Next Article in Journal
Cycle Characteristics of a New High-Temperature Heat Pump Based on Absorption–Compression Revolution
Previous Article in Journal
Enhancing Urban Heating Systems Planning through Spatially Explicit Participatory Modeling
Previous Article in Special Issue
Risk Analysis of HPEM Threats for Linear RF Channel with Pyramid Horn Antenna Based on System-Level SPICE Modeling
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Comparison of Methods for Suppressing Circulating Current in Metal Sheath of Cables Connected in Parallel

1
Anhui Electric Power Design Institute Co., Ltd., China Energy Engineering Group, Hefei 230601, China
2
College of Electrical and Information Engineering, Hunan University, Changsha 410082, China
*
Author to whom correspondence should be addressed.
Submission received: 29 March 2023 / Revised: 12 May 2023 / Accepted: 19 May 2023 / Published: 23 May 2023

Abstract

:
The number of high-voltage parallel cables is rapidly increasing. The alternating magnetic field generated by the working current of power cable cores induces voltage in the adjacent metal sheath; if the sheath and earth form a circuit, the metal sheath will create a circulating current, resulting in a reduction in the load capacity of power cable and the life of cable insulation. This paper uses MATLAB to construct a model for calculating the circulating current of cables connected in parallel in the same phase, and the effects of cable arrangement, phase sequence, and loop distance of cables connected in parallel on the sheath circulating current are investigated. The induced voltage in power cable sheaths is decomposed into two components, i.e., the component resulting from the core current and the component resulting from the metal sheath. Two new sheath connection methods are proposed to suppress the sheath circulating current. Compared with traditional cross-connection grounding, the proposed methods can reduce the coupling degree between loops, thus decreasing the induced voltage and circulating current. The different grounding methods of the sheath are modeled in the environment of an electromagnetic transient program (EMTP), and the sheath circulating current is simulated and compared with the conventional cross-connection grounding method. In the asymmetric arrangement, the proposed series connection method can reduce the sheath circulating current by at least 50%; however, its increases the sheath circulating current in the symmetric arrangement.

1. Introduction

In order to meet the growing demand for electricity, it is often necessary to relocate or rebuild overhead lines, especially in urban areas. To address this issue, overhead lines are gradually replaced by power cables that have higher reliability, lower maintenance, and reduced cost. More importantly, they are not limited by urban land restrictions. The new cables are often installed in tunnels and share the same tunnel with the existing lines in order to save on costs. Multiple cables are connected in parallel to enhance the transmission capacity. As the demand for urban loads grows, parallel cables are increasingly popular [1,2,3]. Several projects have been implemented in China, e.g., the 220 kV double-circuit power cable between the Baoan Substation and Fenjin Substation (Anfen) in Shengzhen. Parallel cables are increasingly popular in electric power system, especially in urban areas [4].
The use of cables connected in parallel will lead to many problems. For instance, it requires the structure of the power cable tunnel to be more complex, and the practice enhances the electromagnetic coupling between different cable loops. Although the parameters of power cables are almost the same, the current is often non-uniformly distributed amongst each individual circuit. This will give rise to additional power losses, overloading, etc. Although overloading is of great importance, it is usually undetectable since the current transformer often monitors the total line current instead of the individual circuit current. The impacts of load current, loop distance, line segment length, grounding resistance, and grounding method on the current distribution have been extensively discussed [1,5,6,7,8,9,10,11]. IEC 60287 presented a theoretical to predict the current distribution between parallel cables. A general current distribution prediction method is proposed for multiphase distribution systems, and the proposed method is experimentally validated [7]. The analytical technique to predict the induced sheath voltage in metal sheaths of underground cables and overhead lines is overviewed in [12]. The influences of harmonic content on the current distribution of cables connected in parallel are investigated in [13]. The induced voltage of underground and rail cable are modelled in [14] and [15]. In order to deal with the current distribution installed on a metal tray, a general method for calculating the current distribution in a multiphase cable distribution system is developed [16]. The skin and proximity phenomena cannot be neglected as doing so will affect the current density distribution in multi-strand cables significantly [17].
When a high-voltage single-core power cable is under normal operation, the load current flowing cable core will generate an alternating magnetic field and induce voltage in the metal sheath through electromagnetic coupling. If the metal sheath and earth form a loop, i.e., the metal sheath is grounded at its ends, a circulating current will be produced along the sheath. This result not only generates power losses but also leads to a temperature rise and hence accelerates cable insulation ageing and affects cable capacity [18,19,20]. In addition to the uneven cable core current distribution, the parallel cables may also lead to additional sheath circulating currents. The cross-connection sheaths produce a returning path of fault current and also restrain the overvoltage in a transient state. Various metal sheath connection methods are described in the associated IEEE guidelines or in technical report of the International Council on Large Electric Systems (CIGRE). The use of mathematical models to compute the induced voltage and current in cable sheaths is also recommended. The grounding method of cable sheaths at a single point or at both ends is normally applied to minimize the induced voltage along the cable sheaths in short-cable systems. However, little attention has been paid to the multi-cable case. There is a lack of research on the problems involved in laying three or even higher number of high-voltage cable loops. Several methods have been proposed to alleviate the circuiting current, such as the use of a series resistor or inductor. A computational model for predicting the circulating current along the metal sheath under the cross-connection condition is developed in [21,22]. However, the above methods mainly deal with the single-loop case, and do not take into account the coupling effect between cable loops. The effect of the core current of other adjacent cables is not included, and the existing methods are no longer applicable to multiple cables connected in parallel.
To limit the circulating current in a metal sheath, the cables generally adopt the grounding method of cross-connection. A finite element method for calculating the cable temperature field and cable capacity has been studied and the results show that an increase in sheath circulating current will lead to an increase in cable temperature. In this paper, the induced voltage of metal sheath is firstly divided into two components; then, three new connection methods for metal sheath are proposed. Their performance in suppressing the sheath circulating current is comprehensively discussed. This paper is organized as follows: Section 2 is dedicated to the mathematical model of cables connected in parallel. A set of simulations have been performed in Section 3. Three new methods for suppressing sheath circulating current are presented and compared with each other in Section 4. The Conclusions are drawn in Section 5.

2. Modeling of Power Cable Connected in Parallel

The schematic diagram for two sub-cables of phase A is depicted in Figure 1. When the cable sheath is grounded in multiple points, a circuit is formed through the grounding point, and the current will flow through the metal sheath of cross-linked polyethylene power cable [1,16].
For the double-loop cable core and sheath, there are a total of 12 conductors. Based on the geometrical parameters of cable and the distances between two cables, the matrix U, which represents the voltage drops of conductor, can be obtained by
U = Z I
where I is the current matrix and Z is the cable impedance matrix. The four types of elements of Z can be calculated as follows.
The self-impedance of cable core [6]:
Z c c = r c + r e + j 0.1445 log D e d G M R c
The self-impedance of metal sheath [6]:
Z s s = r s + r e + j 0.1445 log D e d G M R s
The mutual impedance between cable core and metal sheath [6]:
Z s c = r e + j 0.1445 log D e d G M R s
Other mutual impedance [6]:
Z s c = r e + j 0.1445 log D e D
where r c is the alternating current (AC) resistance of cable core, r s is the AC resistance of sheath, r e is the equivalent resistance of earth, D e is the equivalent depth of earth, d GMRc is the geometric mean distance of core, d G M R s is the geometric radius of sheath and D is the spacing between the cables.
Taking the double circuits as an example, if the sheath is cross-connected, and the two ends are grounded, Equation (1) can be rewritten as:
U = Z | I c a 1 I c b 1 I c c 1 I s a 2 I s b 2 I s c 2 | = | Z C 1 C 1 Z C 1 C 12 Z C 1 S 1 Z C 1 S 2 Z C 2 C 1 Z C 2 C 2 Z S 2 S 1 Z C 2 S 2 Z C 2 S 1 Z C 1 S 2 Z S 1 S 1 Z S 1 S 2 Z C 2 S 1 Z C 2 S 2 Z S 2 S 1 Z S 2 S 2 | | I c a 1 I c b 1 I c c 1 I s a 2 I s b 2 I s c 2 |
where the 12-order impedance matrix Z is divided into 16 block matrices, each of which is a 3-order matrix, and the subscripts C1, S1, C2 and S2 of block matrix are the core of the 1st loop cable, the sheath of the 1st loop cable, the core of the 2nd loop cable, and the sheath of the 2nd loop cable, respectively.
According to Kirchhoff’s current law, the sum of each sub-cable core current is equal to the total current.
{ I c a = i = 1 n I c a i I c b = i = 1 n I c b i I c c = i = 1 n I c c i
where I c a , I c b and I c c are the current of each phase, and I c a i is the current of sub-cable i in A phase. I c b i and I c c i are similar to I c a i .
{ Δ U c a 1 = Δ U c a 2 = Δ U c a n Δ U c b 1 = Δ U c b 2 = Δ U c b n Δ U c c 1 = Δ U c c 2 = Δ U c c n
where Δ U c a n is the voltage drop of sub-cable n in A phase. Obviously, the voltage drops of the sub-cable cores of each phase are all the same.
When the metal sheath is grounded at two ends, it is easy to obtain
Δ U s a 1 = Δ U s b 1 = Δ U s c 1 = ( I s a 1 + I s b 1 + I s c 1 ) R G
where I s a 1 , I s b 1 and   I s c 1 are sheath circulating current of three phases, respectively, and R G is the grounding resistance. Substituting Equation (9) into Equation (6) will yield six equations, and their matrix form is depicted as
| Z C 1 S 1 Z C 1 S 1 Z S 1 S 1 R G Z S 1 S 1 R G Z C 2 S 1 Z C 2 S 2 Z S 2 S 2 R G Z S 2 S 2 R G | | I c a 1 I c b 1 I c c 1 I s a 2 I s b 2 I s c 2 | = | 0 0 0 0 0 0 |
where R G is a third-order matrix, each element of which is equal to R G .
Combined with Equations (7) and (8), the remaining six equations can be obtained as:
| Z C 1 C 1 Z C 2 C 2 Z C 1 C 1 Z C 2 C 2 Z C 1 S 1 Z C 2 S 2 Z C 1 S 1 Z C 2 S 2 E E 0 0 | | I c a 1 I c b 1 I c c 1 I s a 2 I s b 2 I s c 2 | = | 0 0 0 I c a I c b I c c |
where E is a 3-order unit matrix and 0 is a 3-order zeros matrix. Equations (10) and (11) contain a total of 12 equations, and then the 12 current variables can be calculated.
ε is often used to characterize the uniformity of core current distribution in parallel cables, and its calculation formula is
ε = I m a x / I m i n
where Imax and Imin are the maximum and minimum absolute value of core current in each sub-cable of parallel cables.

3. Simulation of Parallel Cable

As shown in Figure 2, the rated voltage of power cables is 220 kV, the cross-sectional area is 2000 mm2, and the total length is 1.5 km. The detailed geometric parameters of selected power cable YJLW03 are listed in Table 1. Here, the soil resistivity is 100 Ω·m, the metal sheath of power cable is under cross-connection, and the total load current is set to 2000 A.
The arrangement of parallel cable is a key factor influencing the current distribution of cables and the circulating current of metal sheaths. Two common formations are introduced in IEEE Standard 575, i.e., the flat horizontal formation and the triangular formation. In terms of the cables connected in parallel, four typical arrangements are considered in this paper, and their structures are depicted in Figure 3.
Phase spacing is the spacing between the geometric center of adjacent cables in a single loop. When double-loop cables are in a flat arrangement, the loop spacing is the spacing between the geometric center of the closest cables in a double loop, as shown in Figure 3a,c. When double-loop cables are in a vertical arrangement, the loop spacing is the spacing between the brackets, as shown in Figure 3b,d.
When the phase sequence of each loop is separate, there are various phase sequence combinations. Each arrangement of a phase sequence is written in the form of 123–456, as defined in Figure 4.
As show in Figure 5, the phase sequence of flat horizontal arrangement is ABC-cba; the flat vertical arrangement has two phase sequences, i.e., ABC-abc and ABC-cba; and the phase sequence of triangle horizontal arrangement is ABC-acb. All the double cable loops are symmetrical in space.

3.1. Phase Current Distribution

The single-loop cable containing only 3 cables has a total of A 3 2 = 6 phase sequence combination. The double-loop cable is regarded as two single-loop cables. As shown in Figure 4, it has A 3 2 A 3 2 = 36 phase sequence combinations. Due to the symmetry, only six phase sequences need to be calculated for a particular arrangement. When the phase sequence of the first loop is fixed as ABC and the phase sequence of the second loop is abc, bca, cab, acb, cba, and bac, respectively, the core current of parallel cable can be calculated. The simulation results of cable core current are listed in Table 2 and Table 3.
The non-uniformity coefficient of cable core current is depicted in Figure 6. In the case of triangular vertical arrangement, the current is almost uniformly distributed between the six conductors. The maximum non-uniformity coefficient is only 1.0426 for abc and acb, and the minimum non-uniformity coefficient is 1.0186 for cab. In terms of flat vertical arrangement, the non-uniformity coefficient varies greatly. If the phase sequence of the second loop is acb or bac, both the non-uniformity coefficients are 1.2534. When the space between three-phase cables is very small, the electromagnetic coupling between the two loops connected in parallel is relatively small, and hence the mutual impedance is enhanced. However, the phase sequence has a greater impact on the current distribution under the flat vertical arrangement. From Equations (2)–(5), it can be seen that, if the mutual impedance of sub-cables of each phase with other cables is equal, the cable core current will be ideally symmetrical.

3.2. Circulating Current Distribution

If the cables are symmetrical in space, the core current of each cable is distributed in a balanced manner. Core current and sheath circulating current can be solved according to Equations (10) and (11). The phase sequences can affect the impedance matrix elements in Equations (10) and (11), causing core current and sheath circulating current to have different simulation results under different phase sequences. The sheath circulating current of parallel cables with different phase sequences under four grounding methods has been calculated. For each grounding method, the corresponding maximum and minimum sheath circulating current, which indicate the worst and best case for circulating current suppression, respectively, were selected from these simulation results. The maximum and minimum values of each arrangement of simulated sheath circulating currents are listed in Table 4.
From Table 4, it can be seen that the phase sequence has a great impact on the circulating current of metal sheath. The maximum value is about 6 times the size of the minimum value. In the case of triangle horizontal arrangement, the difference between the maximum value and the minimum value is the smallest.
It can be seen from Figure 3 that the cable spacing D in Equation (5) is decided by phase spacing and loop spacing. Therefore, the circulating current is influenced by phase spacing and loop spacing. The influence is computed, as plotted in Figure 7. Here, parallel cables are under triangular horizontal arrangement and triangle vertical arrangement.
As the phase spacing increases, the sheath circulating current increases remarkably. As the loop spacing increases, the sheath circulating current declines remarkably. Generally, the loop spacing of triangular horizontal arrangement is larger than that of triangular vertical arrangement. The loop spacing of flat horizontal arrangement is large, meaning that it can effectively reduce the sheath circulating current. Clearly, phase spacing has a greater impact on the sheath circulating current than loop spacing.

4. Comparison of Methods for Suppressing Sheath Circulating Current

The topologies of four metal sheath connection methods are depicted in Figure 8. Scheme 1 is the traditional cross-connection method. For scheme 1, each cable is divided into 6 equal sections and the two ends of the sheath are grounded. For scheme 2, each cable is divided into 6 equal sections, the metal sheaths of the double loops are crossconnected, and the two ends of the sheath are grounded. For scheme 3, each cable is divided into 3 equal sections, and the ends of the sheath from the same loop are linked. In order to reduce the number of cross-connected boxes, scheme 2 can be simplified to scheme 4, in which each cable is divided into 4 sections, and both its first section and fourth section take 1/3 of the total length, whereas both the second section and third section take 1/6 of the total length, and the sheaths of double loops are crossly connected.
When applied in the field test, scheme 2 and scheme 3 are created by changing the connection method of cross-connection box and grounding box, respectively.
The simulated core currents of parallel cable with flat and triangle vertical arrangements in scheme 2 are listed in Table 5 and Table 6, respectively. In the case of flat vertical arrangement, which occurs when the phase sequence is bac and acb, the maximum non-uniformity coefficient is 1.2341,. In the case of a triangular arrangement, which occurs when the phase sequence is abc and acb, it is 1.0985.
In addition, the core current is affected by the grounding methods, and the non-uniformity coefficient for parallel cable is plotted in Figure 9.
In scheme 1, the induced voltage in the sheath can be divided into two components, i.e., the component induced by the cable core current, and the component induced by the metal sheath current. The equivalent circuit for a single-loop sheath in double parallel cables is shown in Figure 10.
Theoretically, if the length of the cross-connection sections is the same and the core currents of each phase are balanced, U1, U2 and U3 are approximately equal to 0 and the phase and magnitudes of U1′, U2′ and U3′ are equal. The circulating current is determined by the total induced voltage in the sheath circuit and the total impedance of the circuit. Reducing the induced voltage and increasing the loop impedance is an effective approach with which to suppress the sheath circulating current.
Figure 10 is the equivalent circuit of the sheath. Generally, U1″ is larger than U1 and U1′, U2″ is larger than U2 and U2′, and U3″ is larger than U3 and U3′. Thus, the induced voltage by the sheath circulating current of the other loop, such as U1″, U2″ and U3″, can generate a large circulating current. The lower the coupling degree of each cable sheath is, the lower the values of U1″, U2″ and U3″ will be. In order to study the principle of scheme 3 to suppress the sheath circulating current, the core current and sheath circulating current of parallel cable under triangular horizontal arrangement are listed in Table 7.
In scheme 3, the circulating current is significantly reduced in all phase sequences, except for the symmetrical phase sequence ABC-acb, and the circulating current is reduced by up to 75% in the case of ABC-abc phase sequence. When the asymmetrical parallel cables adopt scheme 3, each loop only has one sheath circuit and the direction of Is2 is opposite to Is1 and Is3. At this time, the coupling between the sheaths of different cable loops is reduced, which makes the coupling between U1″, U2″ and U3″ lower than that in scheme 1.
From Table 7, in scheme 1, the optimal phase sequence under triangular horizontal arrangement is ABC-acb, and U1′ and U1″, U2′ and U2″, and U3′ and U3″ are arranged in the opposite direction in the same loop. Since the ABC-acb phase sequence is spatially symmetrical, their phase and magnitude of circulating currents are equal in two sheath loops, respectively, which makes them mutually suppressed.
As shown in Figure 11, each sheath circuit consists of the sheaths of all parallel cables in scheme 3. The impedance matrix of parallel cable in scheme 3 is derived from the transfomation impedance matrix in scheme 1. When the parallel cable adopts scheme 3, its impedance matrix is symmetrical even though the arrangement of parallel cables is asymmetric. The coupling between the sheaths will suppress the circulating current.
To verify the proposed method, simulations are performed for each phase sequence under the triangular horizontal arrangement. The circulating currents of the metal sheaths are shown in Table 8.
The circulating current of sheath in scheme 2 is remarkably smaller than that in scheme 1, and the phase and magnitude of open-circuit voltage in three circuits are equal, respectively, whether the core currents of each sub-cable are equal or unequal. The circulating currents of parallel cables in schemes 1 and 2 under symmetrical arrangement are equal. When the sheath circulating current is significantly reduced, the shielding effect of the sheath on the core is weakened and the core current distribution under this situation will be very close to that under one-end grounding situation. Hence, if the non-uniformity coefficient ε under one-end grounding situation is lower than 1.2, scheme 2 can be applied to parallel cable.

5. Conclusions

The following conclusions can be drawn:
  • We have established the calculation model for the circulating current of double cables. The calculation result indicates that the core current distribution is considerably different depending on the arrangement used. As the phase spacing increases, the sheath circulating current increases remarkably. As the loop spacing increases, the sheath circulating current declines remarkably.
  • Since the coupling between the sheaths of different cable loops is reduced, the method of cross-connection between the loop can reduce the sheath current significantly. Moreover, compared to the former, the method of sheath linking in series is more effective due to the higher decoupling effect generated by this technique.
  • For the method of cross-connection between the loop, the core current distribution in parallel cables is similar to that obtained by using a one-end grounding method. The method of cross-connection between the loop can only be applied in the situation that the non-uniformity coefficient of parallel cable is lower than 1.2.

Author Contributions

Conceptualization, W.Z.; methodology, J.Y.; software, J.Y.; validation, H.B.; investigation, R.W.; resources, R.W.; data curation, S.W.; writing—original draft preparation, J.Y.; writing—review and editing, Y.L.; visualization, W.Y.; supervision, H.B.; project administration, W.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Du, Y.; Burnett, J. Current distribution in single-core cables connected in parallel. IEEE Proc.-Gener. Transm. Distrib. 2001, 148, 406–412. [Google Scholar] [CrossRef]
  2. Wang, Y.X. Calculation & analysis of sequence impedance for parallel multi-circuit cable lines. In Proceedings of the 2010 International Conference on Power System Technology, Zhejiang, China, 24–28 October 2010. [Google Scholar]
  3. Todorovski, M.; Ackovski, R. Equivalent Circuit of Single-Core Cable Lines Suitable for Grounding Systems Analysis Under Line-to-Ground Faults. IEEE Trans. Power Del. 2014, 29, 751–759. [Google Scholar] [CrossRef]
  4. Wang, H. Design of Transmission Scheme for Two 220kV Parallel Cables in Phase. Master’s Thesis, Shenzhen University, Shenzhen, China, 2018. [Google Scholar]
  5. Li, Z.; Zhong, X. Simulation of Current Distribution in Parallel Single-Core Cables Based on Finite Element Method. In Proceedings of the 2015 Fifth International Conference on Instrumentation and Measurement, Computer, Communication and Control (IMCCC), Qinhuangdao, China, 18–20 September 2015; pp. 411–415. [Google Scholar]
  6. Zhang, P.L. Study on optimization of laying mode of two parallel high voltage cables in the same phase of two circuits. Energy Report. 2022, 8, 1839–1846. [Google Scholar] [CrossRef]
  7. Artur, C. Optimization of Spatial Configuration of Multistrand Cable Lines. Energies 2020, 13, 5923. [Google Scholar]
  8. Li, L.; Yong, J.; Xu, W. Single-Sheath bounding—A new method to bond/ground cable sheaths. IEEE Trans. Power Del. 2020, 35, 1065–1068. [Google Scholar] [CrossRef]
  9. Wang, X.; Yong, J.; Li, L. Investigation on the implementation of the single-sheath bonding method for power cables. IEEE Trans. Power Del. 2022, 37, 1171–1179. [Google Scholar] [CrossRef]
  10. Qui, L.; Zhang, L.; Wang, E.; Zhu, H.; Xu, X.; Chen, X. Investigation on Circulation Current Calculation and Grounding Methods of Multi-circuit Cables. In Proceedings of the 2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE), Chongqing, China, 25–29 September 2022. [Google Scholar]
  11. Du, X.; Liu, X.; Tang, Y.; Li, T.; Wang, S.; Li, N. Research on the Optimization of Grounding Methods and Power Loss Reduction Based on AC 500kV XLPE Submarine Cable Project. In Proceedings of the IEEE International Conference on the Properties and Applications of Dielectric Materials (ICPADM), Johor Bahru, Malaysia, 12–14 July 2021; pp. 394–397. [Google Scholar]
  12. Shaban, R.; Salam, M.A. Induced sheath voltage in power cables: A review. Renew. Sustain. Energy Rev. 2016, 62, 1236–1251. [Google Scholar]
  13. Masoumeh, R.; Mohammad, M. Effects of non-sinusoidal current on current division, ampacity and magnetic field of parallel power cables. IET Sci. Meas. Technol. 2017, 11, 553–562. [Google Scholar]
  14. Wang, H.; Wu, Z. Study on Induced Voltage and Circulation Current of Metal Layer in Single-Core Cable of High-Speed Railway Power Transmission Line. Energies 2022, 15, 5010. [Google Scholar] [CrossRef]
  15. Santos, M.; Angel Calafat, M. Dynamic simulation of induced voltages in high voltage cable sheaths: Steady state approach. Int. J. Electr. Power Energy Syst. 2019, 105, 1–16. [Google Scholar] [CrossRef]
  16. Du, Y.; Yuan, Y.Z. Current Distribution in Parallel Single-Core Cables on Metal Tray. IEEE Trans. Ind. Appl. 2008, 44, 1886–1891. [Google Scholar] [CrossRef]
  17. Cywiński, A.; Chwastek, K. Modeling of skin and proximity effects in multi-bundle cable lines. In Proceedings of the 2019 Progress in Applied Electrical Engineering (PAEE), Koscielisko, Poland, 17–21 June 2019. [Google Scholar]
  18. Liu, Y.; Wang, L.; Cao, X.L. Calculation of Circulating Current in Sheaths of Two Circuit Arranged Cables and Analyses of Influencing Factors. High Volt. Eng. 2007, 33, 143–146. [Google Scholar]
  19. He, W.; Li, H.; Tu, J.Y. Diagnosis and Location of High-voltage Cable Fault Based on Sheath Current. In Proceedings of the 2018 International Conference on Power System Technology (POWERCON), Guangzhou, China, 6–8 November 2018. [Google Scholar]
  20. Massimo, M.; Giovanni, M. The Feasibility of Cable Sheath Fault Detection by Monitoring Sheath-to-Ground Currents at the Ends of Cross-Bonding Sections. IEEE Trans. Ind. Appl. 2015, 51, 5376–5384. [Google Scholar]
  21. Jung, C.K.; Lee, J.B.; Kang, J.W.; Wang, X.H.; Song, Y.H. Sheath current characteristic and its reduction on underground power cable system. In Proceedings of the IEEE Power Engineering Society General Meeting, San Francisco, CA, USA, 16 June 2005; pp. 2562–2569. [Google Scholar]
  22. Zong, H.B.; Gao, Q.; Wang, R.L.; Wang, H.M.; Liu, Y. Calculation and Restraining Method for Circulating Current of Single Core High Voltage Cable. In Proceedings of the 2nd International Conference on Electrical Materials and Power Equipment, Guangzhou, China, 7–10 April 2019. [Google Scholar]
Figure 1. Schematic diagram of current distribution for cables connected in parallel. Note: I C A n is the core current of sub-cable n of phase A, I SAn is the metal sheath current of sub-cables n of phase A, D is the distance between the geometric center of two cables.
Figure 1. Schematic diagram of current distribution for cables connected in parallel. Note: I C A n is the core current of sub-cable n of phase A, I SAn is the metal sheath current of sub-cables n of phase A, D is the distance between the geometric center of two cables.
Energies 16 04265 g001
Figure 2. Cross-sectional structure of cable YJLW03.
Figure 2. Cross-sectional structure of cable YJLW03.
Energies 16 04265 g002
Figure 3. Typical arrangements of parallel cables. (a) Flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement, (d) triangle vertical arrangement.
Figure 3. Typical arrangements of parallel cables. (a) Flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement, (d) triangle vertical arrangement.
Energies 16 04265 g003
Figure 4. The number of parallel cables. (a) Flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement, (d) triangle vertical arrangement.
Figure 4. The number of parallel cables. (a) Flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement, (d) triangle vertical arrangement.
Energies 16 04265 g004
Figure 5. Symmetrical distribution of double parallel cables. (a) flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement.
Figure 5. Symmetrical distribution of double parallel cables. (a) flat horizontal arrangement, (b) flat vertical arrangement, (c) triangle horizontal arrangement.
Energies 16 04265 g005aEnergies 16 04265 g005b
Figure 6. Non-uniformity coefficient of current distribution.
Figure 6. Non-uniformity coefficient of current distribution.
Energies 16 04265 g006
Figure 7. Distribution of circulating current. (a) Circulating current versus phase spacing; (b) circulating current versus loop spacing.
Figure 7. Distribution of circulating current. (a) Circulating current versus phase spacing; (b) circulating current versus loop spacing.
Energies 16 04265 g007
Figure 8. Topology diagram of grounding methods. (a) Scheme 1, (b) Scheme 2, (c) Scheme 3, (d) Scheme 4.
Figure 8. Topology diagram of grounding methods. (a) Scheme 1, (b) Scheme 2, (c) Scheme 3, (d) Scheme 4.
Energies 16 04265 g008
Figure 9. Effect of grounding method on core current as well as non-uniformity coefficient. Here, I denotes scheme 1 under triangular vertical arrangement; II denotes scheme 2 under triangular vertical arrangement; III denotes one-end grounding method under triangular vertical arrangement; IV denotes scheme 1 under flat vertical arrangement; V denotes scheme 2 under flat vertical arrangement; VI denotes one-end grounding method under flat vertical arrangement.
Figure 9. Effect of grounding method on core current as well as non-uniformity coefficient. Here, I denotes scheme 1 under triangular vertical arrangement; II denotes scheme 2 under triangular vertical arrangement; III denotes one-end grounding method under triangular vertical arrangement; IV denotes scheme 1 under flat vertical arrangement; V denotes scheme 2 under flat vertical arrangement; VI denotes one-end grounding method under flat vertical arrangement.
Energies 16 04265 g009
Figure 10. Equivalent circuit for sheath of single loop in double parallel cables. Note: Is1, Is2 and Is3 are the sheath circulating currents: U1, U2 and U3 are the induced voltages from the core currents of loop itself; U1′, U2′ and U3′ are the induced voltages from the core current of the other loop; U1″, U2″ and U3″ are the induced voltage from the sheath circulating current of the other loop; RG1, RG2 are the grounding resistances; Re is the equivalent resistance of earth.
Figure 10. Equivalent circuit for sheath of single loop in double parallel cables. Note: Is1, Is2 and Is3 are the sheath circulating currents: U1, U2 and U3 are the induced voltages from the core currents of loop itself; U1′, U2′ and U3′ are the induced voltages from the core current of the other loop; U1″, U2″ and U3″ are the induced voltage from the sheath circulating current of the other loop; RG1, RG2 are the grounding resistances; Re is the equivalent resistance of earth.
Energies 16 04265 g010
Figure 11. Equivalent circuit of scheme 3.
Figure 11. Equivalent circuit of scheme 3.
Energies 16 04265 g011
Table 1. Geometric parameters of cable YJLW03.
Table 1. Geometric parameters of cable YJLW03.
CableThickness (mm)Width (mm)
Cable core54.454.4
Metal sheath2.9136.7
Cable jacket5.0146.7
Table 2. Load current distribution for parallel cables under flat vertical arrangement.
Table 2. Load current distribution for parallel cables under flat vertical arrangement.
Phase SequencePhaseCore Current (A)ε
abcA11000.001
A21000.00
B11000.00
B21000.00
C11000.00
C21000.00
bcaA11023.071.2343
A21013.70
B11094.82
B2905.18
C1895.50
C21105.30
cabA1905.181.2343
A21094.82
B11105.3
B2895.5
C11013.7
C21023.07
acbA11012.271.2599
A2997.14
B11123.29
B2891.55
C1897.6
C21125.21
cbaA11000.001
A21000.00
B11000.00
B21000.00
C11000.00
C21000.00
bacA1891.551.2599
A21123.3
B11125.21
B2897.6
C1997.14
C21012.27
Table 3. Load current distribution for parallel cables under triangle vertical arrangement.
Table 3. Load current distribution for parallel cables under triangle vertical arrangement.
Phase SequencePhaseCore Current (A)ε
abcA1982.041.0426
A21018.18
B1995.28
B21005.17
C11020.86
C2979.18
bcaA11007.201.0319
A2992.83
B1984.94
B21015.12
C11006.92
C2993.14
cabA1991.701.0186
A21008.30
B11009.25
B2990.80
C1995.64
C21004.62
acbA1982.041.0426
A21018.18
B1995.28
B21005.17
C11020.86
C2979.18
cbaA1990.531.0197
A21010.00
B11008.51
B2991.70
C1995.12
C21006.35
bacA11008.601.0252
A2991.67
B1986.04
B21014.85
C11008.76
C2992.13
Table 4. Maximum and minimum circulating currents.
Table 4. Maximum and minimum circulating currents.
Grounding MethodCase ICase IICase IIICase IV
Maximum circulating current56.6637.8514.5735.92
Phase sequenceABC-bcaABC-bcaABC-abcABC-abc
Minimum circulating current8.936.927.1218.53
Phase sequenceABC-cbaABC-abcABC-bcaABC-bca
Table 5. Core current of parallel cables with flat vertical arrangement in scheme 2.
Table 5. Core current of parallel cables with flat vertical arrangement in scheme 2.
Phase SequencePhaseCore Current (A)ε
abcA11000.001
A21000.00
B11000.00
B21000.00
C11000.00
C21000.00
bcaA11014.881.1845
A21029.26
B11084.70
B2915.74
C1918.1
C21082.63
cabA1915.731.1845
A21084.70
B11082.63
B2918.10
C11029.26
C21014.88
acbA11002.741.2341
A21010.39
B11115.75
B2904.10
C1918.70
C21103.70
cbaA11000.001
A21000.00
B11000.00
B21000.00
C11000.00
C21000.00
bacA1904.101.2341
A21115.76
B11103.70
B2918.70
C11010.39
C21002.74
Table 6. Core current of parallel cables with triangle vertical arrangement in Scheme 2.
Table 6. Core current of parallel cables with triangle vertical arrangement in Scheme 2.
Phase SequencePhaseCore Current (A)ε
abcA1953.041.0985
A21046.96
B11024.03
B2977.46
C11022.47
C2979.09
bcaA1993.711.0466
A21006.57
B1982.65
B21017.91
C11022.76
C2979.09
cabA1993.791.0466
A21006.48
B11022.78
B2977.23
C1981.06
C21019.43
acbA1953.041.0985
A21046.95
B11024.03
B2977.45
C11022.47
C2979.09
cbaA1992.231.0466
A21007.80
B11022.80
B2977.81
C1980.16
C21021.85
bacA1994.281.0506
A21005.74
B1984.18
B21017.96
C11024.98
C2975.58
Table 7. Circulating current of metal sheath under triangular horizontal arrangement.
Table 7. Circulating current of metal sheath under triangular horizontal arrangement.
Triangular Horizontal ArrangementABC-abcABC-acbABC-bac
Scheme 1 Ismax (A)48.606.4943.81
Scheme 1 ΣUmax (V)119.1524.31163.1
Scheme 3 Ismax (A)12.515.112.9
Scheme 3 ΣUmax (V)23.828.2723.51
Note: ΣUmax is the maximum value of open-circuit voltage of sheath circuit; Ismax is the maximum circulating current.
Table 8. Circulating current and open-circuit voltage in schemes 1 and 2.
Table 8. Circulating current and open-circuit voltage in schemes 1 and 2.
Triangular Horizontal ArrangementABC-abcABC-acbABC-bac
Scheme 1 Ismax (A)48.606.4943.81
Scheme 1 ΣUmax (V)119.1515.27102
Scheme 2 Ismax (A)0.516.493.04
Scheme 2 ΣUmax (V)2.3330.5315.66
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Wu, R.; Zou, W.; Yuan, J.; Bao, H.; Wang, S.; Liu, Y.; Yang, W. Comparison of Methods for Suppressing Circulating Current in Metal Sheath of Cables Connected in Parallel. Energies 2023, 16, 4265. https://0-doi-org.brum.beds.ac.uk/10.3390/en16114265

AMA Style

Wu R, Zou W, Yuan J, Bao H, Wang S, Liu Y, Yang W. Comparison of Methods for Suppressing Circulating Current in Metal Sheath of Cables Connected in Parallel. Energies. 2023; 16(11):4265. https://0-doi-org.brum.beds.ac.uk/10.3390/en16114265

Chicago/Turabian Style

Wu, Rui, Weilin Zou, Jie Yuan, Hua Bao, Shuaijie Wang, Yufeng Liu, and Wentao Yang. 2023. "Comparison of Methods for Suppressing Circulating Current in Metal Sheath of Cables Connected in Parallel" Energies 16, no. 11: 4265. https://0-doi-org.brum.beds.ac.uk/10.3390/en16114265

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop