Adaptability Analysis of Fault Component Distance Protection on Transmission Lines Connected to Photovoltaic Power Stations

School of Mechanical Electronic and Information Engineering, China University of Mining and Technology (Beijing), Beijing 100083, China
*
Author to whom correspondence should be addressed.
Submission received: 22 March 2019 / Revised: 21 April 2019 / Accepted: 23 April 2019 / Published: 25 April 2019
(This article belongs to the Section A2: Solar Energy and Photovoltaic Systems)

Abstract

:
Photovoltaic (PV) power stations tend to have a relatively weak infeed characteristic, unlike conventional synchronous generators. The limited overcurrent capability of power electronic devices and the controllability of grid-connected inverters mean that PV power stations will cause changes in the characteristics of faults on transmission lines. To analyze the adaptability of fault component distance protection on transmission lines connected to PV power stations, a unified phasor expression for the fault current of a PV power station side under various control strategies was deduced in this paper. This expression is then used to derive the equivalent impedance on the PV power station side and the additional impedance. The equivalent impedance and additional impedance are affected greatly by the active and reactive power commands, control targets, and fault conditions. These aspects of a PV power station may cause malfunctions, which can thereby reduce the reliability of fault component distance protection on transmission lines connected to PV power stations. A simulation model of a PV power station was established in PSCAD/EMTDC and the correctness of theoretical analysis was verified by the simulation results.

1. Introduction

With the rapid development of photovoltaic (PV) power-generation technology and the increasing installed capacity of PV power stations, PV power generation has achieved a pivotal position in the global energy system [1,2,3]. Unlike traditional power supply based on synchronous generators, PV power stations have a high degree of controllability. The fault-current characteristics on the PV power station side are affected by the adopted control strategy, control parameters, and fault conditions, among other factors. Additionally, due to the weak infeed characteristic of the PV power station, the fault current in a transmission line will have a lower magnitude than a fault with a conventional power supply [4,5,6]. Therefore, the fault-current characteristics of a PV power station are significantly different from that of a synchronous source. Therefore, the fault analysis and protection schemes used in synchronous source are not suitable for the transmission line connected to a PV power station [7,8,9]. Fault component distance protection offers the advantages of clear directionality, high-speed operation, and is not affected by the pre-fault load current, among others [8]. The fault component distance protection is widely used in high-voltage transmission lines. Therefore, studying the influence of PV power station on fault component distance protection has a great significance, and corresponding solutions should be proposed to ensure the safe and stable operation of the power systems.
Several researches have addressed control strategies for photovoltaic systems but relatively few papers investigated the effects of PV power stations on fault component distance protection. Based on the fault characteristics of traditional power supply, a fault component distance protection is introduced in [10]. Using the current characteristics of a thyristor-controlled series compensator (TCSC), the impact of TCSC on fault component distance protection was analyzed, and it was shown that the fault component distance protection may perform an incorrect operation [11]. A novel weak fault component distance protection was proposed previously, which integrates the performance of a fault component reactance relay and a fault component impedance relay by adjusting the compensated voltage [12]. Simulations showed that this protection scheme offers an improved sensitivity and selectivity while responding to unbalanced faults. Fault component distance protection based on voltage amplitude comparison was introduced and its merit in covering larger fault resistances was analyzed for unified power flow controller (UPFC) [13]. References [10,11,12,13] analyzed fault component distance protection but PV power stations differ from other power systems from the perspective of operating principles and control strategies. Since PV power stations will be interconnected with the existing power networks, the adaptability of the currently protection methods need to be further investigated.
Currently, distance protection is widely utilized in high-voltage transmission networks and several studies have been conducted from the viewpoint of the impact of renewable energy power stations on distance protection. The adaptability problem of typical relay protection schemes to transmission lines emanating from PV power stations was briefly studied in [14]. The fault-current characteristics within a large PV power station were analyzed in [15], and a distance protection scheme was proposed to effectively isolate PV power station from faults in overhead transmission lines. In particular, PV power stations have some impact on traditional current protection and may lead to protection maloperation [16]. The effect of voltage source converter based high voltage direct current (VSC-HVDC) interconnectors on distance protection of transmission lines has also been analyzed in [17,18]. Additionally, a novel pilot protection principle was proposed in [17]. Furthermore, the changes of modular multilevel converter based HVDC (MMC-HVDC) operation mode cause the scope of higher line distance relay Zone 2 to be narrowed, considerably increasing the probability of incorrect operation of distance protection [19]. The influence of full-scale converter-interfaced renewable energy power plants (CIREPPs) on distance relays installed on transmission lines connected to CIREPPs has been investigated in [20], and another novel protection scheme was proposed in [21]. The impact of the several control strategies and the combined impact of a voltage source converter (VSC) with a synchronous condenser on distance protection has been evaluated in [22]. Results showed that the control strategies should avoid the use of constant reactive power to enhance the reliability of distance protection. In addition, wind farms based on doubly fed induction generators (DFIGs) are widely employed in existing power networks, and numerous studies have been performed on distance protection performance in wind farms [23,24,25,26]. Considering the specific fault characteristics and complex control strategies of DFIGs in wind farms, a new adaptive distance protection scheme was proposed in [23] and a distance relay in the time domain based on the resistance- inductance (R-L) differential-equation algorithm was proposed in [26]. However, none of these studies discussed fault component distance protection or considered specific PV power station characteristics. In particular, unlike conventional distance protection, fault component distance protection is based on a voltage and current fault component, which significantly differs in terms of operating principles and advantages. Furthermore, PV power stations differ from DFIG-based wind power integration systems from the perspective of operation mode and fault-current characteristics. Therefore, it is highly necessary to investigate the adaptability problem of the fault component distance protection on the transmission lines connected to PV power stations.
The rest of this paper is organized as follows. Section 2 formulates a phasor expression for the fault current on the PV power station side and discusses the fault-current characteristics. Section 3 describes the general principles for fault component distance protection and uses the phasor expression of fault current to derive the equivalent impedance of the PV power station side and the additional impedance. Furthermore, this section analyzes the influence of equivalent impedance of the PV power station side and the additional impedance on fault component distance protection. The simulation results presented in Section 4 verify the theoretical analysis of the adaptability of fault component distance protection. Discussion and conclusions are drawn in Section 5 and Section 6, respectively.

2. Fault-Current Characteristics at a PV Power Station

A practical 150-MW PV power station connected to a power grid is used as the model for analysis, as shown in Figure 1. The M side is the PV power station side and the P side is the system side. The PV power station is connected to a grid with a two-stage boosting structure. First, the direct current (DC) output of the PV power generation unit is inverted into a power frequency alternating current (AC) through the grid-connected inverter, and is then integrated in a 35 kV switch cabinet. Finally, after 35 kV busbar convergence, the power output is boosted and sent to the local power grid through a 220 kV double-winding transformer.
When asymmetric faults occur in the AC transmission line, MP, the three-phase voltage phasor of the PV power station (M side) can be expressed as:
U ˙ M η = U ˙ η + + U ˙ η + U ˙ 0 = U + ( δ + + θ η ) + U ( δ θ η ) + k 0 U 0 δ 0 ,
where U is the voltage magnitude and δ is the initial phase angle of the voltage. The superscripts “+,” “−,” and “0” denote positive, negative, and zero-sequence components, respectively. η = a, b, and c, θa = 0°, θb = −120°, and θc = 120°; and k0 is the grounding coefficient. If the fault is a ground fault, k0 is equal to 1; otherwise, k0 is equal to 0.
The fault-current characteristics on the M side depend on the control system of a PV grid-connected inverter. Considering unbalanced grid voltage, a current controller under a double synchronous rotating frame is widely used in PV grid-connected inverters [27,28]. Therefore, various control targets are set in PV grid-connected inverter control systems, and a unified expression for the reference current under various control targets can be expressed:
[ i α ref + i β ref + i α ref i β ref ] = 2 3 ( U + ) 2 [ u α + P ref 1 k χ k ρ 2 + u β + Q ref 1 + k χ k ρ 2 u β + P ref 1 k χ k ρ 2 u α + Q ref 1 + k χ k ρ 2 k χ u α P ref 1 k χ k ρ 2 k χ u β Q ref 1 + k χ k ρ 2 k χ u β P ref 1 k χ k ρ 2 + k χ u α Q ref 1 + k χ k ρ 2 ] ,
where kχ is a real number that defines the control targets during the fault-ride-through period. The subscripts “ref” denotes the reference value. When kχ = −1, 0, and 1, the control targets of the PV grid-connected inverter are to eliminate reactive power oscillation, to eliminate negative-sequence current, and to eliminate active power oscillation, respectively. Pref and Qref are the reference values of active and reactive power commands, respectively, and kρ is the grid voltage unbalance coefficient (kρ = U/U+).
When asymmetrical faults occur in the transmission line, since the step-up transformer (high-voltage side) is connected in star, the fault current in the transmission line comprises positive-, negative-, and zero-sequence components. After the reference currents from the control strategy in (2) have been applied, the phasor expression for steady-state fault current on the M side is as follows:
I ˙ M η = I vm ( δ + + φ + θ η ) k χ k ρ I vm ( δ + φ θ η )   +   k 0 I 0 θ 0 ,
where
I vm = 2 3 U + ( P ref 1 k χ k ρ 2 ) 2 + ( Q ref 1 + k χ k ρ 2 ) 2 φ = tan 1 Q ref / ( 1 + k χ k ρ 2 ) P ref / ( 1 k χ k ρ 2 ) ,
where Ivm is the magnitude of the positive-sequence current component. I0 and θ0 represent the magnitude and initial phase angle of the zero-sequence current, respectively. The magnitude and initial phase angle are determined by the zero-sequence voltage and the impedance of the zero-sequence network, respectively.
For synchronous sources, the fault current of traditional synchronous sources has been well studied, and its expression can be expressed as [29,30]:
i η - SG = 2 E q | 0 | ( x d x d x d x d e t T d + x d x d x d x d e t T d ) cos ( ω t + φ η ) + 2 E q | 0 | x d cos ( ω t + φ η ) 2 E q | 0 | cos φ η x d e t T a , t t 0
where η is phase A, B, or C, and SG denotes the synchronous generator. E q | 0 | and x d are the inner potential and reactance of the generator, respectively. x d and x d are the transient reactance and sub-transient reactance, respectively. T d and T d are the transient time constant and sub-transient time constant, respectively. ω is the power frequency electrical angular velocity, φη is the fault inception angle, Ta is the time constant of the stator windings, and t0 is the fault inception time.
As seen in Equation (5), the fault current comprises an exponentially decaying cosine wave, a steady cosine wave, and an exponentially decaying DC component. The fault-current characteristics of a synchronous source are primarily determined by the synchronous source’s characteristics and fault conditions. Generally, the fault-current magnitude is much larger than the rated value.
According to Equations (3)–(5) and the vulnerability of power electronic devices, the observed characteristics are summarized as follows:
  • The fault-current characteristics on the M side differ significantly from those of a synchronous source and are affected by a wide range of factors, such as the control targets, active and reactive power commands, and the voltage unbalance on the grid. The positive-sequence and negative-sequence currents of M side are completely controllable, whereas fault currents of the synchronous source are uncontrollable, which is depended on synchronous source characteristics and fault conditions.
  • Because of the overcurrent limits of power electronic devices and the controllability of grid-facing inverters, the maximum magnitude of positive and negative-sequence currents in a fault current generally do not exceed 1.2 times the rated value. However, the magnitude of the fault current of the synchronous source is much larger than the rated value of the normal current.
  • The main transformers usually adopt YNd11 wiring and PV power stations tend to have a weak infeed for the positive- and negative-sequence components. When a ground fault occurs in the transmission line, the fault current consists of positive, negative, and zero-sequence components, and the zero-sequence current dominates. When an ungrounded fault occurs, the fault current does not include a zero-sequence component.

3. Adaptability Analysis of Fault Component Distance Protection

Based on the analysis of fault current of transmission lines in Section 2, the adaptability of typical fault component distance protection on the M side are analyzed in detail below.

3.1. Principle of Fault Component Distance Protection

The usual operation criteria for fault component distance protection is
| Δ U ˙ op | = | Δ U ˙ M Δ I ˙ M Z set | | U ˙ f [ 0 ] |     internal   fault   | Δ U ˙ op | = | Δ U ˙ M Δ I ˙ M Z set | < | U ˙ f [ 0 ] |     external   fault
where Δ U ˙ op is the fault component of a compensated voltage and U ˙ f [ 0 ] is the pre-fault voltage at fault point. Δ U ˙ M and Δ I ˙ M are the fault components of the voltage and current at relay point M, respectively.
Zone 1 is taken as an example to study the effect of PV power station on fault component distance protection in transmission lines. The analysis method for Zone 1 and the conclusion obtained from Zone 1 are applicable to Zone 2. Zset is the setting impedance of Zone 1 (i.e., 80% of the line impedance).
The operating principle for traditional fault component distance protection is shown in Figure 2. Since the impedance angles of various elements in fault-additional network for traditional power grid are nearly equal, the phases of Δ U ˙ op , Δ U ˙ M , and U ˙ f [ 0 ] are almost the same. In normal conditions, Δ U ˙ op = 0 ; therefore, the fault component distance protection will not engage. During an external metallic fault, Δ U ˙ op and U ˙ f [ 0 ] have the same phase, and as | Δ U ˙ op | < | U ˙ f [ 0 ] | , the fault component distance protection will still not operate reliably. For the internal metallic fault, | Δ U ˙ op | | U ˙ f [ 0 ] | ; hence, the fault component distance protection can operate successfully. For a fault at the end of the protection zone, the fault component distance protection is on the edge of operation.
According to (6) and Figure 2, when a fault occurs in the transmission line, the impedance phase angles of Zs, Zm, and Zset are equal, which is the ideal condition for correct operation of fault component distance protection. Therefore, the operation criterion of (6) can be transformed into impedance form as follows:
| Z s + Z set | | Z s + Z m |    internal   fault   | Z s + Z set | < | Z s + Z m |    external   fault   ,
In phase-to-phase faults, Zs and Zm are obtained as:
Z s = Δ U ˙ M φ φ Δ I ˙ M φ φ , Z m = U ˙ M φ φ I ˙ M φ φ ,
In a single-phase-to-ground fault, Zs and Zm are obtained as
Z s = Δ U ˙ M η Δ I ˙ M η + k l I ˙ 0 , Z m = U ˙ M η I ˙ M η + k l I ˙ 0 ,
where Zs is the equivalent impedance on the M side and Zm is the measured impedance. η = a, b, and c, φφ = ab, bc, and ca. kl is the zero-sequence compensation coefficient, kl = (z0 − z1)/(z1), and z1 and z0 are the positive sequence and zero-sequence impedance of unit length, respectively.
Generally, the setting impedance is not affected by PV power station connected to the power grid, and the value of Zs is basically unchanged in traditional power grid. However, according to the phasor expression in (3) and (4), the fault-current characteristics on the M side differ significantly from those of conventional power grid. Therefore, Zs and Zm are affected greatly by the interconnection of PV power station, which lead Zs and Zm to differ significantly from their values in traditional power grid in terms of magnitude and phase angle, and may further lead fault component distance protection to operate incorrectly.

3.2. Characteristics of Equivalent Impedance on the PV Power Station Side

According to previous discussion, if the measured impedance is equal to the actual fault impedance, the operating performance of fault component distance protection is determined by the equivalent impedance characteristics of M side. Therefore, this section considers an internal metallic fault as an example to study the equivalent impedance characteristics of the M side, and then analyzes the adaptability of fault component distance protection. The influence of the phase angle change of Zs on the operating performance of fault component distance protection is shown in Figure 3. The dotted and solid lines illustrate the cases in which the magnitude of Zs is small and the magnitude of Zs is large, respectively.
Figure 3 shows that the phase angle change of Zs affects the operating performance of fault component distance protection. The following preliminary conclusions can be drawn concerning the operating performance of fault component distance protection:
  • When 0° < arg(Zs) < 180°, the impedance relationship still meets the operation criterion of impedance form in Equation (7). The fault component distance protection will operate correctly; however, the large magnitude of Zs decreases the sensitivity of the fault component distance protection.
  • When −90° < arg(Zs) < 0° and the magnitude of Zs is small, the impedance relationship still meets the operation criterion of the impedance form. When the magnitude of Zs is large, the impedance relationship does not satisfy the operation criterion of impedance form. Due to the weak infeed characteristic of the PV power station, the magnitude of Zs is much larger than that in traditional power grid. Therefore, the fault component distance protection will operate incorrectly.
  • When −180° < arg(Zs) < −90°, the impedance relationship does not satisfy the operation criterion of impedance form, and the fault component distance protection will be more sensitive to changes of Zs. Therefore, the fault component distance protection will operate incorrectly.

3.2.1. Characteristic Analysis of Zs under Phase-to-Phase Fault

When an internal fault occurs at the transmission line MP (f), the phasor expressions for the three-phase voltage and three-phase current of M side before the fault can be expressed as follows:
{ U ˙ M η [ 0 ] = U + k λ ( δ + Δ δ + φ η ) I ˙ M η [ 0 ] = I Nm ( δ + Δ δ + φ η ) I Nm = 2 k λ P 0 3 U + ,
where ∆δ is the jump angle of the positive-sequence voltage, kλ is the coefficient of the positive-sequence voltage sag, and P0 is the power output of the PV power station during normal operation.
PV power station usually adopts the control target of eliminating a negative-sequence current, so kχ = 0. Assuming that an internal phase-to-phase fault occurs at f, if (3), (4), and (10) are substituted into (8), the magnitude and phase angle of Zs can be calculated as
| Z s | = | Δ U ˙ M φ φ Δ I ˙ M φ φ | = | Δ U ˙ M φ φ | 3 I Nm 1 + ( I vm I Nm ) 2 2 I vm I Nm cos ( φ + Δ δ ) ,
arg ( Z s ) = arg ( Δ U ˙ M φ φ Δ I ˙ M φ φ ) = arg ( C + Z s + + C Z s C + + C ) = tan 1 ( k λ ( sin Δ δ + I vm I Nm sin φ ) I vm I Nm sin ( φ + Δ δ ) k λ ( cos Δ δ I vm I Nm cos φ ) + I vm I Nm cos ( φ + Δ δ ) 1 ) ,
where | Δ U ˙ M φ φ | is the magnitude of the difference between the two phases of the voltage when a phase-to-phase fault occurs (refer to Appendix A Equation (A1)), and C+ and C are coefficients describing the distribution of the positive- and negative-sequence current. When the PV power station adopts the control target of eliminating the negative-sequence current, then C = 0.
Due to the weak infeed characteristic of PV power station, the magnitude of Zs is much larger than that in a traditional power grid. According to (4) and (12), arg(Zs) is related to the variables of ∆δ, P*, Q*, and kλ. The difficulty of theoretical analysis increases significantly owing to the presence of several variable factors. When the three-phase fault with 0 Ω fault resistance occurs, kλ = 0 (minimum value). kλ increases as the fault resistance increases. When the value of fault resistance is infinite, kλ = 1 (maximum value). However, it is impossible that the value of fault resistance is infinite when a fault occurs. Three-phase metallic fault rarely occurs. According to simulation data, the range of ∆δ is generally between −25° and 5°. In view of most possible conditions, the following assumptions are applied: (1) the coefficient of the positive-sequence voltage sag: 0.3 ≤ kλ ≤ 0.8 and (2) the positive-sequence voltage jump angle: −π/8 < ∆δ < 0.
The arg(Zs) with different kλ and ∆δ under the control target of eliminating negative-sequence current is shown in Figure 4, drawn using MATLAB/2016B. Figure 4 shows that the arg(Zs) lies between −80° and 110° under these conditions. Furthermore, as derived in Figure 3, when −180° < arg(Zs) < 0°, the fault component distance protection will fail to operate.
In summary, when an internal phase-to-phase metallic fault occurs at f, the magnitude of Zs will be large, and the phase angle is related to the active and reactive power commands, control targets, and fault conditions. Therefore, when −180° < arg(Zs) < 0°, the fault component distance protection will fail to operate.

3.2.2. Characteristics of Zs under a Single-Phase-to-Ground Fault

When an internal phase-A-to-ground metallic fault occurs at f, by substituting (3), (4), and (10) into (9), the magnitude and phase angle of Zs is calculated as
| Z s | = | Δ U ˙ M a | ( I vm sin ( δ + + φ ) I Nm sin ( δ + Δ δ ) + ( k l + 1 ) I 0 sin θ 0 ) 2 + ( I vm cos ( δ + + φ ) I Nm cos ( δ + Δ δ ) + ( k l + 1 ) I 0 cos θ 0 ) 2 ,
arg ( Z s ) = Δ θ ua tan 1 ( I vm I Nm sin ( δ + + φ ) s i n ( δ + Δ δ ) + ( k l + 1 ) I 0 I Nm sin θ 0 I vm I Nm cos ( δ + + φ ) cos ( δ + Δ δ ) + ( k l + 1 ) I 0 I Nm cos θ 0 ) ,
where | Δ U ˙ M a | and ∆θua are the magnitude and phase angle of the A-phase voltage fault component during the phase-A-to-ground fault, respectively (refer to Appendix A (Equations (A2) and (A3)).
As ∆θua is unaffected by the PV power station, and Ivm/INm ≈ 1.2 and I0/INm > 3, the fault current is dominated by the zero-sequence current. Therefore, ∆θiaθ0 and 0° < arg(Zs) < 180°. Generally, owing to the weak infeed characteristic of PV power station, the magnitude of Zs in the PV power station side is larger than that in a traditional power grid. As derived in Figure 3, when an internal phase-A-to-ground metallic fault occurs at f, the fault component distance protection operates reliably.

3.3. Characteristics of Measured Impedance

Above, the equivalent impedance on the M side was analyzed theoretically, and the influence of Zs on the fault component distance protection was considered under the assumption that Zm is equal to the actual fault impedance (Zk). The PV power station’s effect on Zm is considered below and further analysis of the influence of Zm on fault component distance protection is given.
When a fault with fault resistance Rf occurs at f, the measured impedance (Zm) will be:
Z m = Z k + Δ Z = Z k + Δ I ˙ M + Δ I ˙ P Δ I ˙ M R f ,
where Δ I ˙ M and Δ I ˙ P are the fault-current components on M and P side, respectively, Zk is the actual fault impedance (positive-sequence line impedance between the protection location and the fault location f), and ∆Z is the additional impedance caused by the fault resistance.
For the internal metallic fault, the measured impedance will be equal to the actual fault impedance. If the fault resistance Rf is non-zero, ∆Z will appear in the measured impedance, which means that the distance relay will unable to calculate the actual fault impedance accurately. The characteristic of ∆Z will differ for different faults; the following classification discusses the characteristics of ∆Z.

3.3.1. Characteristic Analysis of ∆Z under a Phase-to-Phase Fault

This section takes an internal phase B-to-phase C (BC) fault as an example to study the characteristics of ∆Z and then analyzes the influence of PV power station on the measured impedance. In this case, ∆Z can be expressed as
Δ Z = R f + Z f = R f + R f | Δ I ˙ PBC | | Δ I ˙ MBC | ( Δ θ PBC Δ θ MBC ) ,
where | Δ I ˙ PBC | and | Δ I ˙ MBC | are the magnitudes of the difference between the BC-phase fault-current components on the P side and M side, respectively. And Δ θ MBC are the phase angles of the difference between the BC-phase fault-current components on the P and M side, respectively.
Generally, Δ I ˙ PBC is determined by the characteristics of traditional power supply, and Δ I ˙ MBC is affected by the control parameters and fault conditions. From (3), (4), and (10), the value of Δ I ˙ MBC can be calculated as
| Δ I ˙ MBC | = 3 I Nm ( I vm I Nm cos ( δ + + φ + θ BC ) cos ( δ + Δ δ + θ BC ) I vm I Nm k χ k ρ cos ( δ + φ θ BC ) ) 2 + ( I vm I Nm sin ( δ + + φ + θ BC ) sin ( δ + Δ δ + θ BC ) I vm I Nm k χ k ρ sin ( δ + φ θ BC ) ) 2 ,
Δ θ MBC = tan 1 ( I vm sin ( δ + + φ + θ BC ) I Nm sin ( δ + Δ δ + θ BC ) I vm k χ k ρ sin ( δ + φ θ BC ) I vm cos ( δ + + φ + θ BC ) I Nm cos ( δ + Δ δ + θ BC ) I vm k χ k ρ cos ( δ + φ θ BC ) ) ,
where θBC = 3π/2· | Δ I ˙ PBC | / | Δ I ˙ MBC | is large because of the weak infeed characteristic of PV power station. In addition, the characteristics of ∆Z are mainly determined by Δ θ MBC . According to Equations (4) and (18), Δ θ MBC values are affected by several factors, such as the control targets, active and reactive power commands, and voltage unbalance on the grid. Consider a phase-to-phase fault as an example. When the value of fault resistance Rf equals 0, kρ = 1 (maximum value). When the value of fault resistance Rf is infinite, kρ = 0 (minimum value). However, the value of fault resistance is not zero, and it cannot be infinite. Therefore, the range of kρ is between 0 and 1. Generally, the Pref value during the fault is less than 1.0 pu and is related to the positive-sequence voltage sag. Therefore, to simplify the analysis, the following assumptions are applied: (1) the active power reference values: 0.2 p.u. ≤ Pref ≤ 0.8 p.u.; and (2) the grid voltage unbalance coefficient: 0.2 p.u. < kρ < 0.8 p.u. The Pref and kρ are within a reasonable range, and the range of Pref and kρ can cover most cases.
The ∆θBCM with different Pref and kρ under the control target of eliminating active power oscillations is shown in Figure 5, which was drawn using MATLAB/2016B. Figure 5 shows that the range of ∆θBCM is between −160° and −60°. The difference in phase angle between both sides may express ∆Z as a capacitive or inductive impedance, which significantly differs from those of a conventional power grid. Therefore, the controllability of ∆θBCM may causes the distance relay to be unable to accurately calculate the actual fault impedance. The impedance plane of measured impedance for an internal BC fault is shown in Figure 6a. The characteristics of Zs with different influence factors.

3.3.2. Characteristic Analysis of ∆Z under a Single-Phase-to-Ground Fault

When kχ is zero and with the weak infeed characteristic of PV power station, the positive-sequence current is less than the zero-sequence current and can be neglected. In this case, the zero-sequence compensation coefficient kl can be assumed to be a real number. In this case, ∆Z can be expressed as:
Δ Z = R f Δ I ˙ Ma + Δ I ˙ Pa Δ I ˙ Ma 3 R f 1 + k l ( I ˙ M 0 + I ˙ P 0 I ˙ M 0 ) ,
where I ˙ M 0 and I ˙ P 0 are the zero-sequence currents measured at the M and the P side. Assuming that the zero-sequence impedance angles on the M and P side are equal, I ˙ M 0 is in phase with I ˙ P 0 , and the zero-sequence current magnitude on the M side is smaller than that on the P side. Therefore, the additional impedance yields a large resistance value. The impedance plane of measured impedance for an internal AG fault is shown in Figure 6b.

3.3.3. Influence of the Measured Impedance on Fault Component Distance Protection

According to the discussion in the previous section, the measured impedance was affected greatly by the fault resistance and fault current, which make the distance relay unable to calculate the actual fault impedance accurately. To simplify the analysis, this section considers an internal BC fault as an example to study the influence of the measured impedance on the operating performance of fault component distance protection. In this case, the influence of the measured impedance on the operating performance of fault component distance protection is shown in Figure 7.
As derived in Figure 3, when an internal metallic fault occurs at f and the 0° < arg(Zs) < 90°, the fault component distance protection will operate reliably. However, when an internal fault with fault resistance occurs at f, it can be seen from Figure 7 that the additional impedance (∆Z) will make the distance relay unable to calculate the actual fault impedance accurately, which may enhance the adverse influence of Zs on fault component distance protection in case that the PV power station is connected to a power grid; further, it will lead fault component distance protection to operate incorrectly.

4. Simulation Verification and Analysis

To verify the correctness of the theoretical analysis discussed above, a 150-MW PV power station, as shown in Figure 1, was modeled in PSCAD/EMTDC. The rated power of the PV station is SPV = 150 MVA, rated capacity of the main transformer is ST = 200 MVA, the rated change ratio is kT = 230/37 kV, the connection type of main transformers is YNd11, and the short-circuit impedance is 16%. The rated voltage of the transmission line is 220 kV, the line length is lMP = 50 km, and the positive-sequence and zero-sequence impedance parameters of the unit length of the line are 0.107 + j0.427 and 0.535 + j1.153 Ω/km, respectively. The equivalent positive-sequence impedance and zero-sequence impedance of the power grid system are 0.6 + j6.972 and 0.8 + j10.95 Ω, respectively.
To prevent overcurrent from damaging power electronic switching devices and improve the safety of inverter operation, the actual PV power station usually adopts the control target of eliminating negative-sequence current. Therefore, the simulations discussed below focus on the theoretical analysis of fault component distance protection based on the control target of eliminating negative-sequence current.

4.1. Simulation Verification of Fault-Current Characteristics on PV Power Station Side

Figure 8 shows the simulation results of various faults occurring at 40% of the length of the transmission line from the relay located on the M side (f). The red, black, and green curves plot the A, B, and C phases, respectively. For fault-current waveforms of the AG fault in Figure 8a, the fault current is dominated by the zero-sequence current, and the phase angles of the three-phase currents are nearly equal. However, for the fault current waveforms of the BC fault in Figure 8b, the fault current is solely positive-sequence current, the three-phase current is symmetrical, and its magnitude does not exceed 1.2 times the rated value. These fault-current characteristics are consistent with the theoretical analysis presented in Section 2.

4.2. Simulation Verification of Equivalent Impedance Characteristics on PV Power Station Side

Figure 9 shows the characteristics of Zs with different influence factors under BC fault at point f.
The characteristics of Zs with different fault resistances are shown in Figure 9a. As shown in Figure 9a, the magnitude of Zs is large in all cases, and increases as the fault resistance increases. When Rf = 0, the phase angle of Zs is −76°. Upon comparing different values of Rf, one can see that arg(Zs) also increases as the fault resistance increases. Meanwhile, arg(Zs) is converted from the range of −90° to 0° to 0° to 90°. This conversion means that the fault component distance protection is very likely to malfunction.
The characteristics of Zs with different reactive power commands (Qref) are shown in Figure 9b. If Qref is small or negative, the −180° < arg(Zs) < 0°, and then the fault component distance protection will operate incorrectly; if Qref is positive, the 0° < arg(Zs) < 180°, and the distance-relay fault protection will operate correctly.

4.3. Simulation Verification of Measured Impedance Characteristics

Figure 10 shows the simulation results of the measured impedance (Zm) under unbalanced faults occurring at f. Figure 10a shows the simulation results of Zm under different metallic faults, and Figure 10b shows the simulation results of Zm under unbalanced faults with 5-Ω fault resistance.
As shown in Figure 10a,b, when a metallic fault occurs, the distance relay can calculate the actual fault impedance accurately. When faults with 5-Ω fault resistance occur, influenced by the fault current of the M side, the measured impedance is much larger than the actual fault impedance, and the distance relay will be unable to calculate actual fault impedance accurately. Therefore, the impedance measured by the distance relay on the transmission line will fall outside the protection zone, as shown in Figure 10c,d. When a phase-to-phase fault occurs, Zm will include a large imaginary component, and the measured impedance will differ greatly from the actual fault impedance.

4.4. Simulation Verification of Operating Performance of Fault Component Distance Protection

Figure 11 shows the operating performance of fault component distance protection under various fault conditions. Figure 11a,b presents the operating performance of fault component distance protection under an AG metallic fault and a BC metallic fault, respectively. Figure 11c,d present the operating performance of fault component distance protection under an AG fault with 5 Ω fault resistance and a BC fault with 5 Ω fault resistance, respectively.
As shown in Figure 11a, when an AG metallic fault occurs on line MP at location f, the 0° < arg(Zs) < 90° and the fault component distance protection can operate successfully. Similarly, as shown in Figure 11b, when a BC fault occurs on line MP at f, the −180° < arg(Zs) < −90°, and the fault component distance protection will fail to operate in this case. These simulations of the fault component distance protection are consistent with the theoretical analysis discussed in Section 3.
The results shown in Figure 11c,d imply that the fault component distance protection will fail to operate if a fault with fault resistance occurs in the transmission line. These simulations of fault component distance protection are consistent with the theoretical results discussed in Section 3.

5. Discussion

Currently, some studies have investigated the effects of renewable energy power stations on distance protection [14,15,16,17,18,19,20,21,22,23,24,25,26]. However, these studies have not discussed fault component distance protection or considered the specific fault characteristics of PV power stations. Because of the increasing penetration of PV power generation, investigating the adaptability problem of fault component distance protection on transmission lines connected to PV power stations is crucial. The main contributions of this paper are as follows:
  • The expression of equivalent impedance of a PV power station side is derived based on the phasor expression of fault current. The equivalent impedance characteristic of the PV power station side is considerably affected by active and reactive power commands, control targets, and fault conditions.
  • This paper studied the influence of phase angle change of Zs on fault component distance protection operating performance and found that additional impedance will enhance the adverse influence of Zs on fault component distance protection in cases where a PV power station is connected to a power grid.
  • Previous studies did not analyze the adaptability of fault component distance protection on transmission lines connected to PV power stations. This study is the first to successfully perform the abovementioned analysis.
  • The research ideas used in this study are also applicable to other typical relay protection schemes on transmission lines connected to PV power stations.

6. Conclusions

This study derived the analytical expressions of fault currents on M side under different control targets. Based on the fault-current characteristics, the adaptability of fault component distance protection was analyzed. First, the fault-current characteristics on the M side differ significantly from those of a synchronous source and are affected by a wide range of factors, such as the control targets, active and reactive power commands, and voltage unbalance on the power grid. Then, the analysis showed that the equivalent impedance of M side tends to be large, and the phase angle of equivalent impedance is greatly affected by the active and reactive power commands, control targets, and fault conditions. In particular, when −180° < arg(Zs) < 0°, the fault component distance protection will operate incorrectly.
Third, the analysis showed that the measured impedance is affected by the related parameters in the control strategy, fault resistance, fault location, and fault type, among others. Unlike conventional synchronous generators, the measured impedance differs significantly in terms of magnitude and phase angle, which will make the distance relay unable to calculate the actual fault impedance accurately. Therefore, errors in impedance measurements can exacerbate problems with the adaptability of fault component distance protection when PV power stations are interconnected with a power grid.
Finally, theoretical analysis and simulations showed that existing fault component distance protection are not suitable for fault protection in transmission lines connected to PV power stations. If a ground metallic fault occurs in the transmission lines, the fault component distance protection will operate correctly. However, if the fault type is a phase-to-phase metallic fault or the fault with fault resistance, the fault component distance protection may fail to operate.

Author Contributions

Investigation, Y.L.; methodology, Y.L. and G.X.; supervision, C.W.; validation, G.X.; writing—original draft, G.X.; writing—review and editing, Y.L., W.Z., and C.W.

Funding

This study was supported by the National Natural Science Foundation of China (Grant No.51707193) and the Fundamental Research Funds for the Central Universities (2017QJ05).

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

| Δ U ˙ M φ φ | = 3 U + 1 + k ρ 2 + 1 / k λ 2 + 2 k ρ cos ( δ + δ + θ φ φ ) cos ( Δ δ ) 2 k ρ / k λ cos ( δ + δ Δ δ + θ φ φ ) ,
| Δ U ˙ M a | = ( U + cos δ + + U cos δ + U 0 cos δ 0 U s cos ( δ + Δ δ ) ) 2 + ( U + sin δ + + U sin δ + U 0 sin δ 0 U s sin ( δ + Δ δ ) ) 2 ,
Δ θ ua = tan 1 ( U s sin ( δ + Δ δ ) U + sin δ + U sin δ U 0 sin δ 0 U s cos ( δ + Δ δ ) U + cos δ + U cos δ U 0 cos δ 0 ) ,

Nomenclature

Uvoltage magnitude
ηinitial phase angle of voltage
δsymbol standing for phase A, B, or C
k0grounding coefficient
P0power output of the PV power
Prefstation during normal operation
Qrefactive power commands
Ivmreactive power commands
x d magnitude of the positive-sequence
ωcurrent component
Zkmeasured impedance
∆Zactual fault impedance
Zsetadditional impedance
Rfsetting impedance
kχfault resistance
kρcontrol targets
klgrid voltage unbalance coefficient
kλzero-sequence compensation
δcoefficient

References

  1. Kouro, S.; Leon, J.I.; Vinnikov, D.; Franquelo, L.G. Grid-connected photovoltaic systems: An overview of recent research and emerging PV converter technology. IEEE Ind. Electr. Mag. 2015, 9, 47–61. [Google Scholar] [CrossRef]
  2. Jung, D.Y.; Ji, Y.H.; Park, S.H.; Jung, Y.-C.; Won, Y.-C. Interleaved soft-switching boost converter for photovoltaic power-generation system. IEEE Trans. Power Electr. 2011, 26, 1137–1145. [Google Scholar] [CrossRef]
  3. Karanayil, B.; Ceballos, S.; Pou, J. Maximum power point controller for large scale photovoltaic power plants using central inverters under partial shading conditions. IEEE Trans. Power Electr. 2018, 99, 3098–3109. [Google Scholar] [CrossRef]
  4. Hong-Seok, S.; Kwanghee, N. Dual current control scheme for PWM converter under unbalanced input voltage conditions. IEEE Trans. Ind. Electron. 1999, 46, 953–959. [Google Scholar] [CrossRef]
  5. Baran, M.E.; El-Markaby, I. Fault analysis on distribution feeders with distributed generators. IEEE Trans. Power Syst. 2005, 20, 1757–1764. [Google Scholar] [CrossRef]
  6. Kabiri, R.; Donald, G.H.; Peter McGrath, B. Control of active and reactive power ripple to mitigate unbalanced grid voltages. IEEE Trans. Ind. Appl. 2016, 52, 1660–1668. [Google Scholar] [CrossRef]
  7. Nagpal, M.; Henville, C. Impact of power-electronic sources on transmission line ground fault protection. IEEE Trans. Power Deliv. 2018, 33, 62–70. [Google Scholar] [CrossRef]
  8. Chen, S.; Tai, N.; Fan, C.; Liu, J.; Hong, S. Adaptive distance protection for grounded fault of lines connected with doubly-fed induction generators. IET Gener. Transm. Distrib. 2017, 11, 1513–1520. [Google Scholar] [CrossRef]
  9. Bollen, M.; Hassan, F. Protection. In Integration of Distributed Generation in the Power System, 1st ed.; Hooshyar, A., Azzouz, M.A., El-Saadany, E.F., Eds.; Wiley: Hoboken, NJ, USA, 2011; pp. 299–366. [Google Scholar]
  10. Zhu, S.; Xing, Y.; Sui, F. Fault component reactance relay. IEEE Trans. Power Deliv. 1996, 11, 1292–1300. [Google Scholar]
  11. Qing, L.; Zengping, W.; Yan, X. Study on the influence of TCSC on distance-relay fault protection. In Proceedings of the Transmission and Distribution Conference and Exhibition: Asia and Pacific IEEE/PES, Dalian, China, 18 August 2005; pp. 1–4. [Google Scholar]
  12. Nengling, T.; Chen, C. A new weak fault component reactance distance relay based on voltage amplitude comparison. IEEE Trans. Power Deliv. 2008, 23, 87–93. [Google Scholar] [CrossRef]
  13. Khederzadeh, M. Performance evaluation of fault component distance relay for protection of lines compensated by UPFC. In Proceedings of the 10th IET International Conference Developments in Power System Protection (DPSP 2010), Managing the Change, Manchester, UK, 29 March–1 April 2010. [Google Scholar]
  14. Yan, K.; Zhang, B.; Zhang, W.; Huang, R.; Jin, X. Analysis and improvement of relay protection for photovoltaic power station connected to grid. In Proceedings of the 2013 IEEE International Conference of IEEE Region 10 (TENCON 2013), Xi’an, China, 22 October 2013; pp. 1–4. [Google Scholar]
  15. Jia, K.; Gu, C.; Xuan, Z.; Li, L.; Lin, Y. Fault characteristics analysis and line protection design within a large-scale photovoltaic power plant. IEEE. Trans. Smart Grid 2018, 9, 4099–4108. [Google Scholar] [CrossRef]
  16. Li, B.; Yuan, Y.; Wei, L. Research on relay protection of grid-connected photovoltaic power station in the plateau. In Proceedings of the 2011 International Conference on Advanced Power System Automation and Protection, Beijing, China, 16–20 October 2011; pp. 1814–1818. [Google Scholar]
  17. Xue, S.; Yang, J.; Chen, Y.; Wang, C.; Shi, Z.; Cui, M.; Li, B. The applicability of traditional protection methods to lines emanating from VSC-HVDC interconnectors and a novel protection principle. Energies 2016, 9, 400. [Google Scholar] [CrossRef]
  18. Alam, M.M.; Leite, H.; Liang, J.; Carvalho, A.-D.S. Effects of VSC based HVDC system on distance protection of transmission lines. Int. J. Electr. Power Energy Syst. 2017, 92, 245–260. [Google Scholar] [CrossRef]
  19. Liu, Y.; Li, G.; Wang, H.; Wang, Z.; Yu, M. Research on AC line distance relay in the presence of modular multilevel converter based HVDC. In Proceedings of the 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), Xi’an, China, 25–28 October 2016; pp. 1622–1626. [Google Scholar]
  20. Hooshyar, A.; Azzouz, M.A.; El-Saadany, E.F. Distance protection of lines emanating from full-scale converter-interfaced renewable energy power plants—Part I: Problem statement. IEEE Trans. Power Deliv. 2015, 30, 1770–1780. [Google Scholar] [CrossRef]
  21. Hooshyar, A.; Azzouz, M.A.; El-Saadany, E.F. Distance protection of lines emanating from full-scale converter-interfaced renewable energy power plants—Part II: Solution description and evaluation. IEEE Trans. Power Deliv. 2015, 30, 1781–1791. [Google Scholar] [CrossRef]
  22. Jia, J.; Yang, G.; Nielsen, A.H.; Ronne-Hansen, P. Impact of VSC control strategies and incorporation of synchronous condensers on distance protection under unbalanced faults. IEEE Trans. Ind. Electr. 2019, 66, 1108–1118. [Google Scholar] [CrossRef]
  23. Ma, J.; Zhang, W.; Liu, J.; Thorp, J.S. A novel adaptive distance protection scheme for DFIG wind farm collector lines. Int. J. Electr. Power Energy Syst. 2018, 94, 234–244. [Google Scholar] [CrossRef]
  24. He, L.; Liu, C.C.; Pitto, A.; Cirio, D. Distance protection of AC grid with HVDC-connected offshore wind generators. IEEE Trans. Power Deliv. 2014, 29, 493–501. [Google Scholar] [CrossRef]
  25. Tang, J.; Song, G.; Wang, X.; Wang, C. A novel directional relay applicable to power system with wind farms. In Proceedings of the 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), Xi’an, China, 25–28 October 2016; pp. 2117–2121. [Google Scholar]
  26. Chen, Y.; Wen, M.; Yin, X.; Cai, Y.; Zheng, J. Distance protection for transmission lines of DFIG-based wind power integration system. Int. J. Electr. Power Energy Syst. 2018, 100, 438–448. [Google Scholar] [CrossRef]
  27. Yazdani, A.; Iravani, R. A unified dynamic model and control for the voltage-sourced converter under unbalanced grid conditions. IEEE Trans. Power Deliv. 2006, 21, 1620–1629. [Google Scholar] [CrossRef]
  28. Fang, Y.; Jia, K.; Yang, Z.; Bi, T.; Li, Y. Impact of inverter-interfaced renewable energy generators on distance protection and an improved scheme. IEEE Trans. Ind. Electron. 2018. [Google Scholar] [CrossRef]
  29. Jia, K.; Li, Y.; Fang, Y.; Zheng, L.; Bi, T.; Yang, Q. Transient current similarity based protection for wind farm transmission lines. Appl. Energy 2018, 225, 42–51. [Google Scholar] [CrossRef]
  30. Bergen, A.R.; Vittal, V. Generator Modeling II (Circuit Viewpoint). Power Systems Analysis, 2nd ed.; Prentice Hall: New Jersey, NJ, USA, 1999; pp. 215–269. [Google Scholar]
Figure 1. Model of a grid-connected photovoltaic (PV) power station.
Figure 1. Model of a grid-connected photovoltaic (PV) power station.
Energies 12 01578 g001
Figure 2. Operating principle of fault component distance protection: (a) Operating performance of fault component distance protection; (b) internal metallic faults; and (c) external metallic faults.
Figure 2. Operating principle of fault component distance protection: (a) Operating performance of fault component distance protection; (b) internal metallic faults; and (c) external metallic faults.
Energies 12 01578 g002
Figure 3. Influence of phase angle change of Zs on the operating performance of fault component distance protection: (a) 0° < arg(Zs) < 90°; (b) 90° < arg(Zs) < 180°; (c) −90° < arg(Zs) < 0°; and (d) −180° < arg(Zs) < −90°.
Figure 3. Influence of phase angle change of Zs on the operating performance of fault component distance protection: (a) 0° < arg(Zs) < 90°; (b) 90° < arg(Zs) < 180°; (c) −90° < arg(Zs) < 0°; and (d) −180° < arg(Zs) < −90°.
Energies 12 01578 g003
Figure 4. The characteristics of arg(Zs) with different kλ and ∆δ.
Figure 4. The characteristics of arg(Zs) with different kλ and ∆δ.
Energies 12 01578 g004
Figure 5. The characteristics of ∆θBCM with different active power commands (Pref) and the grid voltage unbalance coefficient (kρ).
Figure 5. The characteristics of ∆θBCM with different active power commands (Pref) and the grid voltage unbalance coefficient (kρ).
Energies 12 01578 g005
Figure 6. Impedance plane of measured impedance: (a) Impedance plane of measured impedance (ZmBC) for an internal phase B-to-phase C (BC) fault; and (b) impedance plane of measured impedance (ZmAG) for an internal phase-A-to-ground (AG) fault.
Figure 6. Impedance plane of measured impedance: (a) Impedance plane of measured impedance (ZmBC) for an internal phase B-to-phase C (BC) fault; and (b) impedance plane of measured impedance (ZmAG) for an internal phase-A-to-ground (AG) fault.
Energies 12 01578 g006
Figure 7. Influence of the measured impedance on the operating performance of fault component distance protection: (a) Additional impedance ∆Z is resistive-capacitive; and (b) additional impedance ∆Z is resistive-inductive.
Figure 7. Influence of the measured impedance on the operating performance of fault component distance protection: (a) Additional impedance ∆Z is resistive-capacitive; and (b) additional impedance ∆Z is resistive-inductive.
Energies 12 01578 g007
Figure 8. The simulation results of various faults occurring at 40% of the length of the transmission line from the relay located on the M side: (a) The waveforms of fault current and fault voltage under AG fault; and (b) the waveforms of fault current and fault voltage under BC fault.
Figure 8. The simulation results of various faults occurring at 40% of the length of the transmission line from the relay located on the M side: (a) The waveforms of fault current and fault voltage under AG fault; and (b) the waveforms of fault current and fault voltage under BC fault.
Energies 12 01578 g008
Figure 9. The characteristics of Zs with different influence factors under BC fault at point f: (a) The characteristics of Zs with different fault resistances; and (b) the characteristics of Zs with different reactive power commands.
Figure 9. The characteristics of Zs with different influence factors under BC fault at point f: (a) The characteristics of Zs with different fault resistances; and (b) the characteristics of Zs with different reactive power commands.
Energies 12 01578 g009
Figure 10. The simulation results of the measured impedance (Zm) under unbalanced faults occurring at f: (a) The simulation results of Zm under different metallic faults; and (b) the simulation results of Zm under unbalanced faults with 5-Ω fault resistance.
Figure 10. The simulation results of the measured impedance (Zm) under unbalanced faults occurring at f: (a) The simulation results of Zm under different metallic faults; and (b) the simulation results of Zm under unbalanced faults with 5-Ω fault resistance.
Energies 12 01578 g010aEnergies 12 01578 g010b
Figure 11. The operating performance of fault component distance protection under different fault conditions: (a) The operating performance of fault component distance protection under a BC metallic fault; (b) the operating performance of fault component distance protection under an AG metallic fault; (c) the operating performance of fault component distance protection under a BC fault with fault resistance; and (d) the operating performance of fault component distance protection under an AG fault with fault resistance.
Figure 11. The operating performance of fault component distance protection under different fault conditions: (a) The operating performance of fault component distance protection under a BC metallic fault; (b) the operating performance of fault component distance protection under an AG metallic fault; (c) the operating performance of fault component distance protection under a BC fault with fault resistance; and (d) the operating performance of fault component distance protection under an AG fault with fault resistance.
Energies 12 01578 g011aEnergies 12 01578 g011b

Share and Cite

MDPI and ACS Style

Liang, Y.; Xu, G.; Zha, W.; Wang, C. Adaptability Analysis of Fault Component Distance Protection on Transmission Lines Connected to Photovoltaic Power Stations. Energies 2019, 12, 1578. https://0-doi-org.brum.beds.ac.uk/10.3390/en12081578

AMA Style