Numerical Investigation of a Novel Heat Pipe Radiant Floor Heating System with Integrated Phase Change Materials †

Faculty of Civil Engineering and Building Services, “Gheorghe Asachi” Technical University of Iasi-Romania, Blvd. Mangeron, No. 1, 700050 Iasi, Romania
*
Author to whom correspondence should be addressed.
Presented at the 14th International Conference on Interdisciplinarity in Engineering—INTER-ENG 2020, Târgu Mureș, Romania, 8–9 October 2020.
Published: 11 December 2020

Abstract

:
The subject of buildings energy efficiency has gained increased interest in modern society. Recently, researchers aiming to reduce the energy demand of buildings have studied the implementation of phase change materials (PCMs) in various building elements. At the same time, researchers studied the implementation of unconventional technologies such as heat pipes (HP) in the buildings’ heating system. This paper combines both of these technologies in order to take advantage of the thermal storage properties of PCMs and overcome their reduced conductivity with heat pipes. Through computational fluid dynamics (CFD) simulations, this paper studies and highlights that with the implementation of a PCM, a reduction of the daily energy demand is achieved through the increase in the discharge phase time.

1. Introduction

Worldwide, energy consumption is increasing, and buildings require over 40% of the global energy demand. In terms of emissions, buildings produce over 30% of the global net greenhouse gas emissions as a result of the increase in the indoor residence time and subsequently the surge in the requirements for indoor thermal environments and the heavy increase in urbanization, deforestation, and global climate change [1].
The increase in the global energy demand is one of the key reasons for the degradation and unstable development of our planet. This increase in the worldwide energy demand is a result of the rise in population coupled with better accessibility to energy of developing countries. Currently, a big portion of the global energy production is represented by fossil fuels; this has a drastic impact on the environment due to the greenhouse gas emissions. Since energy demand and the gross domestic product (GDP) growth of a country are linked, a policy towards the reduction of the energy demand would have a negative impact towards the GDP, and since the growth of renewable energies is slower than the rise in energy demand, an increase in energy efficiency can have a significant impact [2,3,4].
On a European scale, in order to overcome the drawbacks and to reduce the impact energy has on the climate, the European Parliament adopted a legislation in 2012 with the aim to reduce CO2 emissions by 20% by 2020 in comparison to the values recorded in 1990. Studies showed that this goal would not be met by the proposed deadline, and as a result, the target year was set to 2030, but the required reductions values were imposed to 27% for the energy demand and 40% for the CO2 emissions [5].
PCMs are special materials that are capable of storing increased quantities of thermal energy in comparison to other materials through the phase transition process. There are two main ways of storing thermal energy, in the form of sensible heat, when the temperature of the material increases, the material phase being unchanged during this process, and in the form of latent heat, when the material receives thermal energy, changing its phase in the process, the materials that store latent heat being called phase change materials. PCMs can be classified in three categories: solid–liquid PCMs, solid–gas PCMs and liquid–gas PCMs, but among these categories, solid–liquid PCMs are the most commonly used [6,7,8].
In order to address the global concerns regarding topics such as energy consumption, energy efficiency, and sustainable buildings, researchers interest towards PCM has increased drastically in the last decades, highlighted by the number of publications and research articles, Figure 1.
The interest in phase change materials in the scientific community is highlighted by the increased interest towards their applications in buildings and their integration in various building elements such as walls [9,10,11,12,13], windows [14,15], ceilings [16,17], floors [18,19,20,21,22,23].
Heat pipes are highly efficient heat exchangers, being able to rapidly transfer high quantities of thermal energy across a small temperature gradient. A key advantage of heat pipes is their capability to quickly transfer heat from one of their ends to the other one with a reduced heat loss in comparison to other materials; thus, heat pipes can be regarded as “superconductors” [24].
Heat pipe applications in buildings also include the possibility to integrate them in glazed facades to take advantage of the solar radiation [25] to recover the waste heat [26].
The objective of this research is the study of a HPHS with an original design and analyzing the advantages and disadvantages obtained through integrating a PCM into this system.

2. Research Methodology

To achieve the objective of the research paper, studies for an originally designed heat pipe floor heating system were performed using the ANSYS Fluent CFD software in order to simulate the correct operation of two floor heating systems, a floor heating system that uses heat pipes as heat exchangers, and the same heat pipe heating system with an integrated phase change material layer.
For the study, a floor heating system with heat pipes was designed; the heat pipes heat the floor from two opposing sides in order to ensure a uniform distribution of the temperature for the floor.
As a primary agent, water was chosen, being the most commonly used working fluid for floor heating systems. After using this system, two cases were analyzed, the system heating a regular concrete floor and the system heating a concrete floor with an integrated PCM layer; the PCM layer is represented between two layers of concrete, because due to the phase transition process, shape stabilization is a problem that needs to be resolved.
The research is based on multiple CFD simulations using the ANSYS STUDENT 2019 R3 package and addressed the heat transfer of both cases during the heating and cooling cycles in order to demonstrate the system feasibility. The 3D modelling was realized with the DesignModeler part of the package, as highlighted in the horizontal and vertical sections in Figure 2 and Figure 3.
The analyzed models’ geometry and dimensions are as follows:
  • first concrete layer 500 × 500 × 20/10 mm
  • PCM layer 500 × 500 × 10 mm
  • second concrete layer 500 × 500 × 30 mm
  • rectangular heat pipes 10 × 10 mm, 510 mm in length
  • two-circular distributors 22 mm in diameter, 500 mm in length.
In terms of mesh initialization, sizing, and quality, linear element order with a 5 mm element size was imposed, and for the mesh quality, a target skewness of 0.8 was set, as presented in Figure 4.
To have an accurate representation of CFD simulation for the models in the case of the PCM model apart from the energy equation, the solidification/melting model was used.
For the phase change material, a paraffin, RT 21 HC, produced by Rubitherm Technologies GmbH [27] was considered, because it presents impressive purity and specific composition, which translates to increased latent heat capacity with a small temperature range, the performance of the material remaining high for the phase change cycles as a result of the long lifetime of the material. The paraffin properties are shown in Table 1.
The reference temperature for the water inlet was considered to be 35°C, because it is a standard operating temperature for the working fluid in an underfloor heating system.
The initial temperature during the heating phase of the system was considered 10 °C.
In terms of the cooling phase, the temperature of 10 °C was imposed on the upper surface.

3. Results and Discussion

In order to analyze the thermal storage capacity of both systems, complete charging/discharging cycles were simulated.
The numerical simulation shows that in this case, the heating phase of the HPHS reached a convergence temperature after 30 min and 40 s. The heat pipes’ thermal properties are highlighted through the second section, presenting that the heat pipes start heating the concrete layer in less than 1 min (Figure 5). The cooling phase for the HPHS lasted 68 min (Figure 6).
In the case where a PCM layer was integrated, from the liquid fraction during the heating phase the PCM melting can be viewed; the PCM started melting around after 500 s, and it is fully melted after 4800 s; from the point the PCM starts melting, it takes almost 72 min for the PCM to fully melt (Figure 7). The system is fully heated after 127 min (Figure 8).
During the cooling process, the PCM properties are evidenced through the liquid fraction; the PCM starts melting solidifying in under 10 min, but the solidification period is prolonged, reaching a fully solid state, 99.7%, after 135 min (Figure 9).
In case of the second heating system, with a layer of PCM, the discharge period is drastically prolonged in comparison to the system without the PCM; the system is fully cooled down after over 290 min, proving that PCMs can be used in buildings to increase the thermal energy storage (Figure 10).
From the figures, the thermal properties of the HPHS can be observed during the heating and cooling phase, and through adding a PCM layer, the thermal properties of the PCMHPHS change, the second system having a greatly increased discharge phase, but as a result, the heating phase is also increased. Due to an increase in both the heating and cooling time for the second system in comparison to the HPHS, a direct comparison of the heating and cooling time was not used; thus, an analysis on the number of cycles in a 24 h period was used, while recording the charging and discharging time.
Following the numerical simulations, the time for each case was recorded for the heating and cooling cycles (Figure 11) and used to make a comparison between the two systems.
Considering the heating and cooling time for both systems to make a comparison in terms of energy consumption, 24 h uninterrupted cycles were analyzed; thus, the HPHS would require 14.59 cycles over a 24 h period, and the PCMHPHS required 3.45 cycles.
Afterwards, knowing the number of cycles and the heating time, the number of daily hours the heating source would operate is 7.46 h/day for the heat pipe floor heating system and 7.30 h/day for the PCM integrated heat pipe floor heating system.
The results highlight that the HPHS can be a viable alternative to a classic heating system; furthermore, by integrating a PCM into the structure of the floor, a further reduction in the number of working hours for the heating source can be achieved.
In order to further verify these results, further research will be realized through studying the system in comparison to various classic floor heating systems on real scale models and an analysis on the efficiency of different types of PCMs in floor heating systems.

4. Conclusions

The originally designed heat pipe floor heating system harnesses the properties of heat pipes in order to heat the floor in an efficient way and through integrating a PCM in this system a prolonged discharge period can be achieved, highlighting that both technologies have great potential to reduce the energy consumption in buildings.
The proposed heat pipe floor heating system requires a number of 7.46 h/day for heating, while the PCM integrated system requires 7.30 h/day. Apart from the reduction in the required time for heating through integrating a PCM, a further reduction in costs can be achieved through programming and automation if the heating cycles are set during off-peak periods, taking advantage of the PCM thermal energy storage properties.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

HPHeat Pipe
PCMPhase Change Material
HPHSHeat Pipe Heating System
PCMHPHSPhase Change Material integrated Heat Pipe Heating System
TTemperature, [°C]

References

  1. Cao, X.; Dai, X.; Liu, J. Building energy-consumption status worldwide and the state-of-the-art technologies for zero-energy buildings during the past decade. Energy Build. 2016, 128, 198–213. [Google Scholar] [CrossRef]
  2. Akalpler, E.; Shingil, M.E. Statistical reasoning the link between energy demand, CO2 emissions and growth: Evidence from China. Procedia Comput. Sci. 2017, 120, 182–188. [Google Scholar] [CrossRef]
  3. Fotis, P.; Karkalakos, S.; Asteriou, D. The relationship between energy demand and real GDP growth rate: The role of price asymmetries and spatial externalities within 34 countries across the globe. Energy Econ. 2017, 66, 69–84. [Google Scholar] [CrossRef]
  4. IEA. Global Energy Review 2020. IEA. Paris. Available online: https://www.iea.org/reports/global-energy-review-2020 (accessed on 7 February 2020).
  5. Cambeiro, F.P.; Armesto, J.; Bastos, G.; López, J.I.P.; Barbeito, F.P. Economic appraisal of energy efficiency renovations in tertiary buildings. Sustain. Cities Soc. 2019, 47, 101503. [Google Scholar] [CrossRef]
  6. Belz, K.; Kuznik, F.; Werner, K.F.; Schmidt, T.; Ruck, W. Thermal energy storage systems for heating and hot water in residential buildings. In Advances in Thermal Energy Storage Systems; Woodhead Publishing: Sawston, UK, 2015; pp. 441–465. [Google Scholar]
  7. Lin, Y.; Jia, Y.; Alva, G.; Fang, G. Review on thermal conductivity enhancement, thermal properties and applications of phase change materials in thermal energy storage. Renew. Sustain. Energy Rev. 2018, 82, 2730–2742. [Google Scholar] [CrossRef]
  8. Magendran, S.S.; Khan, F.S.A.; Mubarak, N.M.; Vaka, M.; Walvekar, R.; Khalid, M.; Abdullah, E.C.; Nizamuddin, S.; Karri, R.R. Synthesis of organic phase change materials (PCM) for energy storage applications: A review. Nano-Struct. Nano-Obj. 2019, 20, 100399. [Google Scholar] [CrossRef]
  9. Kong, X.; Wang, L.; Li, H.; Yuan, G.; Yao, C. Experimental study on a novel hybrid system of active composite PCM wall and solar thermal system for clean heating supply in winter. Sol. Energy 2020, 195, 259–270. [Google Scholar] [CrossRef]
  10. Wang, H.; Lu, W.; Wu, Z.; Zhang, G. Parametric analysis of applying PCM wallboards for energy saving in high-rise lightweight buildings in Shanghai. Renew. Energy 2020, 145, 52–64. [Google Scholar] [CrossRef]
  11. Rathore, P.K.S.; Shukla, S.K. Potential of macroencapsulated pcm for thermal energy storage in buildings: A comprehensive review. Constr. Build. Mater. 2019, 225, 723–744. [Google Scholar] [CrossRef]
  12. Pirasaci, T. Investigation of phase state and heat storage form of the phase change material (PCM) layer integrated into the exterior walls of the residential-apartment during heating season. Energy 2020, 207, 118176. [Google Scholar] [CrossRef]
  13. Bejan, A.S.; Catalina, T. The implementation of Phase Changing Materials in energy-efficient buildings. Case Study: EFdeN Project. Energy Procedia 2016, 85, 52–59. [Google Scholar] [CrossRef]
  14. Li, S.; Zou, K.; Sun, G.; Zhang, X. Simulation research on the dynamic thermal performance of a novel triple-glazed window filled with PCM. Sustain. Cities Soc. 2018, 40, 266–273. [Google Scholar] [CrossRef]
  15. Hu, Y.; Heiselberg, P.K. A new ventilated window with PCM heat exchanger—Performance analysis and design optimization. Energy Build. 2018, 169, 185–194. [Google Scholar] [CrossRef]
  16. Weinläder, H.; Klinker, F.; Yasin, M. PCM cooling ceilings in the Energy Efficiency Center—Regeneration behaviour of two different system designs. Energy Build. 2017, 156, 70–77. [Google Scholar] [CrossRef]
  17. Yasin, M.; Scheidemantel, E.; Klinker, F.; Weinläder, H.; Weismann, S. Generation of a simulation model for chilled PCM ceilings in TRNSYS and validation with real scale building data. J. Build. Eng. 2019, 22, 372–382. [Google Scholar] [CrossRef]
  18. Yun, B.Y.; Yang, S.; Cho, H.M.; Chang, S.J.; Kim, S. Design and analysis of phase change material based floor heating system for thermal energy storage. Environ. Res. 2019, 173, 480–488. [Google Scholar] [CrossRef]
  19. Lu, S.; Xu, B.; Tang, X. Experimental study on double pipe PCM floor heating system under different operation strategies. Renew. Energy 2020, 145, 1280–1291. [Google Scholar] [CrossRef]
  20. Faraj, K.; Faraj, J.; Hachem, F.; Bazzi, H.; Khaled, M.; Castelain, C. Analysis of underfloor electrical heating system integrated with coconut oil-PCM plates. Appl. Therm. Eng. 2019, 158, 113778. [Google Scholar] [CrossRef]
  21. Guo, J.; Jiang, Y.; Wang, Y.; Zou, B. Thermal storage and thermal management properties of a novel ventilated mortar block integrated with phase change material for floor heating: An experimental study. Energy Convers. Manag. 2020, 205, 112288. [Google Scholar] [CrossRef]
  22. Mays, A.E.; Ammar, R.; Mahamad, H.; Akroush, M.A.; Hachem, F.; Khaled, M.; Ramadan, M. Using phase change material in under floor heating. Energy Procedia 2017, 119, 806–811. [Google Scholar] [CrossRef]
  23. Devaux, P.; Farid, M.M. Benefits of PCM underfloor heating with PCM wallboards for space heating in winter. Appl. Energy 2017, 191, 593–602. [Google Scholar] [CrossRef]
  24. Reay, D.A.; McGlen, R.J.; Kew, P.A. Heat Pipes, Theory, Design and Applications, 6th ed.; Elsevier: Oxford, UK, 2014. [Google Scholar]
  25. Burlacu, A.; Lăzărescu, C.D.; Ciocan, V.; Verdeș, M.; Balan, M.C.; Şerbănoiu, A.A. CFD Heat Transfer Analysis for Heat Pipes Integration into Buildings with Glazed Façades. Procedia Eng. 2017, 181, 658–665. [Google Scholar] [CrossRef]
  26. Burlacu, A.; Sosoi, G.; Vizitiu, R.Ș.; Bărbuță, M.; Lăzărescu, C.D.; Ciocan, V.; Șerbănoiu, A.A. Energy efficient heat pipe heat exchanger for waste heat recovery in buildings. Procedia Manuf. 2018, 22, 714–721. [Google Scholar] [CrossRef]
  27. PCM RT-LINE. Wide-Ranging Organic PCM for Your Application. Available online: https://www.rubitherm.eu/en/index.php/productcategory/organische-pcm-rt (accessed on 7 February 2020).
Figure 1. Worldwide PCM research articles between 1996 and 2019.
Figure 1. Worldwide PCM research articles between 1996 and 2019.
Proceedings 63 00015 g001
Figure 2. A vertical section of the models highlighting the different layers of both models: (a) The HPHS (b) The PCMHPHS: 1. First concrete layer. 2. PCM layer. 3. Second concrete layer. 4. Rectangular heat pipes.
Figure 2. A vertical section of the models highlighting the different layers of both models: (a) The HPHS (b) The PCMHPHS: 1. First concrete layer. 2. PCM layer. 3. Second concrete layer. 4. Rectangular heat pipes.
Proceedings 63 00015 g002
Figure 3. A horizontal section through the heat pipes and distributor. 1. Hot water inlet. 2. Distributors. 3. Rectangular heat pipes.
Figure 3. A horizontal section through the heat pipes and distributor. 1. Hot water inlet. 2. Distributors. 3. Rectangular heat pipes.
Proceedings 63 00015 g003
Figure 4. Model mesh sizing and initialization.
Figure 4. Model mesh sizing and initialization.
Proceedings 63 00015 g004
Figure 5. A section through the HPHS during the heating phase.
Figure 5. A section through the HPHS during the heating phase.
Proceedings 63 00015 g005
Figure 6. A section through the HPHS during the cooling phase.
Figure 6. A section through the HPHS during the cooling phase.
Proceedings 63 00015 g006
Figure 7. A section through the PCMHPHS during the heating phase, displaying the PCM liquid fraction over time.
Figure 7. A section through the PCMHPHS during the heating phase, displaying the PCM liquid fraction over time.
Proceedings 63 00015 g007
Figure 8. A section through the PCMHPHS during the heating phase.
Figure 8. A section through the PCMHPHS during the heating phase.
Proceedings 63 00015 g008
Figure 9. A section through the PCMHPHS during the cooling phase, displaying the PCM liquid fraction over time.
Figure 9. A section through the PCMHPHS during the cooling phase, displaying the PCM liquid fraction over time.
Proceedings 63 00015 g009
Figure 10. A section through the PCMHPHS during the cooling phase.
Figure 10. A section through the PCMHPHS during the cooling phase.
Proceedings 63 00015 g010
Figure 11. The results for the heating/cooling cycles.
Figure 11. The results for the heating/cooling cycles.
Proceedings 63 00015 g011
Table 1. RT 21 HC Material properties.
Table 1. RT 21 HC Material properties.
CharacteristicsValueUnits
Melting area20–23[°C]
Solidification area19–21[°C]
Heat storage capacity190[kJ/kg]
Specific heat capacity2[kJ/kg·K]
Density solid (at 15 °C)0.88[kg/L]
Density liquid (at 25 °C)0.77[kg/L]
Heat conductivity0.2[W/(m·K)]
Max. operation temperature45[°C]
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Brănoaea, M.; Burlacu, A.; Ciocan, V.; Verdeș, M.; Vizitiu, R.Ș. Numerical Investigation of a Novel Heat Pipe Radiant Floor Heating System with Integrated Phase Change Materials. Proceedings 2020, 63, 15. https://0-doi-org.brum.beds.ac.uk/10.3390/proceedings2020063015

AMA Style

Brănoaea M, Burlacu A, Ciocan V, Verdeș M, Vizitiu RȘ. Numerical Investigation of a Novel Heat Pipe Radiant Floor Heating System with Integrated Phase Change Materials. Proceedings. 2020; 63(1):15. https://0-doi-org.brum.beds.ac.uk/10.3390/proceedings2020063015

Chicago/Turabian Style

Brănoaea, Marius, Andrei Burlacu, Vasilică Ciocan, Marina Verdeș, and Robert Ștefan Vizitiu. 2020. "Numerical Investigation of a Novel Heat Pipe Radiant Floor Heating System with Integrated Phase Change Materials" Proceedings 63, no. 1: 15. https://0-doi-org.brum.beds.ac.uk/10.3390/proceedings2020063015

Article Metrics

Back to TopTop