Next Article in Journal
Titanium-Doped Mesoporous Silica with High Hydrothermal Stability for Catalytic Cracking Performance of Heavy Oil
Next Article in Special Issue
Special Issue on “Modeling, Analysis and Control Processes of New Energy Power Systems”
Previous Article in Journal
Cost Optimal Production-Scheduling Model Based on VNS-NSGA-II Hybrid Algorithm—Study on Tissue Paper Mill
Previous Article in Special Issue
Time-of-Use Pricing Strategy of Integrated Energy System Based on Game Theory
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Predictive Commutation Failure Suppression Strategy for High Voltage Direct Current System Considering Harmonic Components of Commutation Voltage

1
School of Electrical Engineering, Southeast University, Nanjing 210096, China
2
State Grid Xinjiang Electric Power Co., Ltd., Urumqi 830011, China
*
Author to whom correspondence should be addressed.
Submission received: 22 August 2022 / Revised: 10 October 2022 / Accepted: 11 October 2022 / Published: 13 October 2022
(This article belongs to the Special Issue Modeling, Analysis and Control Processes of New Energy Power Systems)

Abstract

:
The commutation failure of high voltage direct current (HVDC) systems could lead to unstable operation of the alternating current/direct current (AC/DC) hybrid power grid. The commutation voltage distortion caused by harmonics is a considerable but unclear factor of commutation failure. According to the control switching process of HVDC systems, the commutation voltage-time area method is employed to analyze and reveal the influence mechanism of harmonic components of commutation voltage on first and subsequent commutation failures. Considering the distortion characteristics of AC voltage, a predictive commutation failure suppression strategy considering multiple harmonics of commutation voltage is proposed. In this strategy, the new extinction angle and the zero-crossing offset angle after voltage distortion are calculated considering the harmonic components so as to obtain the compensation margin of the lag trigger angle by combining the correction margin with the voltage change rate. Moreover, the tuning method of parameters of extinction angle and voltage prediction variables are provided. Finally, a case study based on CIGRE standard HVDC system is performed and analyzed by using power systems computer-aided design (PSCAD) software. Compared with the International Council on Large Electric systems (CIGRE) standard test model and traditional commutation failure prevention (CFPREV) control model, the results verify that the proposed strategy can effectively reduce the risk of first and subsequent commutation failures and improve the sensitivity of CFPREV control.

1. Introduction

High voltage direct current (HVDC) transmission with grid converters are widely used in long-distance power transmission, underground and submarine cable power transmission and regional power grid interconnection due to their advantages, such as long transmission distance, small transmission loss and good economy. They are an important means to solve the uneven distribution of energy load in China [1,2,3]. Semi-controlled thyristors are mostly used as the converter elements. When the AC system at the sending and receiving ends fails, it is easy to cause commutation failure [4]. The commutation failure will lead to a sharp increase in DC current and a sharp drop in DC voltage. In serious cases, it will cause a DC blocking fault, which will interrupt the DC transmission power and eventually crash the system [5,6]. If the fault is not cleared in time after the first commutation failure, it is easy to cause subsequent commutation failure. After the subsequent commutation failure, the DC voltage, current, power and other electrical quantities change dramatically, which will have multiple impacts on the AC system. When the AC system is weak, it will cause a DC blocking fault and even cascading failure, bringing great risks and challenges to the safe and stable operation of AC/DC hybrid system [7].
There are many reasons for commutation failure. Considering the fundamental voltage, the increase of DC current, the decrease of AC voltage, the increase of commutation reactance and the decrease of lead trigger angle β will lead to the decrease of extinction angle γ. When γ is less than the inherent critical trigger angle γmin, the commutation failure will occur [8,9]. After an AC system fault, the harmonic component and phase angle offset of commutation voltage will also cause commutation failure. Therefore, voltage distortion is also an important reason for commutation failure [10]. At present, the optimal control of HVDC transmission is mostly based on the protection control modules of converter stations, including voltage dependent current order limiter (VDCOL), commutation failure prevention (CFPREV), constant extinction angle control and power coordination control. The control system has a poor response ability to commutation voltage distortion at present [11,12].
Most of the existing methods to suppress commutation failure are based on improving the converter topology or optimizing the system control strategy [13]. Connecting capacitors and inductors in series and parallel on both sides of the AC transformer and adding reactive power compensation devices to change the structure of the converter can improve the ability to suppress commutation failure to a certain extent. However, adding power electronic devices has the disadvantages of high investment cost and high operation risk [14]. VSC-HVDC uses fully controlled devices to construct converters that are not dependent on AC system commutation, which can effectively inhibit the subsequent commutation failures, but it is not economical and operable [15,16]. Therefore, the optimization control strategy comes more from improving VDCOL and CFPREV modules, with less investment and greater operability. The basic principle of CFPREV is that when an AC fault is detected, a trigger angle margin is generated as the decrease of the lag trigger angle to achieve early triggering and reduce the risk of commutation failure. The harmonic component of the converter bus in the inverter side can cause frequent fluctuation of the CFPREV output, which leads to abnormal fluctuation of DC power. By distinguishing the zero-sequence component of inrush current and AC fault, the output of CFPREV can be controlled to be constant [17]. The literature [18] points out that CFPREV can exacerbate the negative impact of the initial fault voltage angle on commutation failure. When the fault phase voltage crosses zero, the single-phase short-circuit fault will significantly delay the start of CFPREV. Based on this, a calculation method of commutation failure probability is proposed. The literature [19] designs a coordinated controller, which can change the output of CFPREV according to the change of the extinction angle of the remote inverter, so that the trigger angle can be adaptively adjusted. But the accuracy is affected by signal transmission. The existing CFPREV control module has the problems of low output margin accuracy and poor flexibility of parameter adjustment, which may aggravate the subsequent commutation failure in the actual system.
In the process of commutation failure, the control behavior of the controller is affected by many factors. Therefore, the comprehensive effect of various electrical quantities after fault should be considered in the formulation of control and protection strategies. By suppressing the drop of DC current after faults, a control strategy for optimizing VDCOL is proposed in the literature [20], which can suppress AC overvoltage to a certain extent, but the effect of commutation failure suppression needs to be verified. The literature [21] points out that the waveform distortion of commutation voltage is the main reason for commutation failure under slight fault. By considering the time-domain effects of harmonics and DC current, the literature [22] proposes a prediction method of commutation voltage and current to realize the prediction of commutation failure, but the fault suppression strategy needs further study. A trigger angle prediction algorithm is proposed in the literature [23] by using the harmonic component to calculate the extinction angle to detect whether the commutation failure occurred. The commutation-time area method can be used to analyze the influence of harmonics on the commutation process. In the literature [24], the control parameters of each harmonic are calculated by using the commutation-time area method, and an additional harmonic control module is added to VDCOL module. But it cannot suppress the first commutation failure. Based on the commutation-time area, the dynamic adjustment of the extinction angle command value is realized in the literature [25] and the virtual resistor is used to trigger VDCOL in advance, but the suppression effect for some fault scenarios needs to be verified.
In view of the above research deficiencies, this paper analyzes the influence mechanism of the harmonic component of the commutation voltage on the commutation failure and proposes a predictive commutation failure suppression strategy considering the multiple harmonics of the commutation voltage based on the variation characteristics of the AC voltage after the fault. When it is applied to different AC fault scenarios, it can reduce the risk of the first and subsequent commutation failures more sensitively by considering the harmonic component of the voltage distortion and the dynamic change of the AC voltage. Finally, the simulation comparison between the proposed strategy and the traditional CFPREV strategy shows that it can reduce the number of commutation failures.
The main contributions of this paper are summarized as follows:
  • Based on the commutation-time area method, the critical commutation area of harmonic components in fault recovery process is provided. And the mechanism of first and subsequent commutation failures is analyzed in combination with the change of electrical quantity.
  • A novel commutation failure suppression strategy considering multiple harmonics of commutation voltage and voltage prediction is proposed. The new extinction angle and zero-crossing offset angle after voltage distortion are given based on the harmonic components, so as to obtain the compensation margin of the lag trigger angle by combining the correction margin with the voltage change rate.
  • Tuning method of parameters of extinction angle and voltage prediction variables are provided. Extensive case studies based on a CIGRE standard HVDC system are performed and analyzed and compared with a CIGRE standard test model and commutation failure prevention (CFPREV) control model. Simulation results verify that the proposed strategy can suppress the first and subsequent commutation failures and reduce the number of commutation failures effectively when different degrees of faults occur.
The rest of this paper is organized as follows: Section 2 analyzes the principle of the inverter under the influence of harmonics. In Section 3, a commutation failure suppression strategy considering harmonics and voltage prediction is proposed. Based on the strategy, the tuning method of parameters are provided in Section 4. Simulation results based on PSCAD software and discussion are presented in Section 5. Finally, we conclude this paper in Section 6.

2. Commutation Failure and Harmonic Influence

The topology of the line-commutated converter based HVDC (LCC-HVDC) system is depicted in Figure 1, including sending-end grid, rectifier station, DC transmission lines, inverter station and receiving-end grid. Semi-controlled thyristors are widely used as the converter elements in HVDC, which can easily cause commutation failure at the receiving-end grid. Commutation failure is a common fault for HVDC systems, and it is easily affected by harmonics of commutation voltage during the AC fault occurrence. Therefore, it is meaningful to investigate the principle of commutation failure affected by the harmonics.

2.1. The Principle of Commutation under the Influence of Harmonics

When the AC fault occurs in the sending and receiving end power grid, the converter station near the fault point will fail at commutation. The essence of commutation failure is that the extinction angle is smaller than the minimum extinction angle γmin (about 7°) corresponding to the recovery blocking time of the converter valve at the reverse voltage (about 0.4 s for high-power thyristor). In engineering, the converter unit is generally a six-pulse converter. Figure 2a analyzes the commutation process of thyristor VT3 to VT5, and Figure 2b is the simplified diagram of the inverter commutation process.
Before commutation, the thyristor VT3 and VT4 are turned on to form a DC current circuit. When VT5 receives the trigger pulse, VT3 begins to convert to VT5 and the three thyristors are simultaneously turned on. Ignoring the resistance of the large capacity transformer, the default three-phase commutation inductance is equal. The positive directions of current ia, ib and ic are the conduction directions of thyristor. The positive directions of voltage ua, ub and uc are shown in Figure 2a. The voltage equation during the commutation from valve VT3 to valve VT5 can be written as [26]:
L c d i b d t L c d i c d t = u b + u c
where Lc is the commutation inductance. The commutation voltage ubc can be represented by the line voltage amplitude UL on the side of the commutation valve:
u bc = U L sin ( ω t )
Considering the effect of flat wave reactor, the DC current Id before and after commutation is basically unchanged. By substituting id = ib + ic into Formula (1) and integrating both sides from t1 to t2, the expression of commutation voltage time area (S) can be obtained:
S = 2 L c I d = t 1 t 2 u bc d t = ( π β ) / ω ( π γ ) / ω U L sin ( ω t ) d t
where t1 is the trigger time and can be expressed by (πβ)/ω; t2 is the end time of commutation, which can be expressed by (πγ)/ω.
By further simplification, the following formula can be obtained:
γ = arccos ( cos β + 2 ω L c I d U L )
The critical extinction angle γmin is the minimum extinction angle required for normal turn-off of the thyristor. If the extinction angle corresponding to the commutation end time t2 is the critical extinction angle γmin, namely (πγmin)/ω, the maximum commutation area that the system can provide is defined as S max = ( π γ min ) / ω ( π β ) / ω U L sin ( ω t ) d t . The required commutation area for normal commutation of the system is defined as Sneed = 2LcId. When the required commutation area Sneed > Smax, the extinction angle γ will be less than the critical extinction angle γmin, the system cannot provide enough of a commutation margin, and commutation failure will occur. When the commutation voltage is distorted, the voltage distortion waveform is shown in Figure 3. During normal operation of the system, the commutation voltage is U. After an AC fault, the voltage waveform is distorted, the commutation voltage changes from U to U′, the amplitude decreases and the phase angle shifts φ. According to the parameter changes in Figure 3, the commutation area before the fault is Sx + Sy. After the fault, the commutation area provided by the system is reduced to Sy due to the distortion of voltage waveform. In order to provide sufficient a commutation margin, it is necessary to increase the commutation area Sz. At this time, γ decreases to γ′. When the extinction angle is smaller than the critical extinction angle γmin, commutation failure occurs.
After the voltage distortion occurs, the commutation voltage ubc will contain the harmonic components:
u bc = U 1 L sin ( ω t ) + n = 2 N U n L sin ( n ω t + φ n )
Substitute Formula (5) into Formula (3) can get the following formula:
2 L c I d = ( π β ) / ω ( π γ ) / ω [ U 1 L sin ( ω t ) + n = 2 N U n L sin ( n ω t + φ n ) ] d t = S 1 + n = 2 N S n
where S1 and Sn are defined as the commutation area provided by the fundamental voltage and the harmonic voltage, respectively, and further simplification of Formula (6) can be obtained:
S 1 = U 1 L [ cos ( π β ) cos ( π γ ) ]
S n = U n L n [ cos ( n π n β + φ n ) cos ( n π n γ + φ n ) ]
The condition for the normal switching off of thyristors is as follows: the commutation area provided by the system is larger than the required commutation area. Therefore, under the influence of harmonics, the condition for the normal commutation of the system is as follows:
S need S 1 + n = 2 N S n

2.2. Influence of Harmonics on Subsequent Commutation Failure

When faults occur in the AC system of the HVDC transmission system, the control system at the rectifier and inverter side switches the control blocks to increase the trigger angle and ensure a certain commutation margin. As shown in Figure 4, the basic control blocks of the inverter side of the HVDC transmission system include the voltage dependent current order limiter (VDCOL), constant current (CC), constant extinction angle (CEA) and current error control (CEC) [27].
In Figure 4, Udi and Idi are the measured values of DC voltage and DC current on the inverter side after passing through the first-order low-pass filter; Iord1 is the DC current instruction of the upper level; when the DC voltage is lower than the low-voltage current limiting control threshold value, VDCOL starts and outputs the DC current command value Iord; γmin and γref are the minimum measured extinction angle and the reference value of extinction angle (15°), respectively; when the DC current reaches the current deviation control starting threshold, CEC outputs ΔγCEC, which is added to the input of CEA as an increase. In the actual control of the system, CEA and CC control are started at the same time, and output βCEA and βCC, respectively. The maximum values of the two angles are taken as the output of the inverter side advance trigger angle βi, and αi is obtained through transformation.
When a short-circuit fault occurs in the AC system on the inverter side, the second commutation failure will occur if the fault degree is deeper. Take the CIGRE standard test system as an example, the three-phase short-circuit grounding fault on the inverter side is set up. The starting time of the fault is 2 s and lasts for 0.2 s. The changes of electrical quantities during the fault process are shown in Figure 5.
On the one hand, it can be seen from Figure 5 that in the fault recovery process of the first commutation failure (process between green dotted lines), the advance trigger angle βcc > βCEA, and the system switches from CEA control to CC control. After the first commutation failure, the DC voltage decreases and the DC current rises sharply, which makes the inverter side enter the VDCOL control and the DC current command value decreases. When the DC current decreases to a certain extent, the system is normally commutated, and the DC current command value Iord rises slowly. Therefore, in the process of fault recovery, the DC current Id increases slowly with Iord, resulting in the increase of commutation demand area Sneed. On the other hand, in the process of fault recovery, AC voltage and DC current are basically restored to the standard value, but a large number of harmonic components appear at the receiving end. Therefore, it can be preliminarily judged that the subsequent commutation failure is not due to the commutation voltage drop caused by insufficient reactive power, but the commutation voltage distortion caused by harmonics. The critical area of commutation voltage time (γ is 7°) calculated by Formulas (7) and (8) in the fault process is shown in Figure 6. S1 is the commutation area of fundamental voltage, S1–15 and S2–15 are the commutation areas of 1st–15th and 2nd–15th harmonic voltages, respectively. It can be seen that after the fault occurs, although the 2nd–15th harmonic commutation area increases, the fundamental voltage commutation area S1 drops greatly, which causes the S1–15 to drop sharply, so that the Formula (9) cannot be satisfied and the subsequent commutation failure of the system occurs. The waveforms of critical commutation area S1 and S1–15 before the first and subsequent commutation failure are amplified, as shown in Figure 6b,c. One can see that before the first commutation failure occurs, the harmonic deteriorates the commutation condition and the insufficient commutation margin leads to commutation failures. In the process of fault recovery after the first commutation failure, the harmonics reduce the commutation area, and, finally, the subsequent commutation failure occurs.

3. Suppression Strategy Considering Harmonics and Voltage Prediction

The key idea of CFPREV is that after the AC system fault is detected, the reduction of the output angle margin is triggered in advance to increase the extinction angle γ, so as to avoid the abnormal extinction of the thyristor and the commutation failure of the system. The basic control block diagram of CFPREV is shown in Figure 7, including zero sequence detector and abc-αβ three-phase fault detector. The traditional CFPREV has the disadvantages of single detection, insufficient prevention accuracy and lack of flexibility in parameter adjustment. Under some fault conditions, it may even aggravate the fault and cause subsequent commutation failure [28,29].
In order to alleviate the problem of poor speed and sensitivity caused by traditional CFPREV, a commutation failure suppression strategy considering harmonic and voltage prediction is proposed.

3.1. Suppression Strategy Considering Multiple Harmonics of Commutation Voltage

The commutation voltage distortion caused by harmonics will lead to voltage amplitude decrease, phase angle change and even zero-crossing offset. The three-phase short-circuit grounding fault at the inverter side is set in the CIGRE standard test system.
The fault time is 2 s and the duration is 0.2 s. The voltage distortion rate of 2nd–15th and 2nd–31st harmonics (the fundamental voltage distortion rate is 100%) can be obtained by the fast Fourier transform (FFT) decomposition of the commutation voltage, as shown in Figure 8. It can be seen that the voltage has a large harmonic distortion after the fault occurs, and the distortion rate reaches 42.4%. After the fault, the second large harmonic distortion rate appeared, reaching 26.1% at 2.24 s. The two harmonic distortions are both caused by the saturation of converter transformer caused by the substantial increase of DC current. By amplifying the waveform of Figure 8, it can be seen that there is little difference between 2nd–15th harmonic distortion rate and 2nd–31st harmonic distortion rate, the maximum is only 2.07%. Therefore, the subsequent calculation can consider the harmonic number to 15 times.
According to Formulas (7) and (8), the commutation voltage-time area corresponding to fundamental wave and each harmonic can be calculated and the total commutation area can be obtained by the summation:
n = 2 N S n = n = 2 N U n L n [ cos ( n π n β + φ n ) cos ( n π n γ + φ n ) ]
The extinction angle γ can be obtained by Formula (4). Harmonics not only bring changes in the voltage amplitude and phase, but also cause zero crossing offset. If the offset angle is Δφ, the extinction angle should meet the Formula (11) to turn off normally:
arccos ( cos β + 2 ω L c I d U L ) Δ φ γ min
It is assumed that the voltage variation vector diagram of single-phase short-circuit fault occurs on the inverter side of the AC system, as is shown in Figure 9 [18], and the harmonics distort the voltage of each phase. UA, UB and UC are the three-phase voltage amplitudes before the fault; UA′ and UB′ are the voltage amplitudes of phase A and phase B, respectively, after fault; UAB and UAB′ are line voltage amplitude before and after fault; ΔφA and ΔφB are the voltage phase deviation of phase A and phase B before and after the fault; ΔφAB is phase deviation of the line voltage. Expression of ΔφAB can be obtained by cosine theorem and phasor relation:
Δ φ AB = | arccos U AB 2 + U B 2 U A 2 2 U AB U B ( 30 Δ φ B ) |
In the same way, the formulas for calculating the phase deviation of other line voltages can be obtained:
Δ φ BC = | arccos U BC 2 + U C 2 U B 2 2 U BC U C ( 30 Δ φ C ) |
Δ φ CA = | arccos U CA 2 + U A 2 U C 2 2 U CA U A ( 30 Δ φ A ) |
It can be seen from Formulas (12)–(14) that the voltage distortion will cause the phase shift of the commutation voltage, which will be unfavorable to the commutation process of the converter valve. In order to ensure the normal switching off of the thyristor, it should be triggered in advance to ensure a certain commutation margin.

3.2. Compensation Correction Based on Voltage Change Rate

If the output trigger angle margin of CFPREV is too large, it will lead to an increase in the reactive power consumption of the converter at the inverter side, thus causing the voltage drop of the converter bus, which is not conducive to the recovery of the DC system [30]. If the change trend of voltage can be considered in the fault process, the CFPREV output trigger angle can be compensated and corrected, which can promote the recovery of voltage. The design of dynamic voltage prediction variable Ki is shown in Formula (15):
K i = 1 d U aci d t · B ,   B = { B 1 U aci U level B 2 U aci < U level
where Uaci is the effective value of the line voltage of the AC system at the inverter side; B1 and B2 are correction coefficients; Ulevel represents the reference value of AC voltage.
When the voltage drops, the voltage change rate is negative. At this time, Ki is greater than 1, and the output trigger angle is increased, that is, the commutation margin is increased; when the voltage rises, the voltage change rate term is positive, and Ki is less than 1, which reduces the output trigger angle and promotes the voltage recovery. In the subsequent commutation failure process, the coefficient can also dynamically adjust the commutation margin according to the voltage variation trend.

3.3. Suppression Strategy Considering Harmonic and Voltage Prediction

The principle block diagram of commutation failure suppression strategy considering harmonic and voltage prediction is shown in Figure 10, which mainly includes three links: start-up block, voltage prediction block and trigger block.
Considering the start-up link of the multiple harmonics of the commutation voltage, the commutation voltage-time area corresponding to the 2nd–15th harmonics is calculated by Formula (10). Then, it is substituted into Formula (16) to obtain the calculated values γref_AB, γref_BC and γref_CA corresponding to the extinction angles of each commutation voltage in the fault process, and take the minimum value of the extinction angle corresponding to each commutation voltage to obtain γm:
γ = arccos ( cos β + 2 ω L c I d n = 2 N S n U L )
γ m = min { γ ref _ AB , γ ref _ BC , γ ref _ CA }
Combined with the zero-crossing offset after the distortion of the commutation voltage, the zero-crossing offset of each commutation voltage is calculated by Formulas (12)–(14), and the maximum value is taken to obtain Δφm. The difference between γm and Δφm is defined as the risk judgment value of commutation failure considering the distortion of commutation voltage after fault, as shown in Formula (18):
γ m Δ φ m < γ min
where γmin is the critical extinction angle of thyristor (7°). After meeting the starting criterion, the comparator output A1 is equal to 1, and A2 is obtained as the starting criterion of the trigger link after broadening.
In the voltage prediction link, the effective value Uaci of the line voltage of the AC system on the inverter side is collected in real time, compares the voltage at the current time with the voltage value passing through the first-order inertia section to obtain the voltage change rate, which is substituted into Formula (15) to calculate the compensation coefficient Ki. In the actual simulation process, Uaci will have a small range of fluctuations, a low-pass filter can be used to reduce noise. When the startup criterion is established, the output of A2 is 1, which determines that the system has the risk of commutation failure and starts the trigger link to achieve early trigger. The trigger margin Δα is shown in Formula (19), where Δγ is the compensation margin.
Δ α = K i · ( γ m Δ φ m Δ γ )
After detection of commutation failure risk, start the trigger link and output the lag trigger angle margin Δα, as CFPREV output trigger angle reduction. The index of the proposed control strategy is more sensitive to the harmonic component generated by the commutation voltage distortion, and the response speed is faster.

4. Tuning Method of Parameters

4.1. Calculation of Reference Value of Extinction Angle

In order to determine the pre-trigger time and pre-trigger margin of this strategy, the fast Fourier transform FFT is used to decompose each commutation voltage and the UnL and phase angle φn of each harmonic voltage is obtained. The commutation-time areas corresponding to 2nd–15th harmonic voltage are calculated by substituting Formula (10). The reference value γ0 of the extinction angle here is taken as the critical value γmin (7°). Due to the controller switching requiring a certain time, in order to achieve early trigger, the pre-trigger angle takes the actual value of the trigger angle of the previous cycle β0.
After summing the commutation area corresponding to each harmonic, the calculated value of the corresponding extinction angle is substituted into Formula (16), where UL takes the amplitude of the fundamental commutation voltage U1L. The relevant formulas are shown in (20) and (21):
n = 2 N S n = n = 2 N U n L n [ cos ( n π n β 0 + φ n ) cos ( n π n γ 0 + φ n ) ]
γ = arccos ( cos β 0 + 2 ω L c I d n = 2 N S n U 1 L )

4.2. Voltage Change Rate Module Parameter Tuning

Collect the effective value Uaci of the converter bus voltage in real time and make a difference between the voltage value at the current moment and the voltage value after the first-order low-pass filter [31], so as to obtain the calculated value of the change rate of the converter bus voltage, as shown in Figure 10.
The reason for the first commutation failure is that the commutation margin is insufficient due to the commutation bus voltage drop. In order to suppress the occurrence of the first commutation failure, the value of B2 should be increased to obtain a larger trigger margin, and trigger in advance to suppress the failure. When the voltage exceeds the converter bus voltage threshold Ulevel, the value of B1 is reduced to avoid too small a margin to suppress subsequent commutation failure. After the simulation test, the reference values of B1 and B2 are 3–10 and 11.5–18.5, respectively. The actual parameters will be adjusted according to the fault scenario. The voltage threshold Ulevel is 0.928 p.u.
When the fault occurs, the measurement time of FFT is 2–3 ms [32], and the calculation time of voltage change rate of the converter bus is about 1 ms. The calculation and discrimination of the advanced firing angle can be realized by a multi-core digital signal processor (DSP) with a nanoseconds processing speed [33,34]. The time scale from the fault of the converter bus to the local commutation failure is generally 6–8 ms, so the proposed control strategy can meet the requirements of the rapidity of commutation failure suppression.

5. Case Study

Based on the PSCAD/EMTDC simulation platform, the proposed suppression strategy is built on the CIGRE standard test model. The CFPREV parameters are consistent with the literature [35]. The CIGRE model parameters are shown in Table 1.

5.1. Validation of Commutation Failure Suppression

A three phase short-circuit fault is set on the AC bus at the inverter side, the fault occurs in 2 s and lasts for 0.2 s. The aim is to compare and analyze the fault response of the following three control strategies: control strategy I: CIGRE standard test system; control strategy II: CFPREV control; control strategy III: the strategy proposed in this paper. The responses of extinction angle, AC voltage, trigger angles of inverter side, predictive variable of dynamic voltage Ki and currents at valve side of converter transformer under three strategies are shown in Figure 11.
According to the valve side currents of converter transformer in Figure 11, after a three-phase short-circuit fault in inverter side of AC system, both control strategies I and II failed to commutation failure once and the extinction angle decreased to 0. The reason for the commutation failure of the CFPREV strategy at 2.21 s is that the CFPREV output leads to the small trigger angle α at the inverter side, the increase of reactive power consumption of the converter and the voltage drop of the AC system, which deteriorate the commutation conditions. The strategy in this paper suppresses the first commutation failure and the system has no subsequent commutation failure. When the fault occurs, the voltage change rate is less than 0, the predictive variable of dynamic voltage Ki is greater than 1 and the trigger angle margin is increased to suppress the first commutation failure. By comparing the lag trigger angle of Figure 11, it can be seen that the strategy in this paper realizes the early trigger and the trigger margin is greater than the other two strategies, which can suppress commutation failure to a certain extent.
In order to further verify the adaptability of the strategy in this paper, single-phase short-circuit and three-phase short-circuit grounding faults are set on the inverter side and the electrical responses are shown in Figure 12 and Figure 13. It can be seen from Figure 12 that the single-phase short-circuit fault leads to two consecutive commutation failures in the original CIGRE system, and both CFPREV and the proposed strategy inhibit the first and subsequent commutation failures. However, the trigger angle margin of this strategy is obtained in advance compared with CFPREV strategy, and the advance trigger angle margin increases and the voltage recovery speed is faster. At the same time, in the steady state of the fault, the value of the extinction angle of the strategy in this paper does not increase, and the converter consumes less reactive power, which is conducive to the rapid recovery of the DC system. It can be seen from Figure 13 that under the three-phase short-circuit grounding fault, strategy I has two commutation failures and the CFPREV strategy has deteriorated the commutation conditions, resulting in one commutation failure. The proposed strategy realizes the early triggering and obtains a large trigger angle margin, which inhibits the first and subsequent commutation failures.

5.2. Subsequent Commutation Failure Suppression Verification

In order to fully verify the ability of the proposed strategy to suppress the first and subsequent commutation failures at different fault levels, further simulations are performed in different fault scenarios. First, it is necessary to define the fault level FL as shown in (22). The larger the FL value is, the more serious the fault is.
F L = U L 2 ω L f 1 P dN × 100 %
where PdN is the rated DC transmitted power; UL is the AC bus voltage on the inverter side; Lf is the grounding inductance; and ω is the rated angular frequency.
Two fault scenarios of three-phase short-circuit fault and single-phase short-circuit fault are set up with different fault severity levels to compare and analyze the fault suppression capability of the strategy in this paper, the CFPREV strategy and the original CIGRE system. The results are shown in Figure 14.
The simulation results show that the CFPREV and the proposed strategy can suppress the subsequent commutation failure compared with the original CIGRE system when the three-phase short-circuit fault occurs in the inverter side AC system, but the suppression effect of the proposed strategy is better. CFPREV control and the strategy in this paper begin to fail in the first commutation when FL is 17.9% and 23.8%, respectively. Therefore, the strategy in this paper can inhibit the first commutation failure to a certain degree of failure. When a single-phase short-circuit fault occurs, the original CIGRE system and CFPREV strategy have different degrees of single and subsequent commutation failures, while the strategy in this paper has no commutation failure below 67.28% of the fault level. When FL exceeds 67.28%, the single-phase short-circuit fault is more serious, and the restraining ability of commutation failure of the strategy in this paper is the same as the other two strategies.
Compared with CFPREV control, the proposed strategy can track the dynamic changes of voltage in real time. When the commutation voltage drops, the compensation margin of the trigger angle is increased, so as to realize the early trigger and suppress the first commutation failure. In the stage of fault recovery, the compensation margin of the trigger angle is dynamically adjusted to reduce, which is conducive to the rapid recovery of the DC system and inhibits the occurrence of subsequent commutation failures.

6. Conclusions

In this paper, a predictive commutation failure suppression strategy considering multiple harmonics of commutation voltage is proposed combined with the first and subsequent commutation failure mechanisms in HVDC transmission. The proposed strategy comprehensively considers the harmonic component of commutation voltage distortion and the dynamic change of AC bus voltage, and triggers in advance to increase the commutation supply area. Through theoretical and simulation analyses, the conclusions are as follows:
  • During the fault recovery process after the first commutation failure, the voltage distortion of the commutation bus caused by harmonics leads to a significant reduction in the commutation supply area, which is an important factor leading to the subsequent commutation failure.
  • The proposed strategy calculates the extinction angle and offset angle based on the harmonic components and constructs a comparator to judge whether there is a risk of commutation failure. It is more accurate to obtain the early trigger amount in advance and improves the sensitivity of commutation failure suppression.
  • The prediction module of proposed strategy considers the dynamic change rate of AC bus voltage during the process of faults and suppresses the first and subsequent commutation failures by calculating different indicators. Compared with the traditional control methods, the strategy in this paper can suppress the first commutation failure under the three-phase short-circuit fault degree of 23.8% and the subsequent commutation failure, and the first and subsequent commutation failures with single-phase short-circuit fault degree below 67.28%.
The future works will focus on interaction principle and suppression strategy of commutation failure in multi-infeed HVDC system.

Author Contributions

Conceptualization: X.L., B.G. and Z.C.; validation: X.L. and Z.C.; investigation: X.L. and B.G.; methodology: X.L.; original draft: X.L.; writing—review and editing: X.L. and B.G.; data provision: Z.Z., X.W. and F.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by State Grid Corporation of China Science and Technology Project: “Research on DC control optimization for improving dynamic and transient performance of AC / DC hybrid power grid”, grant number 5230HQ21000S.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available in article.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

αTrigger delay angle of LCC.
βTrigger advance angle of LCC.
γExtinction angle.
μOverlap angle.
uAlternating voltage.
LcEquivalent inductance.
UCommutation voltage.
ULAmplitude of commutation voltage.
IDirect current.
SCommutation area.
iAlternating current.
φCurrent error control.
ΔPerturbational component of variables.
BCorrection coefficients of voltage change rate.
IY/DCurrent at valve side of converter transformer.
KDynamic voltage prediction variable.
FLFault level.
Superscripts and Subscripts
NMaximum harmonic numbers.
refReference value of variables.
dVariables at direct current side.
level, 0Steady-state value of variables.
acVariables at alternating current side.
nHarmonic numbers.
ordCommand value of variables.
iVariables at inverter side.
ab,bc,ca/AB,BC,CAPhase to phase of variables.
a,b,c/A,B,CPhase to neutral of variables.

References

  1. Wang, M.; An, T.; Ergun, H.; Lan, Y.; Andersen, B.; Szechtman, M.; Leterme, W.; Beerten, J.; Hertem, D.V. Review and Outlook of HVDC Grids as Backbone of Transmission System. CSEE J. Power Energy Syst. 2021, 7, 797–810. [Google Scholar]
  2. Yang, Z.; Gao, B.; Cao, Z. Optimal Current Allocation Strategy for Hybrid Hierarchical HVDC System with Parallel Operation of High-Voltage and Low-Voltage DC Lines. Processes 2022, 10, 579. [Google Scholar] [CrossRef]
  3. Xue, Y.; Zhang, X.; Yang, C. AC Filterless Flexible LCC HVDC With Reduced Voltage Rating of Controllable Capacitors. IEEE Trans. Power Syst. 2018, 33, 5507–5518. [Google Scholar] [CrossRef]
  4. Li, C.; Li, K.; Jiang, F.; Tai, W.; Wu, X.; Tang, Y. Improvement Method of Commutation Failure Predictive Control Based on Voltage Waveform Fitting. In Proceedings of the 2021 IEEE Sustainable Power and Energy Conference (iSPEC), Nanjing, China, 23–25 December 2021. [Google Scholar]
  5. Wei, J.; Cao, Y.; Wu, Q.; Li, C.; Huang, S.; Zhou, B.; Xu, D. Coordinated Droop Control and Adaptive Model Predictive Control for Enhancing HVRT and Post-Event Recovery of Large-Scale Wind Farm. IEEE Trans. Sustain. Energy 2021, 12, 1549–1560. [Google Scholar] [CrossRef]
  6. Yin, C.; Li, F. Analytical Expression on Transient Overvoltage Peak Value of Converter Bus Caused by DC Faults. IEEE Trans. Power Syst. 2021, 36, 2741–2744. [Google Scholar] [CrossRef]
  7. Hong, L.; Zhou, X.; Xia, H.; Liu, Y.; Luo, A. Mechanism and Prevention of Commutation Failure in LCC-HVDC Caused by Sending End AC Faults. IEEE Trans. Power Deliv. 2021, 36, 473–476. [Google Scholar] [CrossRef]
  8. Jing, W.; Jun, L.; Yang, Z.; Hao, Z.; Cong, X.; Hu, Y. A Novel Control Strategy for Suppression of HVDC Subsequent Commutation Failure. In Proceedings of the 2020 IEEE 3rd Student Conference on Electrical Machines and Systems (SCEMS), Jinan, China, 4–6 December 2020. [Google Scholar]
  9. Liu, L.; Lin, S.; Sun, P.; Liao, K.; Li, X.; Deng, Y.; He, Z. A Calculation Method of Pseudo Extinction Angle for Commutation Failure Mitigation in HVDC. IEEE Transactions on Power Delivery. 2019, 34, 777–779. [Google Scholar] [CrossRef]
  10. Yang, W.; Miao, S.; Zhang, S.; Li, Y.; Han, J.; Xu, H.; Zhang, D. A Commutation Failure Risk Analysis Method Considering the Interaction of Inverter Stations. Int. J. Electr. Power Energy Syst. 2020, 120, 106009. [Google Scholar] [CrossRef]
  11. Liu, B.; Chen, Z.; Yang, S.; Lu, C.; Deng, X.; Wang, R. Research on methods of measuring extinction angle and measures to suppress repetitive commutation failures through equivalent DC input resistance. Int. J. Electr. Power Energy Syst. 2021, 133, 107326. [Google Scholar] [CrossRef]
  12. Chen, M.; Kang, Z.; Gan, D.; Wu, H. Impact of Commutation Failure Preventions on HVDC System Based on a Multi-Index Value Set Approach. IEEE Access. 2021, 9, 48080–48090. [Google Scholar] [CrossRef]
  13. Xue, Y.; Zhang, X.; Yang, C. Commutation Failure Elimination of LCC HVDC Systems Using Thyristor-Based Controllable Capacitors. IEEE Trans. Power Deliv. 2018, 33, 1448–1458. [Google Scholar] [CrossRef]
  14. Wang, H.; Dong, X. Commutation Failure Mitigation Method Based on Improved Commutation Area in HVDC system. In Proceedings of the 2019 IEEE 8th International Conference on Advanced Power System Automation and Protection (APAP), Xi’an, China, 21–24 October 2019. [Google Scholar]
  15. Xu, C.; Yu, Z.; Chen, Z.; Zhao, B.; Wang, Z.; Ren, C.; Zeng, R. Comprehensive Analysis and Experiments of RB-IGCT, IGCT with Fast Recovery Diode and Standard Recovery Diode in Hybrid Line Commutated Converter for Commutation Failure Mitigation. IEEE Trans. Ind. Electron. 2022, 70, 1126–1139. [Google Scholar] [CrossRef]
  16. González-Cabrera, N.; Castro, L.M.; Gutiérrez-Alcaraz, G.; Tovar-Hernandez, J.H. Alternative approach for efficient OPF calculations in hybrid AC/DC power grids with VSC-HVDC systems based on shift factors. Int. J. Electr. Power Energy Syst. 2021, 124, 106395. [Google Scholar] [CrossRef]
  17. Gao, K.; Li, C.; Li, X.; Wang, H.; Rao, Y.; Liu, W. Transformer Inrush Current Impact on Commutation Failure Prevention of UHVDC Transmission system. In Proceedings of the 2019 IEEE 3rd Conference on Energy Internet and Energy System Integration (EI2), Changsha, China, 8–10 November 2019; pp. 2730–2734. [Google Scholar]
  18. Yao, W.; Liu, C.; Fang, J.; Ai, X.; Wen, J.; Cheng, S. Probabilistic Analysis of Commutation Failure in LCC-HVDC System Considering the CFPREV and the Initial Fault Voltage Angle. IEEE Trans. Power Deliv. 2020, 35, 715–724. [Google Scholar] [CrossRef]
  19. Yao, W.; Wang, L.; Xiong, Y.; Tan, Y.; Li, D.; Li, C.; When, J. Interaction Mechanism and Coordinated Control of Commutation Failure Prevention in Multi-Infeed Ultra-HVDC System. Int. Trans. Electr. Energy Syst. 2022, 2022, 7088114. [Google Scholar] [CrossRef]
  20. Wang, T.; Pei, L.; Wang, J.; Wang, Z. Overvoltage Suppression Under Commutation Failure Based on Improved Voltage-Dependent Current Order Limiter Control Strategy. IEEE Trans. Ind. Appl. 2022, 58, 4914–4922. [Google Scholar] [CrossRef]
  21. Zhang, G.; Jing, L.; Wang, B. Study on HVDC Consecutive Commutation Failures Mitigation Method Caused by Harmonics. Proc. CSEE 2020, 48, 33–41. [Google Scholar]
  22. Wang, Q.; Zhang, C.; Wu, X.; Tang, Y. Commutation Failure Prediction Method Considering Commutation Voltage Distortion and DC Current Variation. IEEE Access 2019, 7, 96531–96539. [Google Scholar] [CrossRef]
  23. Xiao, H.; Li, Y.; Duan, X. Enhanced Commutation Failure Predictive Detection Method and Control Strategy in Multi-Infeed LCC-HVDC Systems Considering Voltage Harmonics. IEEE Trans. Power Syst. 2021, 36, 81–96. [Google Scholar] [CrossRef]
  24. Chen, J.; Wang, Q.; Zhu, Z. Evaluation of Commutation failure Risk for HVDC Caused by Harmonic Voltage. In Proceedings of the 2019 IEEE 3rd Conference on Energy Internet and Energy System Integration (EI2), Changsha, China, 8–10 November 2019. [Google Scholar]
  25. Wei, Z.; Fang, W.; Liu, J. Variable Extinction Angle Control Strategy Based on Virtual Resistance to Mitigate Commutation Failures in HVDC System. IEEE Access 2020, 8, 93692–93704. [Google Scholar] [CrossRef]
  26. Mirsaeidi, S.; Tzelepis, D.; He, J.; Dong, X.; Said, D.M.; Booth, C. A Controllable Thyristor-Based Commutation Failure Inhibitor for LCC-HVDC Transmission Systems. IEEE Trans. Power Electron. 2021, 36, 3781–3792. [Google Scholar] [CrossRef]
  27. Xiao, H.; Li, Y.; Lan, T. Sending End AC Faults can Cause Commutation Failure in LCC-HVDC Inverters. IEEE Trans. Power Deliv. 2020, 35, 2554–2557. [Google Scholar] [CrossRef]
  28. Sun, W.; Wang, Q.; Gu, R.; Zheng, C.; Wang, Y. Coordinated Control Method of Multi-infeed DC System for Commutation Failure Prevention. In Proceedings of the 2021 IEEE Sustainable Power and Energy Conference (iSPEC), Nanjing, China, 23–25 December 2021. [Google Scholar]
  29. Wei, Z.; Yuan, Y.; Lei, X.; Wang, H.; Sun, G.; Sun, Y. Direct-Current Predictive Control Strategy for Inhibiting Commutation Failure in HVDC Converter. IEEE Trans. Power Syst. 2014, 29, 2409–2417. [Google Scholar] [CrossRef]
  30. Tian, D.; Xiong, X. Corrections of Original CFPREV Control in LCC-HVDC Links and Analysis of its Inherent Plateau Effect. CSEE J. Power Energy Syst. 2022, 8, 10–16. [Google Scholar]
  31. Zhang, J.; Lin, W.; Wen, J. DC Fault Protection of DC Grid Based on DC Voltage Change Rate. South. Power Syst. Technol. 2017, 11, 14–22. [Google Scholar]
  32. Tiwari, R.; Gupta, O.; Ansari, S. Frequency Spectral Analysis of 6-Pulse LCC-HVDC in Single Conductor Ground Return Configuration Using FFT. In Proceedings of the 2022 2nd International Conference on Power Electronics & IoT Applications in Renewable Energy and its Control (PARC), Mathura, India, 1–5 January 2022. [Google Scholar]
  33. Psaras, V.; Vozikis, D.; Adam, G.; Burt, G. Real Time Evaluation of Wavelet Transform for Fast and Efficient HVDC Grid Non-Unit Protection. In Proceedings of the 2020 IEEE Power & Energy Society General Meeting (PESGM), Montreal, QC, Canada, 1–5 August 2020. [Google Scholar]
  34. Zhu, Y.; Chang, D.; Guo, Q.; Guo, H.; Hu, B.; Wu, M.; Zhu, Y.; Yu, D. Research and Implementation of Real-Time Accurate Simulation Platform for Large-Scale Stability Control System. In Proceedings of the 2021 IEEE 5th Conference on Energy Internet and Energy System Integration (EI2), Taiyuan, China, 22–24 October 2021. [Google Scholar]
  35. Meah, K.; Sadrul Ula, A.H.M. Simulation Study of the CIGRE HVDC Benchmark Model with the WSCC Nine-bus Power System Network. In Proceedings of the 2009 IEEE/PES Power Systems Conference and Exposition, Seattle, WA, USA, 15–18 March 2009. [Google Scholar]
Figure 1. Topology of LCC-HVDC.
Figure 1. Topology of LCC-HVDC.
Processes 10 02073 g001
Figure 2. Mechanism analysis of commutation process. (a) Equivalent model of inverter side 6-pulse converter. (b) Simplified diagram of inverter commutation process.
Figure 2. Mechanism analysis of commutation process. (a) Equivalent model of inverter side 6-pulse converter. (b) Simplified diagram of inverter commutation process.
Processes 10 02073 g002
Figure 3. Diagram of voltage waveform distortion.
Figure 3. Diagram of voltage waveform distortion.
Processes 10 02073 g003
Figure 4. Control block diagram of HVDC inverter side.
Figure 4. Control block diagram of HVDC inverter side.
Processes 10 02073 g004
Figure 5. Response waveform of inverter side after three-phase short-circuit grounding fault.
Figure 5. Response waveform of inverter side after three-phase short-circuit grounding fault.
Processes 10 02073 g005
Figure 6. Commutation voltage time area after commutation bus fault. (a) Commutation voltage time area of the whole simulation. (b) Commutation voltage time area before the first commutation failure. (c) Commutation voltage time area before the subsequent commutation failure.
Figure 6. Commutation voltage time area after commutation bus fault. (a) Commutation voltage time area of the whole simulation. (b) Commutation voltage time area before the first commutation failure. (c) Commutation voltage time area before the subsequent commutation failure.
Processes 10 02073 g006
Figure 7. Schematic diagram of CFPREV control.
Figure 7. Schematic diagram of CFPREV control.
Processes 10 02073 g007
Figure 8. Harmonic voltage distortion rate under fault.
Figure 8. Harmonic voltage distortion rate under fault.
Processes 10 02073 g008
Figure 9. Three-phase voltage phasor diagram of short circuit fault.
Figure 9. Three-phase voltage phasor diagram of short circuit fault.
Processes 10 02073 g009
Figure 10. Principle block diagram of commutation failure suppression strategy considering harmonic and voltage prediction.
Figure 10. Principle block diagram of commutation failure suppression strategy considering harmonic and voltage prediction.
Processes 10 02073 g010
Figure 11. Waveforms of three-phase short-circuit fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Figure 11. Waveforms of three-phase short-circuit fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Processes 10 02073 g011
Figure 12. Waveforms of single-phase short-circuit fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Figure 12. Waveforms of single-phase short-circuit fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Processes 10 02073 g012
Figure 13. Waveforms of three-phase short-circuit grounding fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Figure 13. Waveforms of three-phase short-circuit grounding fault under different strategies. (a) Extinction angle γ under three strategies. (b) Current at valve side of converter transformer under strategy Ⅰ. (c) Trigger advance angle β under three strategies. (d) Current at valve side of converter transformer under strategy Ⅱ. (e) Trigger delay angle α under three strategies. (f) Current at valve side of converter transformer under strategy Ⅲ. (g) Predictive variable of dynamic voltage Ki. (h) AC voltage at inverter side.
Processes 10 02073 g013
Figure 14. The suppression ability under different strategies to commutation failure. (a) Frequency of commutation failure under three-phase short-circuit fault. (b) Frequency of commutation failure under single-phase short-circuit fault.
Figure 14. The suppression ability under different strategies to commutation failure. (a) Frequency of commutation failure under three-phase short-circuit fault. (b) Frequency of commutation failure under single-phase short-circuit fault.
Processes 10 02073 g014
Table 1. Test system parameters.
Table 1. Test system parameters.
ParameterRectifierInverter
AC voltage/kV345230
DC voltage/kV507497
DC current/kA22
trigger angle/(°)2018
DC power/MW1014994
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Liu, X.; Cao, Z.; Gao, B.; Zhou, Z.; Wang, X.; Zhang, F. Predictive Commutation Failure Suppression Strategy for High Voltage Direct Current System Considering Harmonic Components of Commutation Voltage. Processes 2022, 10, 2073. https://0-doi-org.brum.beds.ac.uk/10.3390/pr10102073

AMA Style

Liu X, Cao Z, Gao B, Zhou Z, Wang X, Zhang F. Predictive Commutation Failure Suppression Strategy for High Voltage Direct Current System Considering Harmonic Components of Commutation Voltage. Processes. 2022; 10(10):2073. https://0-doi-org.brum.beds.ac.uk/10.3390/pr10102073

Chicago/Turabian Style

Liu, Xiaolin, Zeyu Cao, Bingtuan Gao, Zhuan Zhou, Xingang Wang, and Feng Zhang. 2022. "Predictive Commutation Failure Suppression Strategy for High Voltage Direct Current System Considering Harmonic Components of Commutation Voltage" Processes 10, no. 10: 2073. https://0-doi-org.brum.beds.ac.uk/10.3390/pr10102073

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop