Article

Enhanced Reactive Power Sharing and Voltage Restoration Based on Adaptive Virtual Impedance and Consensus Algorithm

by
Mohamed Keddar
1,*,
Mamadou Lamine Doumbia
1,
Karim Belmokhtar
2 and
Mohamed Della Krachai
3
1
Department of Electrical and Computer Engineering, Université du Québec à Trois-Rivières, Trois-Rivières, QC G8Z 4M3, Canada
2
Research and Innovation, Nergica, Gaspé, QC G4X 1G2, Canada
3
Department of Electrical Engineering, University of Science and Technology Mohamed Boudiaf, Oran 31000, Algeria
*
Author to whom correspondence should be addressed.
Submission received: 4 April 2022 / Revised: 28 April 2022 / Accepted: 3 May 2022 / Published: 10 May 2022

Abstract

:
In this paper, power-sharing management control on an AC islanded microgrid is investigated to achieve accurate reactive power sharing. The droop control method is primarily used to manage the active and reactive power sharing among the DGs in the microgrid. However, the line impedance mismatch causes unbalanced reactive power sharing. As a solution a consensus-based adaptive virtual impedance controller is proposed, where the consensus algorithm is used to set the reactive power mismatch; then a virtual impedance correction term is generated through a proportional-integral controller to eliminate the line impedance mismatch. Thus, reactive power sharing is achieved without knowledge of the line impedances or using a central controller. Moreover, the consensus algorithm is used to restore the AC bus voltage to the nominal value by estimating the DGs average voltage using neighbor communication to compensate for the decreased magnitude of the voltage reference. Matlab/Simulink is used to validate the accuracy of reactive power sharing and voltage restauration achievement of the proposed solution through simulation of different scenarios. In addition, a dSPACE DS1104 is used within a developed experimental testbench based on two parallel DGs to validate the effectiveness of the proposed solution in the real world.

1. Introduction

The world energy demand is increasing quickly, and it is expected to reach 50% by 2050 [1]. This is due to the increase in the population of the world and the rapid development of technologies. To accommodate this growth in energy demand, the development of new power generation and massive integration of renewable energy become a priority respecting the agreements on the emission reduction of CO2. Recently, several new technologies have been contributing to power generation plants such as the Distributed Generation (DG) using renewable energy sources, Electrolyzers (Ely) and fuel cells (FC), Electric Vehicles (EVs), and Energy Storage Systems (ESSs). Connected to a common bus with a centralized or decentralized controller and power management system with communication, they establish a new power generation system called a microgrid (MG). A MG can operate in both connected mode when it is coupled to the main grid, or autonomous mode when it is islanded [2,3].
The massive integration of Renewable Energy Resources (RES) in MGs can reduce the operation cost, increase the benefits on the environment by reducing the CO2 emissions, and create new power sources [4]. However, the nature of these sources and sudden variations in the weather cause perturbation and instability to the MG, resulting in voltage and frequency deviations. MGs are considered to have a low system inertia due to the low capacity of the DGs supplied by RES. Furthermore, the sudden changes in the connected loads may lead to critical frequency deviations and power flow management issues during the MG operation [5,6,7].
In autonomous microgrids, the connected DGs share the load power according to their power ratings for the profitability and to ensure the stability of the MG. The commonly adopted method in power sharing is the droop control approach. Active power sharing between DGs can be easily achieved using the frequency droop control method, whereas the reactive power sharing cannot be achieved easily due to the impedance mismatch between DGs which leads to voltage deviation and system instability [8,9]. To solve the inaccurate reactive power sharing issue, other ameliorated control methods have been developed [10,11,12,13]. In [10], a decentralized self-changing control was proposed using the adaptive droop control method. To increase the accuracy of reactive power sharing, an inductive virtual impedance (VI) loop was introduced; however, this method was not examined for a wide scope of working points. In [11], an adaptive droop controller was proposed to ensure dynamic stability of power sharing, where derivatives of active and reactive power are added to the traditional droop controller. Then, droop control gains were tuned adaptively conforming to the output power variations. However, the reactive power sharing was not as expected [12]. A modified Q-V droop control method was introduced in [13] to improve the power sharing accuracy. However, the reactive power sharing difference cannot be completely removed.
Other methods based on improved hierarchical control strategies have been proposed [14,15]. A secondary controller with a primary droop controller was presented in [14] to achieve accurate reactive power sharing in islanded MGs. However, a communication link between the central controller (CC) and DG’s local controller is needed, increasing the response time and the total cost. In [15], virtual impedance control was applied in islanding MGs at different levels according to transient variations in the active power. A transient control term was used in the traditional droop control by injecting frequency disturbances. However, this approach could result in lower reliability and instability of the MG because of their reliance on the central controller. Moreover, the reactive power sharing was not addressed. Nonetheless, in these methods, power-sharing accuracy, especially reactive power can be influenced by communication congestion or delays regarding the number of connected DGs [16,17]. VI-based methods were widely used to improve reactive power sharing [18,19,20]. The VI is used to eliminate the impedance mismatch between lines and then improve reactive power sharing as well system stability. Based on injection of disturbances, online impedance estimation, or using MGCC, this approach can flexibly deal with the impedance mismatch between lines as well as the variation in load power, improving the dynamic performance of the MG. In order to enhance accurate reactive power sharing between parallel DGs, a complex VI approach including resistive and inductive factors systems was introduced [21,22] where the reactive power sharing was significantly enhanced. Furthermore, the result can be better with communication-based complex VI [23]. However, the communication delays can result in less reactive power sharing accuracy and degraded performance.
Recently, consensus algorithms were combined with the adaptive VI approach in order to guarantee accurate power sharing and current harmonics sharing. In addition, the voltage and the frequency value restoration can be achieved using these algorithms. Based on the information from neighbor communication or MGCC systems, the consensus approach is used to guarantee accurate reactive power distribution. The virtual impedance of DGs is tuned by the consensus approach to move towards a common objective in terms of reactive power sharing [24,25,26]. However, the communication system should be optimized to enhance the MG stability and improve the MG performance.
When only the neighbor communication system is used, the MG cost and communication time will be reduced. This kind of communication can be used in one or two directions, depending on the system specifications. Reactive current information can be used in order to have accurate reactive power sharing. On the other hand, the active current information is used for active power sharing accuracy [27]. Moreover, to compensate for the voltage deviations and drop caused by the VI, DG output voltage restoration was introduced using a consensus algorithm [23]. The approach uses a communication system between adjacent DGs to exchange information on reactive power sharing and voltage restoration. However, this approach is dependent on communication system reliability. Microgrid reliability and efficiency are related to several parameters such as communication links and control strategy. MGCC presents a very sturdy and efficient control strategy. However, the complex communication system may increase the total cost as well as the impact of communication time delays. Therefore, decentralized control strategies are favored especially in autonomous MG where DGs, loads, and storage systems are from multiple customers. In this case, complex central communication systems should be avoided in order to reduce the information dependency on each DG.
Encouraged by this aspect, several attempts have been made by this work. Since the reactive power sharing issue is directly related to the DGs voltage and their behaviors, it can be solved based on information exchange between adjacent DGs and local information through a progressive process. The line impedance can be first estimated and tuned by each DG using the consensus algorithm; then this value can be shared with the neighbors. The VI is adaptively adjusted by the consensus algorithm to remove the mismatch between line impedance, ensuring accurate reactive power sharing without line impedance knowledge. Furthermore, the consensus control is used to compensate and restore the output voltage of each DG to the MG voltage. Therefore, the developed control contributions from this work are summarized as follows:
Adaptive virtual impedance control combined with a consensus algorithm is proposed for reactive power-sharing accuracy and parallel DGs voltage restoration with line impedance mismatch in autonomous MGs.
To achieve accurate reactive power sharing, neighbor information through a unidirectional communication link is used to estimate the VI, reducing the cost and the time delay impact of communication. Additionally, this approach cancels out the line impedance knowledge.
The proposed control approach was confirmed by experimental validation using a small-scale laboratory test bench based on MGs with two DGs.
The rest of the paper is arranged as follows: Section 2 presents the power sharing using conventional droop, the microgrid configuration, control, and modeling. Section 3 explores the proposed approach based on adaptive VI and consensus algorithms used to have accurate reactive power sharing and system voltage restoration. Then, Section 4 shows the simulation verification and Section 5 presents the experimental validation results of the proposed control approach. Finally, summary and main findings of this paper are presented in Section 6.

2. Droop Control and Reactive Power Sharing Theory

Droop control is the most used classical approach to control parallel DGs in power systems. This method presents high flexibility with good reliability and redundancy. It does not require a central controller or communication system and is mostly used in the primary control of MGs.

2.1. Droop Control

To analyze the power flow in steady state, it is assumed that the inverter is a controlled voltage source; then the dynamics of the inner control loop can be neglected. Figure 1 illustrates an inverter connected to the point of common coupling (PCC) through a line impedance Z.
Assuming a balanced 3-phase system, the power flowing in a transmission line can be derived by:
S = P + j Q = V I = E   E V Z = E   E V e j Z e j θ = E 2 Z e j θ E V Z e j θ +
where S, Q, P represent apparent, reactive, and active power, respectively. E represents the output voltage of the power inverter at an angle δ. Z represents the impedance of the transmission line between the inverter and the PCC with angles V and θ that represent the voltage at the PCC with an angle equal to zero.
Using Euler’s simplification and replacing the line impedance by Ze = R + jX, the active and reactive power equations can be written as follows [28]:
P = E X 2   + R 2 R E V cos   δ + X V sin   δ  
Q = E X 2   + R 2 X E V cos   δ + R V sin   δ  
In normal cases, the output power of a DG unit is far below the maximum transmission capability of the feeder line; thus, δ will be small. For this reason, the approximation cosδ→1 and sinδδ can be adopted. In addition, assuming that the line impedance is inductive and satisfies the condition XiRi Equations (2) and (3) become:
δ X P   E V  
E V X Q E  
Equations (4) and (5) show that the power angle strongly depends on the active power and the voltage difference depends on the reactive power. In other words, active power can be frequency controlled and reactive power regulated by voltage. This finding leads to the following common droop control equations:
ω = ω 0 m p P  
V   = V 0 n Q Q  
where V0 and ω0, represent the nominal values of the voltage and the frequency, nQ and mP represent the droop coefficients, and V, ω, represent the nominal output of the voltage and the frequency. Then, the droop control coefficients (nQ, mP) can be defined by the following equations [28,29]:
m p = Δ ω m a x P n o m i n a l  
n q = Δ v m a x Q n o m i n a l  

2.2. Reactive Power Sharing

Accurate reactive power sharing cannot be achieved by conventional droop control. In order to solve the issue and eliminate the deviations of the voltage and frequency, secondary control was used. Figure 2 shows the investigated MG configuration. It is composed of distributed generation (DG) based on renewable energy sources and a battery storage system (BSS). Each DG is connected to a common AC bus through an inverter and an LCL filter.
The control structure of the MG is based on hierarchical control using primary and secondary control levels. The primary control contains the current and voltage control loops. While the secondary control contains the consensus algorithm, adaptive virtual impedance, and droop control.

2.3. DGs Modeling and Global Control Strategy

The control strategy at the primary control level is based on proportional-integral (PI) controllers. Figure 3 shows the global control scheme of inverters for each DG. Secondary control level includes the droop controller, power calculation, the adaptive virtual impedance, and the consensus algorithm with the communication network. References of voltage and adaptive VI value are generated and sent to the primary control level. Afterward, inverter control signals are generated based on these references. An LCL filter is used to connect the inverter to the AC bus, where Lf is the inverter side inductor of the filter with Rf as internal resistance, 𝐶f is the capacitor value of the filter and finally, Lg is the inductor of the filter at the grid side with an internal resistance Rg.
The dynamic equations model can be derived using voltage and current law followed by Park transformation as follows:
L f d d t i d i q = E d E q v d v q R f i d i q + 0                 ω L f ω L f             0 i d i q  
C f d d t v d v q = i d i q i l d i l q + 0                 ω C f ω C f             0 v d v q  
where Ed, Eq represent direct and quadrature voltage before the filter, Vd, Vq after the filter, and Id, Iq the current direct and quadrature values. After simplification, the equations of the current and the voltage controllers can be written as follows [2]:
I r e f _ d = K p v + K i v S V c d r e f V c d ω C V c q + i g q I r e f _ q = K p v + K i v S V c q r e f V c q ω C V c d + i g d  
V r e f _ d = K p i + K i i S i r e f _ d i l d ω L f i l q + V c q V r e f _ q = K p i + K i i S i r e f _ q i l q ω L f i l d + V c d  
where Kpi, Kii are the proportional and the integral coefficients of the current PI controller, Kpv, Kiv are the proportional and the integral coefficients of the voltage PI controller. Vcdref and Vcqref are the voltage references calculated by the droop controller. The adaptive VI control is as follows:
V c d r e f V c q r e f = V c _ r e f d V v i _ d V c _ r e f q V v i _ q  
where Vvi_d, Vvi_q represent the references from the adaptive VI controller and Vc_refd, Vc_refq the references of the droop controller.

3. Adaptive Virtual Impedance and Consensus Algorithm

In a MG, the active and reactive power are coupled and depend on the output frequency and voltage due to the nature of the line impedance, which can be resistive inductive or both. The use of VI in combination with the physical impedance can modify the total output impedance of the DG. In this section, the proposed approach based on adaptive VI and consensus algorithms is explored.

3.1. Adaptive Virtual Impedance

VI has been used for many applications recently, such as reactive power sharing by ensuring a consistent and equivalent output impedance for all parallel DGs in the autonomous MGs [2,25,26,27]. This VI can be adjusted adaptively in order to calculate the total impedance and then the voltage reference. Thus, the total output impedance of a DG can be written as follows [27]:
Z i = Z l i n e , i + Z v , i + Z a d p , i  
Zi represents the total output impedance of the DGi and the line impedance can be represented by Zline,i. The virtual impedance can be divided into two terms, Zv,i which represents the static virtual impedance value used to ensure an inductive total impedance. The other term, Zadp,i represents the adaptive VI. Equation (15) shows that the output impedance of each DG is increased by the adaptive term in order to match with other DG impedances and eliminate the mismatch. Then, reactive power sharing can be improved using droop control relations.

3.2. Consensus Algorithm

In order to have a similar output impedance between different DGs, in this work, the adaptive VI in Equation (14) is calculated and adjusted using a consensus algorithm. To have an accurate reactive power sharing, consensus control is used to reach a general agreement among all MG agents. Thus, the droop control and reactive power coefficients must be designed to be inversely proportional, according to the following equation [26,27,28,29]:
n Q 1 Q 1 = n Q 2 Q 2 = = n Q N Q N  
By replacing (7) in (5), the reactive power flow of each DG can be written as follows:
n q i Q i = V E 0 V X i n i + V  
Therefore, to satisfy Equation (16), the term Xi/ni of each DG must be the same in Equation (17), from which the following equation can be written:
X 1 n 1 =   X 2 n 2 = = X N n N  
From Equation (18), it can be noticed that the term ni must be proportional to the line reactance Xi. Considering Equation (16), in order to obtain accurate reactive power sharing the reactance of the line must be designed to be inversely proportional to the reactive power, then the following equation can be written [23,25,26]:
X 1 Q 1 = X 2 Q 2 = = X N Q N  
The consensus control of the reactive power can be treated as a synchronization problem of a first-order linear agent system [26,27,28]. Then, Equation (20) is obtained from the linearization of Equation (15):
u Q i = n Q i Q ˙ i = C n Q e n i Q i
where, u Q i is the auxiliary control, e n i Q i represents the reactive power error between the local DG and its neighbor, and CnQ is the coupling gain. The local neighbor’s reactive power sharing error is represented by:
e n i Q i = j = N a i j n Q i Q i n Q j Q j  
where aij represents the changes in connection between DGs from the adjacency matrix. The whole consensus system can be written in matrix representation as:
u Q 1 u Q 1 · · u Q N = n Q 1 Q ˙ 1 n Q 2 Q ˙ 2 · · n Q N Q ˙ N = n Q 1 Q ˙ 1 n Q 2 Q ˙ 2 · · n Q N Q ˙ N j = N a 1 j a 2 j · · a N j n Q 1 Q 1 n Q j Q j n Q 2 Q 2 n Q j Q j · n Q N Q N n Q j Q j
Then the Adaptive VI references in Equation (14) can be presented as follows:
V v i _ d V v i _ q = R v i   ω L v i   R v i               ω L v i i g d i g q  
L v i R v i = L v i R v i u Q i k l k r  
where, L vi * and R vi * represent the resistance and inductance of the static impedance. Lvi, and Rvi are the resistance and inductance of the VI. kl and kr are adjusting gains of the consensus controller. Based on these equations, the adaptive VI implementation is illustrated in Figure 4.

3.3. Bus Voltage Restoration

In order to compensate the voltage drop caused by the droop control and the VI, a secondary voltage controller based on consensus control is used to restore the average voltage of each DG to the MG nominal voltage. This will eliminate the voltage deviation between DGs, improve the power flow control, and ensure a reliable operation of the MG. The average voltage of each DG can be defined as the average output voltage value of all MG DGs [23,26,27]:
V ˇ = j = 1 N V j N  
where V ˇ is the average voltage, Vj is the output voltage of DGj, and N is the total number of DGs connected to the MG. Using the consensus based adaptive VI control, once the virtual impedance is adaptively set and the reactive power sharing is achieved, the droop controller output voltage of each DG becomes the same. However, the DG output voltage at the filter output level cannot be identical for all the DGs due to impedance mismatch, as explained previously. This can cause deviations in the output voltage and exceed the allowable range. Therefore, a secondary control for voltage restoration should be used to regulate the average MG voltage. The DG average voltage estimation can be expressed using its own output voltage V ˇ i and its neighbor DG voltage V ˇ j .
V ˇ i t = V i t + C v j ϵ n i a i j ( V ˇ i t V ˇ j t )   d t  
where Vi is the voltage of DGi and Cv is a coupling gain. Then, the dynamics of the voltage consensus control can be expressed as follows:
V ˇ l ˙ t = V l ˙ t + C v j ϵ n i a i j ( V ˇ i t V ˇ j t )  
The implementation of the proposed approach for voltage restoration is shown in Figure 5.

4. Simulation Verification

In order to verify the effectiveness of the proposed control approach, simulation tests were conducted using MATLAB/Simulink software. The MG shown in Figure 2 was modeled in Simulink. The MG is composed of three DGs connected to renewable energy sources (solar or wind) with different rated powers and a battery storage system. All DGs are connected to the AC bus through an LCL filter and an impedance. Moreover, different loads are connected to the AC bus. All DGs are connected to a communication link in order to change information between neighbors. The sharing power ratio is 1:1:0.5 for DG1, DG2, and DG3, respectively. Table 1 shows the parameters used in this simulation. The simulation is divided into three parts. In the first one, reactive power sharing accuracy was verified using the proposed control approach. In the second one, the robustness of the control approach under load changes is explored, and finally, in the third one, the voltage restoration performance was investigated.

4.1. Case Study #1

Figure 6 represents the active power sharing between the three DGs. The active power was well shared before and after applying the proposed strategy. The reactive power sharing is shown in Figure 7, where it is not achieved using the conventional method. The proposed control strategy was applied at t = 7.5 s, which offers an accurate reactive power sharing in the desired ratio without affecting the active power sharing. The virtual resistance and reactance of each DG are illustrated in Figure 8 and Figure 9.
After activating the consensus algorithm control, DG1 and 2 resistance and reactance values become equal. This is due to their equal power-sharing ratios. While the resistance and reactance values for DG3 are larger because the sharing ratio of this DG is lower than the others. The output currents corresponding to the three DG units are indicated in Figure 10. Figure 10b,c shows a zoom before and after the application of the proposed consensus controller. Before the application of the proposed method, there was a phase shift between the three DGs currents. After t = 7.5 s, the output currents of DGs become synchronized and proportional to the nominal power demanded by loads and the phases are almost identical.

4.2. Case Study #2

In the second part of the simulations, the performance of the system was tested during load changes. In this case study, the renewable resources are operated under deloaded mode, their maximum output power is between t = 5 s and t = 7.5. Otherwise, they are operated under deloaded mode. Initially, the system load is (2.2 kW, 0.6 kVAR), after t = 2.5 s the load was increased to (3.2 kW, 0.85 kVAR), then after t = 5 s, the load was increased to (4.2 kW, 1.1 kVAR). Finally, at t = 7.5 s the load was reduced to (3.2 kW, 0.85 kVAR). The simulation results are shown in Figure 11, Figure 12, Figure 13 and Figure 14. For active and reactive power sharing and by ignoring transient periods as shown in Figure 11 and Figure 12, the consensus control eliminates progressively the reactive power error between DGs during all periods of load changes. This provides improved power sharing, as shown by these results. The output currents of each DG are shown in Figure 13. It can be seen that the currents are well synchronized and proportional to the power demand of each DG. The same result was reflected on all load change conditions during this simulation period. The load changes during simulation are represented in Figure 14.

4.3. Case Study #3

The third simulation case was dedicated to voltage restoration control. At the beginning, one load was connected to the AC bus, then at time t = 1.5 s the restoration control was activated. To verify the effectiveness of the voltage restoration control, another load was connected to the AC bus at t = 3 s. The results of this simulation are shown in Figure 15, Figure 16, Figure 17, Figure 18, Figure 19 and Figure 20. Initially, the output voltages of the three DGs are lower than the reference voltage as shown in Figure 15. After application of the proposed control (at t = 1.5 s), the output voltage of each DG was increased until the average voltage was set to the MG nominal voltage. The active and reactive power sharing was always maintained, as shown in Figure 16 and Figure 17. Likewise, the output frequency was maintained within the allowed limits (Figure 18). Figure 19 shows the average voltage of the AC bus. The latter is equal to 120 V after the activation of the restoration control algorithm, which represents the nominal value. The currents of DGs are illustrated in Figure 20, an increase regarding the power-sharing ratio for each DG was observed after time t = 3 s due to the load increase. The load changes during simulation are represented in Figure 21.

5. Experimental Validation

In order to validate the proposed control approach, the simulation results were compared with experimental ones. A laboratory-scale MG was constructed and used to validate the proposed control. A dSPACE DS1004 control board was used to implement different control algorithms. Two inverters were built using Infineon IKCM30F60GD smart modules with two DC power supplies. The inverters are connected to the AC bus through LCL filters. Inductors with different values were added to the inverter output to represent the line impedances. Finally, two inductive resistive loads are connected to the AC bus through contactors to allow connection or disconnection of these loads. The experimental parameters are illustrated in Table 2 and the benchmark is shown in Figure 22.

5.1. Case Study #1

The first scenario of experimental validation was carried out to verify the sharing of active and reactive powers. The power-sharing ratio used in these tests is the same for the two DGs. Figure 23 shows the active power. It is well shared between the two inverters, before and after the application of the proposed approach. The reactive power sharing is shown in Figure 24. It was not achieved using the conventional method until the application of the proposed control strategy after t = 7.5 s which allows accurate reactive power sharing. The output currents of inverters are illustrated in Figure 25. Figure 25b,c, shows a zoom before and after the activation of the proposed controller. A phase-shift between the output currents was observed before the application of the proposed control. After t = 7.5 s, they become synchronized.

5.2. Case Study #2

In the second scenario, another experimental test was carried out to verify the robustness of the proposed approach by increasing load. The load was increased from (280 W, 30 VAR) to (380 W, 60 VAR) at time t = 10 s. As expected, the results are similar to the simulation, both DGs follow the change and the active and reactive power was shared accurately as shown in Figure 26 and Figure 27, respectively. Figure 28 shows the voltage of the load, a slight drop was observed when the load increases. Figure 29 shows the load changes during simulation. The output currents of each DG are shown in Figure 30 at the top. The currents are well synchronized with the same amplitude, then increase when the load rises, while the DGs output voltage keeps the same value as shown in the same figure at the bottom. This confirms the effectiveness of the consensus control algorithm and the adaptive VI. Finally, the output voltages of each inverter are shown in Figure 31. They represent the phase a and b voltages. They are well synchronized with the same RMS value.

6. Conclusions

In this paper, a new power flow management algorithm was proposed to improve reactive power sharing between parallel inverters in islanded MGs. The proposed strategy was based on the adaptive VI approach with consensus algorithms in order to ensure better reactive power sharing under line impedance mismatch. The consensus algorithm was used to estimate and adjust the values of the VI. Then, the obtained VI was added to the total impedance to calculate the new reference voltage for the primary controller. This control approach improves reactive power sharing without the need of a central controller or the line impedance value. The consensus algorithm uses a simple communication link between neighbors’ DGs, minimizing the cost and increasing the efficiency of the MG. Furthermore, to compensate for the output voltage drop produced by the VI, a secondary voltage controller based on a consensus algorithm was used. This controller can restore the average voltage of each DG to the nominal MG voltage. This eliminates the voltage deviation between DGs and ensures reliable operation of the MG under hierarchical control.
Finally, simulations and experimental results were presented to validate the performance and feasibility of the proposed controller. These results show that the overall control system provides a complete solution for improving MGs dynamic performance, accurate reactive power sharing, and output voltage restoration, while ensuring the robustness of the MGs under connected load changes, uncertainties, and possible disturbances.

Author Contributions

Conceptualization, M.K.; methodology, M.K. and M.L.D.; software, M.K. and M.D.K.; validation, M.L.D., K.B. and M.D.K.; resources, M.K. and M.D.K.; writing—original draft preparation, M.K.; writing—review and editing, M.L.D., K.B. and M.D.K.; visualization, M.K. and M.D.K.; supervision, M.L.D. and K.B. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. IRENA. World Energy Transistion Outlook-1.5 °C Pathway; International Renewable Energy Agency (IRENA): Abu Dhabi, United Arab Emirates, 2021. [Google Scholar]
  2. Keddar, M.; Doumbia, M.L.; Belmokhtar, K.; Della Krachai, M. A new energy management strategy of an autonomous microgrid based on virtual impedance in multilevel droop controlled inverters. In Proceeding of International Conference on Advanced Electrical Engineering (ICAEE), Algiers, Algeria, 19–21 November 2019. [Google Scholar]
  3. Shahbazitabar, M.; Abdi, H.; Nourianfar, H.; Anvari-Moghaddam, A.; Mohammadi-Ivatloo, B.; Hatziargyriou, N. An Introduction to Microgrids, Concepts, Definition, and Classifications. Microgrids, Power Systems; Springer: Cham, Switzerland, 2021. [Google Scholar]
  4. Mahmood, D.; Javaid, N.; Ahmed, G.; Khan, S.; Monteiro, V. A Review on Optimization Strategies Integrating Renewable Energy Sources Focusing Uncertainty Factor—Paving Path to Eco-Friendly Smart Cities. Sustain. Comput. Inform. Syst. 2021, 30, 100559. [Google Scholar] [CrossRef]
  5. Kim, Y.-S.; Kim, E.-S.; Moon, S.-I. Frequency and Voltage Control Strategy of Standalone Microgrids with High Penetration of Intermittent Renewable Generation Systems. IEEE Trans. Power Syst. 2016, 31, 718–728. [Google Scholar] [CrossRef]
  6. Kerdphol, T.; Rahman, F.S.; Mitani, Y.; Watanabe, M.; Kufeoglu, S. Robust Virtual Inertia Control of an Islanded Microgrid Considering High Penetration of Renewable Energy. IEEE Access 2018, 6, 625–636. [Google Scholar] [CrossRef]
  7. Ma, D.; Liu, M.; Zhang, H.; Wang, R.; Xie, X. Accurate power sharing and voltage regulation for AC microgrids: An event-triggered coordinated control approach. IEEE Trans. Cybern. 2021, 1–11. [Google Scholar] [CrossRef] [PubMed]
  8. Raj, D.C.; Gaonkar, D.N. Frequency and voltage droop control of parallel inverters in microgrid. In Proceedings of the 2016 2nd International Conference on Control, Instrumentation, Energy & Communication (CIEC), Kolkata, India, 28–30 January 2016; pp. 407–411. [Google Scholar]
  9. Bouzid, A.E.; Sicard, P.; Yamane, A.; Paquin, J.N. Simulation of droop control strategy for parallel inverters in autonomous AC microgrids. In Proceedings of the 2016 8th International Conference on Modelling, Identification and Control (ICMIC), Algiers, Algeria, 15–17 November 2016; pp. 701–706. [Google Scholar]
  10. Hamzeh, M.; Mokhtari, H.; Karimi, H. A decentralized self-adjusting control strategy for reactive power management in an islanded multi-bus MV microgrid. Can. J. Electr. Comput. Eng. 2013, 36, 18–25. [Google Scholar] [CrossRef]
  11. Mohamed, Y.; El-Saadany, E.F. Adaptive decentralized droop controller to preserve power sharing stability of paralleled inverters in distributed generation microgrids. IEEE Trans. Power Electron. 2008, 23, 2806–2816. [Google Scholar] [CrossRef]
  12. Mahmood, H.; Michaelson, D.; Jiang, J. Reactive power sharing in islanded microgrids using adaptive voltage droop control. IEEE Trans. Smart Grid 2015, 6, 3052–3060. [Google Scholar] [CrossRef]
  13. Zhou, J.; Cheng, P. A Modified Q− V . Droop Control for Accurate Reactive Power Sharing in Distributed Generation Microgrid. IEEE Trans. Ind. Appl. 2019, 55, 4100–4109. [Google Scholar] [CrossRef]
  14. He, J.; Li, Y.W.; Blaabjerg, F. Voltage Stability and Reactive Power Sharing in Review of Active and Reactive Power Sharing Strategies in Hierarchical Controlled Microgrids. IEEE Trans. Power Electron. 2015, 30, 3389–3401. [Google Scholar] [CrossRef]
  15. Micallef, A.; Apap, M.; Staines, C.S.; Guerrero, J.M. Secondary Control for Reactive Power Sharing in Droop-Controlled Islanded Microgrids. In Proceedings of the 3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG), Aalborg, Denmark, 25–28 June 2012; pp. 492–498. [Google Scholar]
  16. Han, Y.; Li, H.; Shen, P.; Coelho, E.A.A.; Guerrero, J.M. Review of active and reactive power sharing strategies in hierarchical controlled microgrids. IEEE Trans. Power Electron. 2017, 32, 2427–2451. [Google Scholar] [CrossRef] [Green Version]
  17. Schiffer, J.; Seel, T.; Raisch, J.; Sezi, T. Voltage Stability and Reactive Power Sharing in Inverter-Based Microgrids With Consensus-Based Distributed Voltage Control. IEEE Trans. Control Syst. Technol. 2016, 24, 96–109. [Google Scholar] [CrossRef] [Green Version]
  18. Zhu, Y.; Zhuo, F.; Wang, F.; Liu, B.; Gou, R.; Zhao, Y. A virtual impedance optimization method for reactive power sharing in networked microgrid. IEEE Trans. Power Electron. 2016, 31, 2890–2904. [Google Scholar] [CrossRef]
  19. Mahmood, H.; Michaelson, D.; Jiang, J. Accurate reactive power sharing in an islanded microgrid using adaptive virtual impedances. IEEE Trans. Power Electron. 2015, 30, 1605–1617. [Google Scholar] [CrossRef]
  20. He, J.; Li, Y.W.; Guerrero, J.M.; Vasquez, J.C.; Blaabjerg, F. An islanding microgrid reactive power sharing scheme enhanced by programmed virtual impedances. In Proceedings of the 3rd IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG), Aalborg, Denmark, 25–28 June 2012; pp. 229–235. [Google Scholar]
  21. Hoang, T.V.; Lee, H.H. An Adaptive Virtual Impedance Control Scheme to Eliminate the Reactive-Power-Sharing Errors in an Islanding Meshed Microgrid. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 6, 966–976. [Google Scholar] [CrossRef]
  22. Zandi, F.; Fani, B.; Sadeghkhani, I.; Orakzadeh, A. Adaptive complex virtual impedance control scheme for accurate reactive power sharing of inverter interfaced autonomous microgrids. IET Gener. Trans. Distrib. 2018, 12, 6021–6032. [Google Scholar] [CrossRef]
  23. Zhang, H.; Kim, S.; Sun, Q.; Zhou, J. Distributed adaptive virtual impedance control for accurate reactive power sharing based on consensus control in microgrids. IEEE Trans. Smart Grid 2017, 8, 1749–1761. [Google Scholar] [CrossRef]
  24. An, R.; Liu, Z.; Liu, J. Successive-approximation-based virtual impedance tuning method for accurate reactive power sharing in islanded microgrids. IEEE Trans Power Electron. 2020, 36, 87–102. [Google Scholar] [CrossRef]
  25. Yu, L.; Shi, D.; Xu, G.; Guo, X.; Jiang, Z.; Jing, C. Consensus Control of Distributed Energy Resources in a Multi-Bus Microgrid for Reactive Power Sharing and Voltage Control. Energies 2018, 11, 2710. [Google Scholar] [CrossRef] [Green Version]
  26. Alsafran, A.S.; Daniels, M.W. Consensus Control for Reactive Power Sharing Using an Adaptive Virtual Impedance Approach. Energies 2020, 13, 2026. [Google Scholar] [CrossRef]
  27. Lyu, Z.; Wei, Q.; Zhang, Y.; Zhao, J.; Manla, E. Adaptive Virtual Impedance Droop Control Based on Consensus Control of Reactive Current. Energies 2018, 11, 1801. [Google Scholar] [CrossRef] [Green Version]
  28. Sultani, J.F. Modelling, Design and Implementation Of D-Q Control in Single-Phase Grid-Connected Inverters for Photovoltaic Systems Used in Domestic Dwellings; De Montfort University: Leicester, UK, 2013. [Google Scholar]
  29. Keddar, M.; Doumbia, M.L.; Belmokhtar, K.; Della Krachai, M. Experimental Validation of an Accurate Reactive Power-Sharing Approach Based on Adaptive Virtual Impedance and Consensus Control. In Proceedings of the 12th International Renewable Energy Congress (IREC), Hammamet, Tunisia, 26–28 October 2021; pp. 1–6. [Google Scholar]
Figure 1. Inverter connected the point of common coupling.
Figure 1. Inverter connected the point of common coupling.
Energies 15 03480 g001
Figure 2. Configuration of the investigated islanded microgrid.
Figure 2. Configuration of the investigated islanded microgrid.
Energies 15 03480 g002
Figure 3. Global control scheme of DGs.
Figure 3. Global control scheme of DGs.
Energies 15 03480 g003
Figure 4. Adaptive VI and consensus algorithm implementation.
Figure 4. Adaptive VI and consensus algorithm implementation.
Energies 15 03480 g004
Figure 5. Implementation of the reference voltage generator.
Figure 5. Implementation of the reference voltage generator.
Energies 15 03480 g005
Figure 6. Active power of DGs.
Figure 6. Active power of DGs.
Energies 15 03480 g006
Figure 7. Reactive power of DGs.
Figure 7. Reactive power of DGs.
Energies 15 03480 g007
Figure 8. Virtual impedance reactance.
Figure 8. Virtual impedance reactance.
Energies 15 03480 g008
Figure 9. Virtual impedance resistances.
Figure 9. Virtual impedance resistances.
Energies 15 03480 g009
Figure 10. Output currents of DGs, (a) output current, (b) zoom before, and (c) zoom after applying the proposed controller.
Figure 10. Output currents of DGs, (a) output current, (b) zoom before, and (c) zoom after applying the proposed controller.
Energies 15 03480 g010
Figure 11. Active power of DGs.
Figure 11. Active power of DGs.
Energies 15 03480 g011
Figure 12. Reactive power of DGs.
Figure 12. Reactive power of DGs.
Energies 15 03480 g012
Figure 13. Output current of DGs.
Figure 13. Output current of DGs.
Energies 15 03480 g013
Figure 14. Load profile.
Figure 14. Load profile.
Energies 15 03480 g014
Figure 15. Output voltage of DGs.
Figure 15. Output voltage of DGs.
Energies 15 03480 g015
Figure 16. Active power of DGs.
Figure 16. Active power of DGs.
Energies 15 03480 g016
Figure 17. Reactive power of DGs.
Figure 17. Reactive power of DGs.
Energies 15 03480 g017
Figure 18. Frequency of DGs.
Figure 18. Frequency of DGs.
Energies 15 03480 g018
Figure 19. Average AC bus voltage.
Figure 19. Average AC bus voltage.
Energies 15 03480 g019
Figure 20. Output current of DGs.
Figure 20. Output current of DGs.
Energies 15 03480 g020
Figure 21. Load profile.
Figure 21. Load profile.
Energies 15 03480 g021
Figure 22. Laboratory experimental benchmark.
Figure 22. Laboratory experimental benchmark.
Energies 15 03480 g022
Figure 23. Active power of DGs (1 div = 10 W).
Figure 23. Active power of DGs (1 div = 10 W).
Energies 15 03480 g023
Figure 24. Reactive power of DGs (1 div = 10 VAR).
Figure 24. Reactive power of DGs (1 div = 10 VAR).
Energies 15 03480 g024
Figure 25. Output currents of DGs, (a) output current, (b) zoom before, and (c) zoom after applying the proposed controller (1 div = 5 A/50 V).
Figure 25. Output currents of DGs, (a) output current, (b) zoom before, and (c) zoom after applying the proposed controller (1 div = 5 A/50 V).
Energies 15 03480 g025
Figure 26. Active power of DGs (1 di = 10 W).
Figure 26. Active power of DGs (1 di = 10 W).
Energies 15 03480 g026
Figure 27. Reactive power of DGs (1 div = 10 VAR).
Figure 27. Reactive power of DGs (1 div = 10 VAR).
Energies 15 03480 g027
Figure 28. Output voltage of DGs.
Figure 28. Output voltage of DGs.
Energies 15 03480 g028
Figure 29. Load profile.
Figure 29. Load profile.
Energies 15 03480 g029
Figure 30. Output current of DGs (1 div = 5 A/50 V).
Figure 30. Output current of DGs (1 div = 5 A/50 V).
Energies 15 03480 g030
Figure 31. Output voltage of DGs (1 div = 5 A/50 V).
Figure 31. Output voltage of DGs (1 div = 5 A/50 V).
Energies 15 03480 g031
Table 1. Simulation parameters.
Table 1. Simulation parameters.
ParametersValue
Inverter power rating5 KVA
Line voltage208 V
Bus frequency 60 Hz
Dc bus voltage 400 V
Line impedances
line 17.5 mH, 0.6 Ω
line 24.5 mH, 0.5 Ω
line 37.5 mH, 0.6 Ω
Proportional gain in PI current controller Kpi50
Integral gain in PI current controller Kii0.5
Proportional gain in PI voltage controller Kpv2
Integral gain in PI voltage controller Kiv0.5
Droop coefficient
mP1, mP22 × 10−4
mP34 × 10−4
nQ1, nQ25 × 10−4
nQ37.5 × 10−4
Load 14 kW, 1.1 kVAR
Load 22.2 kW, 0.6 kVAR
Load 3,41 kW, 0.25 kVAR
Table 2. Experimental parameters.
Table 2. Experimental parameters.
ParametersValue
Power rating500 VA
Line voltage40 V
Bus frequency 60 Hz
DC bus voltage 80 V
Line impedances
line 10.82 mH, 0.02 Ω
line 21.2 mH, 0.03 Ω
Proportional gain in PI current controller Kpi100
Integral gain in PI current controller Kii0.5
Proportional gain in PI voltage controller Kpv50
Integral gain in PI voltage controller Kiv1.5
Droop coefficient
mP12 × 10−3
mP24 × 10−3
nQ15 × 10−3
nQ27.5 × 10−3
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Keddar, M.; Doumbia, M.L.; Belmokhtar, K.; Krachai, M.D. Enhanced Reactive Power Sharing and Voltage Restoration Based on Adaptive Virtual Impedance and Consensus Algorithm. Energies 2022, 15, 3480. https://0-doi-org.brum.beds.ac.uk/10.3390/en15103480

AMA Style

Keddar M, Doumbia ML, Belmokhtar K, Krachai MD. Enhanced Reactive Power Sharing and Voltage Restoration Based on Adaptive Virtual Impedance and Consensus Algorithm. Energies. 2022; 15(10):3480. https://0-doi-org.brum.beds.ac.uk/10.3390/en15103480

Chicago/Turabian Style

Keddar, Mohamed, Mamadou Lamine Doumbia, Karim Belmokhtar, and Mohamed Della Krachai. 2022. "Enhanced Reactive Power Sharing and Voltage Restoration Based on Adaptive Virtual Impedance and Consensus Algorithm" Energies 15, no. 10: 3480. https://0-doi-org.brum.beds.ac.uk/10.3390/en15103480

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop