave generators. To consider various composition of wave generation system, the circuit analysis is performed by considering several different arrays. With the ESS component, the node equation can be redesigned, as shown in Equation (12):
| g 1 + g 12 g 12 0 0 0 g 12 g 2 + g 12 + g 10 0 0 g 10 0 0 g 3 + g 34 g 34 0 0 0 g 34 g 4 + g 34 + g 30 g 30 0 g 10 0 g 30 g 10 + g 30 + g e q + g E S S | | V 1 V 2 V 3 V 4 V d c | = | 0 0 0 0 i d c |
where gn is the equivalent admittance of the wave generator.
In the equivalent circuit, several admittance components are defined to reflect the variation of power profile. The components have to be changed according to the electrical condition. In order to impose the changed condition in the control plan, the modification process adopts an iterative calculation method based on a fixed current value for the generator. Since the derived generator depends on the specified voltage, the wave generators will be transformed to negative resistances at state of power extraction. The equivalent admittances of each wave generator can be defined by the power profile and the voltage at the connection node (Equation (13)):
g n = P n V n 2
The admittance value for the applied ESS is additionally required through the equation. The reference signal generating process can be achieved with the iteration process to predict voltage variation according to the ESS profile. The updated values are transferred and utilized in additional modification process. Since the output section of PCS is fixed with current value, the finalized voltage level for other node can be derived. The iteration process can be aggregated using Equation (14).
[ V ] = [ g ] 1 × [ I ]

3.2. Advanced Curtailment Plan

In the case of the discharging process, the proposed prediction plan can be directly utilized for calculating the signal. However, the curtailment process demands additional modifications for the entire data flow because it has a cooperative relation with the wind generators.
The added sections are described in Figure 6. By utilizing previously calculated signals, an additional modified controller can be activated to enhance the accuracy. With the proposed voltage-prediction method, the mentioned supervisory controller can obtain a more realistic controllable value for both mechanical and electrical values.

4. Simulation

4.1. Simulation Configuration

By considering a layout for the proposed combined system, a simulation was configured using PSCAD. Figure 7 shows a layout of the combined generation system, which utilizes the linked DC section. Each wind turbine in the generation farm is a 2-MVA VSC interfaced system. As described above, the wave generation system includes 24 PMSLG units and adopts a 4-MVA PCS system. The location data of the layout are also described in the figure. The PCC information, which is related to the transmission line for the utility grid, is shown in Table 1 and the cable parameters are imposed according to the numerical data designed by the cable manufacturer [47].
The composed simulation mainly includes curtailment condition to handle the exceed power than reference signal. The reference signal is designed to change, while the configured simulation time and the entire simulation time are set to 15 s (including the transient section for start-up). To check both operating condition, designated fluctuation section was extracted from historical wind data. By assuming that the order from TSO is changed every few seconds, two order changes were imposed in the simulation.
The case studies consider harsh wind-variation conditions by utilizing the measured weather data. To compare between basic pitch control and ESS support applications, specified limitation signals will be applied to both control systems. Additionally, the ESS discharging process will be included in the simulation analysis to confirm the accuracy of the proposed ESS operation plan for the discharging process.
Consequently, the simulation will gradually progress from the non-limitation condition to the proposed method. First, the pitch-control application will be compared to the non-curtailment condition. Pitch control only considers mechanical curtailment when the generated profile exceeds the order. Since the control is based on the mechanical characteristics, errors related to control accuracy are expected. Next, the ESS will be applied along with pitch control to support the curtailment process in the designated section. The ESS control is performed with two different control modes, regarding the decision about the charging and discharging quantity according to the order, irrespective of whether the voltage-prediction method is applied or not. Both control modes focus on supporting the wind system’s mechanical limitations within the internally available capacity of the PCS. When the operator sets the reference for the entire generation system, the entire generation system including ESS should follow the quantity until the next signal is imposed. Table 2 includes applied parameters for the case studies.

4.2. Simulation Results

Figure 8 and Figure 9 show curve comparison between the non-pitch and pitch-applied case studies including the total generation profile. The measured wind and wave data are applied over the entire simulation time. As both generation profiles change continuously, some control-demanding sections were generated as shown in the figure. By focusing on the peak power-profile section, we establish a curtailment plan for enhancing the control response capability of an operator. The blue curve in Figure 8 show the original power curve without pitch control. Since both wind and wave systems generate peak power in the same sections, a significant peak power section is generated as highlighted in the figure. To reduce this power variation, mechanical control is applied as illustrated in Figure 9 over the entire combined generation system. As described in the above section, however, only the wind turbines can respond to the curtailment signal due to the absence of a power-control plan in the wave-generation systems. The total power flows for PCC are controlled as the wind turbine limits its own power profile (curtailed power is described separately in the wind profile’s curve). Nonetheless, several control errors exist in the target section due to its low response rate.
Case 2 was designed to analyze the performance of ESS. Figure 10 presents the curve comparison between the two control conditions. The analysis considers not only the charging section for power curtailment but also the discharging section to confirm the operational enhancement in the discharging process. Compared with Case 1, effective power curtailment processes were performed using the ESS charging method. The fast response of ESS reduces control errors and makes the entire pitch-control smooth in the targeted section.
We apply the proposed voltage-prediction method described in Section 3 in the normal ESS application analysis. In the proposed method, realistic voltage-calculation processes were performed based on the DC power flow. Compared with the proposed method, as shown in Figure 10, there are some unexpected power-control errors in the previous ESS operation plans in case of both charging and discharging process. These conditions were caused by the inappropriate control signals used to extract power from the ESS.
The power profiles from ESS are presented in Figure 11 to analyze the situation. The charging and discharging quantities, in the two different operation plans, are slightly different as shown in the figure. These changes occur in both compensating processes. Overall, the discharge profile of the previous control method is slightly higher than that of the proposed method. The reason is that the transferred power from the DC section has increased, when compared to the peak-power condition. The highlighted analysis sections in Figure 10, which show the highest differences in terms of the power profile for the entire process, are specifically illustrated with DC voltages in Figure 12.
The current profiles are managed within the rated capacity. The differences between the two control plans are generated based on whether the controllers consider the voltage fluctuations by the real power order or not. In the charging section, the additional controller does not seem to provide significant enhancements in the ESS operation plan. However, the wind turbine can use the modified signal, which can reduce the mechanical control load in the turbine operation. In the discharging section, the profiled currents are quite different as described in Figure 12b. General operation plans do not consider the increased DC voltages, and unexpected variations are generated as described in Figure 10. The modified solution handles these mismatches and extracts more stable profiles. The total mismatch in the power profiles is presented in Table 3. The difference between the demanded control quantity and the profile is reduced in both control modes, and the reliability of the profiled quantity is improved significantly in terms of energy compensation. The error generated by the ESS application, especially in the discharging condition, also decreases in the designated section.
The SOC curves are compared with calculated value according to the imposed order (black), as illustrated in Figure 13. The graphs about general (blue) and proposed (red) ESS operation methods were represented in the figure. In the graphs, the variation due to charging and discharging is not significant because the simulation was based on short-term analysis. The red curve, nevertheless, which represents the modified operating condition according to the proposed plan, shows lower difference than general ESS operation plan. Even though the mitigation of error on the basis of order is not significant, the improvement can be useful to the system owner in terms of ESS management process regarding SOC. The realistic controller will improve the prediction process about remain quantity for ESS, and it can help active support regarding real power curtailment method in terms of operational accuracy. Most of all, it can lead further opportunities in SOC prediction plan which related with middle-term ESS operation plan.

5. Conclusions

This paper suggested an advanced power-control algorithm for the combined generation systems to support the power-management situation. To perform the ESS operation with effective reference order, a voltage-prediction method was formulated and adopted in the designed generation system. Through case studies, performance improvements regarding the real power management that respond to the TSO order were verified. In accordance with the changed order by operator, the main controller predicted the voltage variation with consideration of real power profiles from each unit. The precise controller would be useful when applying ESS on further large-scale combined generation system. It is clear that the combined generation farm would adopt certain power-control methods for helping the management process. The pitch controller is still the main curtailment application in the proposed study. However, large-scaled generation system with diverse generators has possibility in terms of power management plan. Since the designed generation system is based on a large-scale DC platform, the active support plan with ESS can be a reasonable solution including the cost issues. With the proposed control, the power-curtailment process is enhanced as the controller can manage more realistic control signals.

Acknowledgments

This work was supported by the Power Generation & Electricity Delivery Core Technology Program of KETEP grant (No. 20131020000100) and by the National Research Foundation of Korea (NRF) grant (No. NRF-2013R1A2A2A01067762) funded by the Korea government.

Author Contributions

The voltage prediction method was proposed by Seungmin Jung. The experiment results were collected and analyzed by Seungmin Jung, Yong-Tae Yoon, and Gilsoo Jang.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Kusiak, A.; Zheng, H.; Song, Z. Short-Term Prediction of Wind Farm Power: A Data Mining Approach. IEEE Trans. Energy Convers. 2009, 24, 125–136. [Google Scholar]
  2. Morales, A.; Robe, X.; Sala, M.; Prats, P.; Aguerri, C.; Torres, E. Advanced grid requirements for the integration of wind farms into the Spanish transmission system. IET Renew. Power Gener. 2008, 2, 47–57. [Google Scholar] [CrossRef]
  3. Jialiang, Y.; Pádraig, F.L.; Peter, J.D.; Pengfei, W.; Philip, C.T. Robust Scheduling Scheme for Energy Storage to Facilitate High Penetration of Renewables. IEEE Trans. Sustain. Energy 2015, 7, 797–807. [Google Scholar]
  4. Goran, M.; Adel, N.; Ehsan, G.; Eduard, M. Lithium-Ion Capacitor Energy Storage Integrated with Variable Speed Wind Turbines for Power Smoothing. IEEE J. Emerg. Sel. Top. Power Electron. 2013, 1, 287–295. [Google Scholar]
  5. Miao, L.; Wen, J.; Xie, H.; Yue, C.; Lee, W. Coordinated control strategy of wind turbine generator and energy storage equipment for frequency support. IEEE Trans. Ind. Appl. 2015, 51, 2732–2742. [Google Scholar] [CrossRef]
  6. Focken, U.; Lange, M.; Monnich, K.; Waldl, H.; Beyer, H.G.; Luig, A. Short-term prediction of the aggregated power output of wind farms—A statistical analysis of the reduction of the prediction error by spatial smoothing effects. J. Wind Eng. Ind. Aerodynam. 2002, 90, 231–246. [Google Scholar] [CrossRef]
  7. Wang, X.Y.; Mahinda Vilathgamuwa, D.; Choi, S.S. Determination of Battery Storage Capacity in Energy Buffer for Wind Farm. IEEE Trans. Energy Convers. 2008, 23, 868–878. [Google Scholar] [CrossRef]
  8. Quanyuan, J.; Haisheng, H. Wavelet-Based Capacity Configuration and Coordinated Control of Hybrid Energy Storage System for Smoothing out Wind Power Fluctuations. IEEE Trans. Power Syst. 2013, 28, 1363–1372. [Google Scholar]
  9. Peng, W.; Zhiyong, G.; Lina, B.T. Operational Adequacy Studies of Power Systems with Wind Farms and Energy Storages. IEEE Trans. Power Syst. 2012, 27, 2377–2384. [Google Scholar]
  10. Hans, B.; José, A.D.-N. A Probabilistic Method for Energy Storage Sizing Based on Wind Power Forecast Uncertainty. IEEE Trans. Power Syst. 2011, 26, 1651–1658. [Google Scholar]
  11. Abdallah, T.; Mamadou, B.C.; Brayima, D. Energy Management in the Decentralized Generation Systems Based on Renewable Energy—Ultracapacitors and Battery to Compensate the Wind/Load Power Fluctuations. IEEE Trans. Ind. Appl. 2015, 51, 1817–1827. [Google Scholar]
  12. Hartmann, B.; Dan, A. Cooperation of a Grid-Connected Wind Farm and an Energy Storage Unit—Demonstration of a Simulation Tool. IEEE Trans. Sustain. Energy 2012, 3, 49–56. [Google Scholar] [CrossRef]
  13. Jin Woo, C.; Shin Young, H.; Mum Kyeom, K. Hybrid operation strategy of wind energy storage system for power grid frequency regulation. IET Gener. Transm. Distrib. 2016, 10, 736–749. [Google Scholar]
  14. Dominic, D.B.-H.; Gareth, A.T.; Chris, A.S.; Malcolm, R.I. Flow Batteries for Enhancing Wind Power Integration. IEEE Trans. Power Syst. 2012, 27, 1690–1697. [Google Scholar]
  15. Fengbing, L.; Kaigui, X.; Jiangping, Y. Optimization and Analysis of a Hybrid Energy Storage System in a Small-Scale Standalone Microgrid for Remote Area Power Supply (RAPS). Energies 2015, 8, 4802–4826. [Google Scholar]
  16. Ross, M.; Hidalgo, R.; Abbey, C.; Joos, G. Energy storage system scheduling for an isolated microgrid. IET Renew. Power Gener. 2011, 5, 117–123. [Google Scholar] [CrossRef]
  17. Jin-Hong, J.; Jong-Yul, K.; Hak-Man, K.; Seul-Ki, K.; Changhee, C.; Jang-Mok, K.; Jong-Bo, A.; Kee-Young, N. Development of hardware in-the-loop simulation system for testing operation and control functions of microgrid. IEEE Trans. Power Electron. 2010, 25, 2919–2929. [Google Scholar] [CrossRef]
  18. Le, H.T.; Santoso, S.; Nguyen, T.Q. Augmenting wind power penetration and grid voltage stability limits using ESS: Application design, sizing, and a case study. IEEE Trans. Power Syst. 2012, 7, 161–171. [Google Scholar] [CrossRef]
  19. Jia, H.; Fu, Y.; Zhang, Y.; He, W. Design of hybrid energy storage control system for wind farms based on flow battery and electric double-layer capacitor. In Proceedings of the 2010 Asia-Pacific Power and Energy Engineering Conference, Chengdu, China, 28–31 March 2010.
  20. Fernando, A.I.; Jordi, P.-Q.; Fernando, D.B. Control of a Supercapacitor Energy Storage System for Microgrid Applications. IEEE Trans. Energy Convers. 2013, 28, 690–697. [Google Scholar]
  21. Wandhare, R.G.; Agarwal, V. Novel integration of a PV-wind energy system with enhanced efficiency. IEEE Trans. Power Electron. 2015, 30, 3638–3649. [Google Scholar] [CrossRef]
  22. Seungmin, J.; Hyun-Wook, K.; Gilsoo, J. Adaptive power control method considering reactive power reserve for wave-offshore hybrid power generator system. Energy Procedia 2014, 61, 1703–1706. [Google Scholar]
  23. Beerens, J. Offshore Hybrid Wind-Wave Energy Converter System. Master’s Thesis, Delft University of Technology, Delft, The Netherlands, 26 February 2010. [Google Scholar]
  24. Boo, S.Y.; Kim, K.H.; Lee, K.; Park, S.; Choi, J.S.; Hong, K. Design challenges of a Hybrid Platform with multiple wind turbines and wave energy converters. In Proceedings of the 21st Offshore Symposium, Houston, TX, USA, 16 February 2016.
  25. Aubry, J.; Ben Ahmed, H.; Multon, B. Sizing Optimization Methodology of a Surface Permanent Magnet Machine-Converter System over a Torque-Speed Operating Profile: Application to a Wave Energy Converter. IEEE Trans. Ind. Electron. 2012, 59, 2116–2125. [Google Scholar] [CrossRef]
  26. Seungmin, J.; Gilsoo, J. Development of an Optimal Power Control Scheme for Wave-Offshore Hybrid Generation Systems. Energies 2015, 8, 9009–9028. [Google Scholar]
  27. Byungdoo, J.; Hyun, K.; Heechan, K.; Hansang, L. Development of a Novel Charging Algorithm for On-board ESS in DC Train through Weight Modification. J. Electr. Eng. Technol. 2014, 9, 1795–1804. [Google Scholar]
  28. Abbey, C.; Joos, G. A Stochastic Optimization Approach to Rating of Energy Storage Systems in Wind-Diesel Isolated Grids. IEEE Trans. Power Syst. 2009, 24, 418–426. [Google Scholar] [CrossRef]
  29. Francesco, B.; Giancarlo, G.; Edoardo, S. Modal Analysis of a Railway Braking Resistor. In Proceedings of the 27th International Modal Analysis Conference, Orlando, FL, USA, 9–12 February 2009.
  30. Yang, J.; Fletcher, J.E.; O’Reilly, J. Multiterminal DC wind farm collection grid internal fault analysis and protection design. IEEE Trans. Power Del. 2010, 25, 2903–2912. [Google Scholar] [CrossRef]
  31. Stoutenburg, E.D.; Jacobson, M.Z. Reducing Offshore Transmission Requirements by Combining Offshore Wind and Wave Farms. IEEE J. Ocean. Eng. 2011, 36, 552–561. [Google Scholar] [CrossRef]
  32. Wang, L.; Li, H.W.; Wu, C.H.T. Stability Analysis of an Integrated Offshore Wind and Seashore Wave Farm Fed to a Power Grid Using a Unified Power Flow Controller. IEEE Trans. Power Syst. 2013, 28, 2211–2221. [Google Scholar] [CrossRef]
  33. Kim, K.-H.; Lee, K.; Sohn, J.M.; Park, S.; Choi, J.-S; Hong, K. Conceptual Design of 10MW Class Floating Wave-Offshore Wind Hybrid Power Generation System. In Proceedings of the Twenty-Fifth International Offshore and Polar Engineering Conference, Kona, HI, USA, 21–26 June 2015.
  34. Sannino, A.; Postiglione, G.; Bollen, M.H.J. Feasibility of a DC network for commercial facilities. IEEE Trans. Ind. Appl. 2003, 39, 1499–1507. [Google Scholar] [CrossRef]
  35. Kaipia, T.; Salonen, P.; Lassila, J.; Partanen, J. Possibilities of the low voltage DC distribution systems. In Proceedings of the NORDAC 2006 Conference, Stockholm, Sweden, 30 August 2006.
  36. Starke, M.R.; Tolbert, L.M.; Ozpineci, B. AC vs. DC distribution: A loss comparison. In Proceedings of the 2008 IEEE/PES Transmission and Distribution Conference and Exposition, Chicago, IL, USA, 21–24 April 2008; pp. 1–7.
  37. Salonen, P.; Kaipia, T.; Nuutinen, P.; Peltoniemi, P.; Partanen, J. An LVDC distribution system concept. In Proceedings of the Nordic Workshop on Power and Industrial Electronics (NORPIE/2008), Espoo, Finland, 9–11 June 2008.
  38. Kakigano, H.; Miura, Y.; Ise, T.; Momose, T.; Hayakawa, H. Fundamental characteristics of DC microgrid for residential houses with cogeneration system in each house. In Proceedings of the Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, Pittsburgh, PA, USA, 20–24 July 2008; pp. 1–8.
  39. Lee, H.; Shin, B.Y.; Han, S.; Jung, S.; Park, B.; Jang, G. Compensation for the Power Fluctuation of the Large Scale Wind Farm using Hybrid Energy Storgage Applications. IEEE Trans. Appl. Supercond. 2012, 22, 5701904. [Google Scholar] [CrossRef]
  40. Hong, Y.; Eriksson, M.; Castellucci, V.; Boström, C.; Waters, R. Linear generator-based wave energy converter model with experimental verification and three loading strategies. IET Renew. Power Gener. 2016, 10, 349–359. [Google Scholar] [CrossRef]
  41. Zhang, L.; Sun, K.; Xing, Y.; Feng, L.; Ge, H. A Modular Grid-Connected Photovoltaic Generation System Based on DC Bus. IEEE Trans. Power Electron. 2011, 26, 523–531. [Google Scholar] [CrossRef]
  42. Chen, C.S.; Chuang, H.J.; Fan, L.J. Design of main transformer capacity for electrified railway power systems. In Proceedings of the International Conference on Power System Technology, Perth, Australia, 4–7 December 2000; Volume 1, pp. 311–316.
  43. Jackson, L.; Heldwein, M.L. Operation and Control-Oriented Modeling of a Power Converter for Current Balancing and Stability Improvement of DC Active Distribution Networks. IEEE Trans. Power Electron. 2011, 26, 877–885. [Google Scholar]
  44. Eriksson, M.; Waters, R.; Svensson, O.; Isberg, J.; Leijon, M. Wave power absorption: Experiments in open sea and simulation. J. Appl. Phys. 2007, 102, 084910. [Google Scholar] [CrossRef]
  45. Bunjongjit, K.; Kumsuwan, Y.; Sriuthaisiriwong, Y. An implementation of three-level BTB NPC voltage source converter based-PMSG wind energy conversion system. In Proceedings of the TENCON 2014 IEEE Region 10 Conference, Bangkok, Thailand, 22–25 October 2014; pp. 1–5.
  46. Rodriguez, P.; Pou, J.; Bergas, J.; Candela, J.I.; Burgos, R.P.; Boroyevich, D. Decoupled double synchronous reference frame PLL for power converters control. IEEE Trans. Power Electron. 2007, 22, 584–592. [Google Scholar] [CrossRef]
  47. 6–36kV Medium Voltage Underground Power Cables. Available online: http://www.nexans.co.uk/UK/files/Underground%20Power%20Cables%20Catalogue%2003-2010.pdf (accessed on 18 August 2016).
Figure 1. Power support concept of ESS for generation farm.
Figure 1. Power support concept of ESS for generation farm.
Sustainability 08 00818 g001
Figure 2. DC-link description including control purpose.
Figure 2. DC-link description including control purpose.
Sustainability 08 00818 g002
Figure 3. Voltage limitation solution for flywheel application.
Figure 3. Voltage limitation solution for flywheel application.
Sustainability 08 00818 g003
Figure 4. Structural analysis of the DC-based generation farm including ESS.
Figure 4. Structural analysis of the DC-based generation farm including ESS.
Sustainability 08 00818 g004
Figure 5. Equivalent circuit of DC section.
Figure 5. Equivalent circuit of DC section.
Sustainability 08 00818 g005
Figure 6. Modified control diagram for power curtailment.
Figure 6. Modified control diagram for power curtailment.
Sustainability 08 00818 g006
Figure 7. Entire system layout for designed simulation.
Figure 7. Entire system layout for designed simulation.
Sustainability 08 00818 g007
Figure 8. Power profile of the designed generation system without pitch control (Case 1).
Figure 8. Power profile of the designed generation system without pitch control (Case 1).
Sustainability 08 00818 g008
Figure 9. Power profile of the designed generation system with pitch control (Case 1).
Figure 9. Power profile of the designed generation system with pitch control (Case 1).
Sustainability 08 00818 g009
Figure 10. Power profile of the designed generation system (Case 2).
Figure 10. Power profile of the designed generation system (Case 2).
Sustainability 08 00818 g010
Figure 11. Charging and discharging quantities of SC.
Figure 11. Charging and discharging quantities of SC.
Sustainability 08 00818 g011
Figure 12. Detailed current compensation quantities for applied SC and DC voltage variations: (a) absorbed current quantity in the charging control section (8.15 to 8.65 s); and (b) extracted current quantity in the discharging control section (14.1 to 14.6 s).
Figure 12. Detailed current compensation quantities for applied SC and DC voltage variations: (a) absorbed current quantity in the charging control section (8.15 to 8.65 s); and (b) extracted current quantity in the discharging control section (14.1 to 14.6 s).
Sustainability 08 00818 g012
Figure 13. SOC variation in the case studies.
Figure 13. SOC variation in the case studies.
Sustainability 08 00818 g013
Table 1. Numerical data for the simulation.
Table 1. Numerical data for the simulation.
Specific DataValueUnit
Rated AC voltage of inner system22.9kV
Rated DC voltage of wave system4kV
Operating voltage range (DC)3.5–4.5kV
Rated energy of SC200kWh
Rated power of SC800kW
Kpf (SC)1MW/Hz
Rated power of wind turbine1.75 (2 units)MW
Inertia constant (wind turbine)1.27s
Rated power of wave generator0.15 (24 units)MW
Short-circuit ratio of utility grid15
X/R ratio of utility grid15
Table 2. Reference signal change in case studies.
Table 2. Reference signal change in case studies.
Comparison CaseApplied ControlFirst OrderSecond Order
Pitch ControlESS SupportVoltage PredictionDuration (s)Constraint (MW)Duration (s)Constraint (MW)
1---2 to 6-6 to 15-
O--Below 4Below 5
2OO-Above 3
Below 4
Above 3
Below 5
OOO
Table 3. Numerical results for imposed order and profiled quantity.
Table 3. Numerical results for imposed order and profiled quantity.
ControlSC ModeAccumulative Demand (kWh)Accomplished Quantity (kWh)Gapm (kWh)Error (%)
GeneralCharging3.3473.2040.1434.26
Discharging2.3442.2340.114.69
ProposedCharging3.1173.0430.0742.37
Discharging2.3172.3060.0110.77

Share and Cite

MDPI and ACS Style

Jung, S.; Yoon, Y.-T.; Jang, G. Adaptive Curtailment Plan with Energy Storage for AC/DC Combined Distribution Systems. Sustainability 2016, 8, 818. https://0-doi-org.brum.beds.ac.uk/10.3390/su8080818

AMA Style

Jung S, Yoon Y-T, Jang G. Adaptive Curtailment Plan with Energy Storage for AC/DC Combined Distribution Systems. Sustainability. 2016; 8(8):818. https://0-doi-org.brum.beds.ac.uk/10.3390/su8080818

Chicago/Turabian Style

Jung, Seungmin, Yong-Tae Yoon, and Gilsoo Jang. 2016. "Adaptive Curtailment Plan with Energy Storage for AC/DC Combined Distribution Systems" Sustainability 8, no. 8: 818. https://0-doi-org.brum.beds.ac.uk/10.3390/su8080818

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop