Article

Procedure for Improving the Energy, Environmental and Economic Sustainability of Transformation Houses

by
Vicente León-Martínez
,
Elisa Peñalvo-López
*,
Clara Andrada-Monrós
,
Jorge Cano-Martínez
,
Amparo León-Vinet
and
Laura Molina-Cañamero
Institute for Energy Engieneering, Universitat Politècnica de València, 46022 Valencia, Spain
*
Author to whom correspondence should be addressed.
Submission received: 16 March 2022 / Revised: 10 April 2022 / Accepted: 12 April 2022 / Published: 21 April 2022
(This article belongs to the Section Electrical, Electronics and Communications Engineering)

Abstract

:
A procedure for improving the energy, economic and environmental sustainability of the transformation houses in low-voltage distribution networks is described in this paper. This procedure is based on the reduction of the transformer consumption, copper and core losses. Likewise, the procedure distinguishes between transformation houses with old and new transformers. The reduction of core losses, replacing transformers with others of lower power or that are more efficient, achieves significant improvements in energy and environmental aspects. The reduction of copper losses, and applying reactive compensation techniques, such as harmonic filtering and load balancing, applied in old and new transformation houses, have a greater impact on cost savings, especially when there are capacitive consumptions, as the Circular 3/2020 of the National Markets and Competition Commission of Spain determines. The procedure has been applied to an industrial transformation house, which has an old 1600 kVA transformer, resulting in significant economic savings and CO2 reductions of more than 60%, after replacing the current transformer with a more efficient one.

1. Introduction

The transformers of the electrical distribution networks, used in industrial, commercial and residential activities, have significant energy consumptions and give rise to high carbon dioxide emissions into the atmosphere. Consequently, these machines affect the energy and environmental sustainability of electrical systems [1,2,3,4]. The energy consumption of transformers is due to their copper and core losses, as is well-known [5,6,7,8,9,10]. A report carried out in 2008 for the project “Strategies for development and diffusion of Energy Efficient Distribution Transformers (SEEDT)” [11] estimated the percentage of energy losses caused by distribution transformers is a third of the total losses in the electrical networks. That same report counted more than 4.5 million transformers in the distribution networks of the EU-27, with energy consumption—caused by losses—of 33.4 TWh/year, of which 24.1 TWh/year corresponded to core losses, and 9.3 TWh/year was due to copper losses. The saving potential estimated by the report reached 12 TWh/year and a reduction in CO2 emissions of up to 4 million tons/year of CO2 in the year 2025 [12] and was the most favorable scenario for a rapid replacement of existing transformers for more efficient ones, which had only 49% losses in the core than current transformers.
Following the proposals presented by the SEEDT project, organizations [13,14] and companies in the electricity sector [15,16,17,18] have promoted changes in regulations [19,20,21,22,23,24,25,26,27,28,29] to favor the manufacture and use of efficient transformers [30,31].
Aware of the importance of reducing the transformers’ own consumptions, as a necessary step to promote the circular economy and guarantee energy and environmental sustainability in the electricity sector, this paper describes a procedure to improve the sustainability of transformation houses in low-voltage distribution networks. This procedure is based on the reduction of transformer copper and core losses.
Actions to reduce copper losses were analyzed in a previous article [32]. These consist of minimizing the values of reactive, unbalanced and distortion currents, using well-known techniques, such as reactive power compensation and the use of harmonic filters. As a novelty, the minimization of unbalanced current is achieved using the active and reactive components of the unbalanced power vector ( S uip , S uiq ) [33]. These quantities provide sufficient information to network operators to obtain a more equitable distribution, in real-time, of the loads connected to the transformers. Copper loss reduction techniques are complementary to actions to reduce core losses and can be applied to both old, inefficient, transformers and efficient transformers.
The reduction of losses in the core is achieved in the procedure by replacing the old transformers with more efficient ones, of equal or lesser power. The use of efficient, lower-power transformers considerably improves the energy sustainability of transformation centers, larger than the improvement derived from the reduction of copper losses.
The procedure for sustainability improvement has been applied to a transformation house of the low-voltage distribution network of an industrial estate, which has a 1600 kVA transformer, 25 years old, from the manufacturer Ormazabal. The study has focused on energy, environmental and economic aspects. For the energy study, a measurement campaign has been carried out, using the FLUKE 435 Series II network analyzer, whose loss calculator allows for the copper losses due to each component of the secondary currents to be measured separately. The environmental effects caused by copper and core losses, that is, the amount of emissions of carbon dioxide and other gases, have been determined using the emission factor from Spain (0.241 kg CO2/kWh), corresponding to the year 2019 [34], prior to which the measurement campaign was made. The economic effects have been obtained by applying Circular 3/2020 of the National Markets and Competition Commission of Spain [35]. The penalties for capacitive consumptions caused by two permanently connected capacitor banks Q c 1 = 3 × 25   kVAr and Q c 2 = 3 × 100   kVAr amount to tens of thousands of euros per year.
Finally, the energy, environmental and economic sustainability improvements resulting from the application of the procedure in the transformation house of the example are summarized in the conclusions.

2. Economic Costs of Transformer Losses and Charges for Capacitive Consumptions

Nowadays, the costs derived from energy losses in distribution transformers deserve special attention due to the high cost of energy. In Spain, these costs are obtained through the energy billing term [35],
F E = p = 1 p = i T e p · W p  
being:
  • F E = billed energy, in euros;
  • T e p = energy price in the hourly period p , expressed in EUR/kWh (Table 1), for the 6.1 TDA toll, where the transformation houses are included;
  • W p = energy lost by the transformer in the hourly period p , expressed in kWh;
  • i = the number of hourly periods of the transmission and distribution tolls.
Table 1 shows the strong increase in energy prices, especially during off-peak hours (up to 25 times), the result of which has been a reduction in the difference in prices between peak, flat and off-peak hours.
The energy is supplied in the transformation houses according to the 6.1 TDA toll, with voltage values between 1 and 30 kV, as shown in Table 2.
For the purposes of calculating energy costs, according to Equation (1), the prices of each hourly period in Table 1 must be applied to the supplies made at the times indicated in Table 3, based on the type of day. Five types of days are distinguished, in the peninsular territory of Spain, namely [35]:
  • Type A: from Monday to Friday, excluding high season holidays (January, February, July and December);
  • Type B: from Monday to Friday, excluding mid-high season holidays (March and November);
  • Type B1: from Monday to Friday, except for mid-season holidays (June, August and September);
  • Type C: from Monday to Friday, excluding low season holidays (April, May and October).
  • Type D: Saturdays, Sundays, holidays and January 6.
Likewise, in order to ensure the quality of the electricity supply, Circular 3/2020, of the National Commission of Markets and Competition of Spain, January 15, establishes that the supplies made with the 6.1 toll:
  • Will be penalized for all capacitive consumptions supplied under power factors (PF) less than 0.98, between 0 and 8 h, on working days, and 24 h on holidays;
  • Will not be penalized for capacitive consumptions outside these periods, even when the power factor is less than 0.98, or when the power factor in said periods is greater than 0.98.
The value of the power factor is obtained by the electrical companies, in each hourly period, as:
P F = W p W p 2 + W q 2  
where W p is the active energy (in kWh) and W q is the net reactive energy (in kVAr-h), calculated as the difference between the inductive and capacitive reactive energy supplies in the hourly period.
The surcharge or penalty for capacitive reactive power supplies (RCAP) is calculated as [36]:
R C A P = 0.05   · Δ W q
being:
Δ W q = W q 0.20306 · W p
the value of the net reactive energy supplies that exceed those corresponding to a power factor of 0.98 capacitive (0.20306   W p ). In other words, 20.306% of the capacitive reactive power supplies are not penalized.

3. Proposed Procedure for Improving Sustainability of Transformation Houses

Improving the sustainability of the transformation houses of the electrical distribution networks requires reducing the losses of the existing transformers in them. For this, the proposed methodology has two main steps (Figure 1): (1) the reduction of copper losses, and (2) the reduction of core losses.

3.1. Reduction of Copper Losses

This consists of reducing the value of fundamental frequency currents, due to reactive power supplies and/or imbalances, as well as losses caused by non-fundamental frequency currents.
This step can be applied both in transformation houses with old (inefficient) and new (efficient) transformers.

3.1.1. Reduction of Copper Losses Caused by Reactive Currents

Losses caused by fundamental frequency reactive currents ( P c r + ) are usually the main copper losses of transformers in distribution networks and on which the managers of these electricity networks have the greatest savings. These losses can be calculated from the fundamental-frequency positive-sequence reactive powers Q + and line-to-neutral voltages, as follows:
P c r + = 1 3   r c c · ( Q + V + ) 2  
measured in the secondary of the transformer, and the short-circuit resistance of the transformers, and is obtained by:
r c c = P c N · ( V 20 S N ) 2
where V 20 is the RMS value of the secondary line-to-line no-load voltages, P c N is the rated copper power losses, determined according to IEC 60076-1 [37], and S N is the transformer rated power.
Losses due to the reactive currents can be greatly reduced by using relatively inexpensive devices such as capacitor banks. In highly distorted electrical networks, capacitor banks can be replaced by harmonic filters, both active and passive, which are capable of jointly reducing load losses caused by reactive and distortion currents.
However, the use of non-variable compensation devices, both capacitor banks and passive filters, can be the cause of overcompensation, which usually increases the value of these losses in distribution transformers even above the existing values without reactive compensation devices. This case will be dealt with in more detail in the application case, in Section 4.

3.1.2. Reduction of Copper Losses Caused by Imbalanced Currents

Unbalances in the active power and reactive power supplies give rise to losses due to the load on the transformer, of value:
P c u = 3   r c c · ( I 2 + I 0 2 )
where I and I 0 are, respectively, the negative and zero sequence components of the transformer secondary currents and r c c is determined by (6).
Currently, devices are known [38,39,40,41,42] for reducing unbalanced currents, which also have the ability to compensate for reactive power ( Q + ) and, therefore, can additionally reduce the losses due to reactive currents ( P c r + ), defined by (5).
However, as indicated in Figure 1, the losses caused in the transformers due to unbalanced loads can be reduced, in industrial practice, by equitably distributing the active power and reactive power supplies between the secondary phases. To carry out this task, the managers of the electrical networks can use the representation of the angles ( α p and α q ) of the following vector quantities [33]:
S u i p P A + a 2 P B + a   P C = S u i p α p   S u i q Q A + a 2 Q B + a Q C = S u i q α q
The first one ( S u i p ) measures the effects of active power imbalances ( P A ,   P B ,   P C ) supplied in each phase ( z = A , B , C ) of the transformer secondary, where a = 1 ∠ 120°. The second vector quantity ( S u i q ) determines the effects of unbalances in reactive power supplies ( Q A ,   Q B ,   Q C ).
The angles α p and α q can have values between 0° and 360°, and each phase of a three-phase system occupies a spatial sector of 120°. Imbalances in phase A correspond to the values of the angles α p and α q between −60° and 60°. Imbalances in phase B give values of these angles between −60° and −180° and imbalances in phase C correspond to the values of α p and α q between 60° and 180°.
The ends of the segments represented in Figure 2a,b indicate the angular positions ( α p and α q ) of the components S u i p and S u i q of the imbalance power vector. Therefore, these segments determine the phases of the transformer in which the imbalances caused by active loads (Figure 2a) and reactive loads (Figure 2b) have a greater value. These representations can be known in real-time and therefore help network operators to distribute loads more evenly.

3.1.3. Reduction of Copper Losses Caused by Harmonic Currents

The losses due to the circulation of harmonic currents through the transformer windings are obtained by:
P c h = r c c · z = A , B , C I h z 2 = r c c · z = A , B , C n 1 I n z 2  
where I h z are the RMS values of the harmonic currents in each phase of the transformers ( z = A , B , C ), n = f n / f 1 is the ratio between each harmonic frequency ( f n ) and the fundamental frequency ( f 1 = 50 ÷ 60   Hz ) and r c c is the short-circuit resistance, determined according to (6).
The reduction of these losses can be done using passive or active harmonic filters. The use of passive filters is recommended, due to their cheaper cost—if the harmonic pollution is not too high. The elimination of harmonics of a very high value can be carried out by passive filters of the first order, tuned to the frequency ( f n ) of the harmonic to be eliminated. The series association of a coil, of inductance,
L n = 1 ( 2 π f n ) 2 · C n  
and a capacitor,
C n = ( 1 1 n 2 ) · Q c n + 3 · 2 π   f 1 · V + 2  
constitutes these passive filters, in which f 1 is the fundamental frequency, n = f n / f 1 , Q c n + is the reactive power that the filter must compensate and V + is the effective value of the positive sequence voltage and fundamental frequency. Equation (10) is the resonance condition of a coil-capacitor series association at the tuning frequency f n , whereas that of Equation (11) follows from the reactive power (at the fundamental frequency) of the three coil-capacitor series associations of a three-phase passive filter.

3.2. Reduction of Core Losses

The second step of the proposed procedure is implemented in two ways:
  • In transformation houses with old, inefficient transformers, the reduction of core losses requires the replacement of these transformers with other efficient ones, of equal or less nominal power (Figure 1);
  • In new transformation houses, in which efficient transformers have already been installed, the only option to reduce core losses is to replace them with other efficient transformers of lower nominal power, whenever possible (Figure 1).
The replacement of transformers by others of lower power can be carried out when the transformer in operation in the transformation house works with very low load rates. Under these conditions, the losses in the core are always much greater than the losses in the copper and, therefore, the energy savings that result from reducing the former can be high.
The previously described actions for core loss reduction are based on the fact of these losses decrease with the rated power of the transformer. However, in the case of equally efficient transformers, the value of the short-circuit resistance ( r c c ) evolves in the opposite direction, that is, it increases as the rated power decreases. For this reason, when a transformer is replaced by another of lower-rated power, the decrease in core losses must be weighed against the increase in copper losses in the new transformer.

4. Application Example

The procedure was applied to improve the energy, economic and environmental sustainability of one of the transformation houses of the low-voltage distribution network of an industrial area, in which there are furniture manufacturing, vehicle repair, industrial spare parts stores, as well as a couple of cafes/restaurants, among other companies. The transformation house has an operating transformer from the manufacturer ORMAZABAL, of 1600 kVA, whose primary is connected to the 20 kV medium voltage electrical network, with nominal features indicated in Table 4.
Connected to the secondary of this transformer, there is a three-phase non-variable capacitor bank, with a power Q c 1 = 3 × 25 kVAR. Likewise, after the first power measurements were made in the secondary of the transformer, the existence of a second three-phase non-variable capacitor bank was detected, with an estimated power Q c 2 = 3 × 100   kVAR. This second reactive compensator was not visible, as it was outside the transformation house, inside the companies.
To carry out the study, a measurement campaign was made between the months of October and December of the year 2020, using the Fluke 435 Series II network analyzer. This instrument has a loss calculator for the distribution lines (Figure 3), which can be adapted to measure the losses in transformers, introducing the value of the short-circuit resistance of the transformer instead of the resistance of the lines, and discounting the values of losses in the neutral conductor.
The economic costs derived from the operation of the transformer and the surcharges for capacitive consumption have been obtained by applying Circular 3/2020, of the National Commission of Markets and Competition of Spain, 15 January.

4.1. Energy Study of the Transformation House

The Fluke 435 Series II analyzer was connected to the transformer secondary terminals and measurements were made on working days and holidays. The values of the transformer copper losses, due to each component of the secondary currents, were measured by the Fluke 435 Series II analyzer, entering in the loss screen of this instrument (Figure 3) a value of resistance equal to the short-circuit resistance of the transformer, indicated in Table 4.
The active ( P ) and reactive ( Q ) powers recorded throughout the measurement campaign on working days and holidays remained (without significant changes) at the values represented in Figure 4 and Figure 5, for working days and holidays, respectively.
Based on the measured values of reactive power ( Q ), represented in Figure 4 and Figure 5, it was deduced that the capacitor banks ( Q c 1 and Q c 2 ) were permanently connected at all hours of working days and holidays, giving rise to the high values of capacitive reactive power (higher than 300 kVAr) during times of low activity of companies. The values of the reactive power absorbed by the installations fed by the transformer, without the effect of the capacitor banks, are those represented by Q in Figure 4 and Figure 5.
The values of the transformer copper losses, due to the active and reactive currents ( P c a and P c r ), are those represented in Figure 6 and Figure 7, for working days and holidays, respectively. Likewise, these figures represent the losses that the reactive currents would cause if the capacitor banks ( P c r ) were not connected. The comparison of the values of P c r and P c r shows the impact produced by the capacitor banks on the copper losses of the transformer, which are especially important in periods of low activity of the companies. It can be noted in Figure 6 and Figure 7 that transformer power losses caused by reactive currents have values between 500 and 700 W each hour in low activity periods, with capacitor banks, whereas these power losses reach only between 50 and 100 W each hour in these periods if capacitor banks were disconnected.
Likewise, the Fluke 435 Series II analyzer recorded the values of copper losses caused in the transformer by unbalanced currents ( P c u ) and distortion currents ( P c h ). These values are those indicated in Figure 8 and Figure 9, for working days and holidays, respectively. It can be seen in these figures that the copper losses caused by the distortions were greater than those caused by the unbalances, undoubtedly due to the amplification of the distortion currents produced by the Ferranti effect in the presence of capacitive loads. However, the importance of losses due to imbalances and distortions is comparatively much less than those caused by capacitive reactive currents.
From the values of the powers and losses in the copper measured in the secondary of the transformer, an inefficient operation of the same is observed, whose cause is, mainly, in the inadequate operation of the non-variable capacitor banks, used for the compensation of the reactive power. These devices are responsible for high values of capacitive reactive power in periods of low activity in companies (Figure 4 and Figure 5). Consequently:
(1)
There are significant copper losses in the transformer, caused by the reactive compensation equipment, which give rise to significant CO2 emissions.
This fact can be seen in the energy losses on holidays in Table 5. The energy losses due to reactive currents on holidays amount to 1772.7 kWh/year. This value has been obtained by multiplying the losses caused by the reactive currents, each day (15.55 kWh, calculated based on the values in Figure 6), by 114 holidays in a one-year period, between September 2020 and August 2021. If the capacitor banks had not been connected, the reactive losses would have been only 113.92 kWh, on holidays (at a rate of only 0.9993 kWh/day). Likewise, CO2 emissions, on holidays, are 427.21 kg each year compared to only 27,454 kg/year that would be produced without the capacitor banks. The CO2 emissions indicated in Table 5 have been determined based on the 0.241 kg CO2/kWh ratio, obtained from Red Eléctrica Española, in 2019 [34].
On the contrary, during the hours of greatest activity on working days, the capacitor banks work properly and achieve significant savings in losses and CO2 emissions (Table 5).
(2)
There are high economic penalties for capacitive reactive consumptions, after the Circular 3/2020 of the National Commission of Markets and Competition of Spain was introduced. (Table 6).
In accordance with what is indicated in Section 2, not all the capacitive reactive energy ( W q ), recorded each day in kVAr-h, is penalized, but only the net value ( Δ W q ) that results from discounting the inductive reactive energy in the penalty periods and indicated in Table 6, for working days and holidays. Penalties for the capacitive reactive energy (RCAP) have been calculated based on Equations (3) and (4), for a period of one year, between September 2020 and August 2021. This period includes 251 business days and 114 holidays.
(3)
Copper losses and CO2 emissions caused by unbalanced and distortion currents in the transformer windings are much lower than those due to reactive currents.
These energy losses have been obtained by adding the values of copper losses indicated in Figure 8 and Figure 9, for each hour of the working days and holidays, and multiplying the resulting values by 251 working days and 114 holidays (Table 7). The carbon dioxide emissions, indicated in Table 7, have been calculated by multiplying the energy losses by 0.241 kg CO2/kWh [34].

4.2. Energy and Environmental Effects Resulting from Improving the Sustainability of the Transformation House

The elimination of penalties for capacitive reactive energy, as well as a reduction in carbon dioxide emissions in the transformation center, can be carried out based on three actions, included in the procedure described in Section 3:
(4)
Optimization of the operation of the capacitor banks;
(5)
Reduction of copper losses caused by imbalances and distortions;
(6)
Replacing the transformer with a more efficient one, with less power.
The first of these actions is the one that can bring economic benefits, while the third provides, above all, energy and environmental benefits.

4.2.1. Optimization of the Operation of the Capacitor Banks

We have already indicated above that there are two banks of three-phase capacitors, fixed, connected to the secondary of the transformation center transformer. The first, Q c 1 = 3 × 25 kVAR is located in the transformation center itself. The existence of the second bank of capacitors, Q c 2 = 3 × 100 kVAR, was deduced after analyzing the registered powers.
The operation of the capacitor banks Q c 1 and Q c 2 is only efficient in the periods of greatest activity of the companies, in which the reactive power supplies are considerably reduced (Figure 2) and the power factor of the transformer is close to 1 (Figure 10). However, in periods of low activity, whether on working days or holidays, the capacitor banks supply large amounts of reactive power to the mains (Figure 4 and Figure 5), with factors of capacitive power being very small, less than 0.3 capacitive (Figure 10).
The environmental and economic consequences of reactive power in the inefficient operation of the transformer are observed in Table 5 and Table 6, respectively. To reduce their impact, it is necessary to optimize the operation of the capacitor banks. For this, it is proposed:
  • Maintain the operation of the first capacitor bank ( Q c 1 ), without disconnection, at any time of the day, every day of the year, both working days and holidays;
  • Connect the second capacitor bank ( Q c 2 ) only between 7:00 a.m. and 8:00 p.m. on working days, keeping it disconnected for the rest of the hours on working days and all hours on holidays. This solution can be applied, in a very economical way, by incorporating a switch with a programmable timer in this capacitor bank.
The energy effects of the limitation of the period of operation of the capacitor bank Q c 2 are:
(1)
A significant decrease in the reactive power supplied, with very short capacitive periods, which are compensated by the inductive periods on working days and holidays (Figure 11), reaching power factors very close to unity (Table 8);
(2)
The high reduction of transformer copper losses caused by reactive currents, especially on holidays (Figure 12), which, compared to those indicated in Table 5, represent energy savings of 2820 kWh/year and 679.58 kg/year, in CO2 emissions (Table 9).

4.2.2. Reduction of Transformer Copper Losses Caused by Imbalance and Distortion Currents

The losses caused by current imbalances in the transformer are not affected by the operation of the capacitor banks, since these are balanced loads. Likewise, the values of these losses are very small, both working days and holidays (Figure 8 and Figure 9). This is an indication that the loads are slightly unbalanced and, therefore, it will not be necessary to apply any specific action to reduce these losses, whose values will remain at those indicated in Table 7.
Regarding the phenomenon of distortion, the optimization of the operation of the capacitor banks has an additional beneficial effect, reducing the distortion currents and copper losses.
Indeed, the distortion of the currents is fundamentally caused by the amplifying effect caused by the capacitive loads. This fact is observed in Figure 13. During periods of low activity of the companies, in which there are high supplies of capacitive reactive power, the currents are highly distorted (Figure 13a), with THD% of 14.58%, while in the times of high activity of the companies, the currents are slightly distorted (Figure 13b), with THD% lower than 3.74%. Under these latter conditions, distortion copper losses have an average value of 5.5 W (Figure 8). In our opinion, this is the maximum value of the losses caused by the distortion of the loads, without the amplifying effect of the capacitors, in periods of low activity for the companies.
Consequently, the disconnection of the capacitor bank Q c 2 , in the periods of low activity of the companies, gives rise to an additional reduction of the distortion currents and the losses caused by them. Considering that the value of losses due to distortion, without the effect of the capacitors, is the previously indicated 5.5 W every hour, it results in a 50% decrease in energy losses due to distortion currents, indicated in Table 7, for working days, and 75% for holidays. These reductions also extend, with the same percentage, to carbon dioxide emissions (Table 10). These important benefits make the additional installation of harmonic filters unnecessary, in our opinion.

4.2.3. Replacing the Actual Transformer with a More Efficient One, with Less Power

The nominal values of the copper and core losses of efficient distribution transformers are indicated in Table 11. It is observed that the core losses of the transformers are smaller in the transformers of lower nominal power. This fact could justify the replacement of transformers with others of lower-rated power. However, it can also be seen in Table 11 that the short-circuit resistance ( r c c ) evolves in the opposite direction, so the load losses will increase if lower-power transformers are used, since the currents maintain their value. For this reason, in the event of replacing the actual transformer with another of lower power, the most suitable replacement transformer must be the one whose total losses, obtained as the sum of the copper losses and the core losses, have the lowest value.
The comparison of the energy loss values in the copper of the 1600 kVA Ormazabal transformer ( W c ( 1 ) ), indicated in Table 12, and is measured by the Fluke 435 Series II instrument according to the equation:
W c ( 1 ) = W c a + W c r + W c u + W c h  
denotes the impact of optimizing the operation of capacitor banks. The copper energy lost in the 1600 kVA Ormazabal transformer, with the optimized operation of the capacitors ( W c ( 2 ) ), is obtained as the sum of the losses due to the active currents ( W c a ), to the reactive currents ( W c r , Table 9), to the unbalanced currents ( W c u , Table 7) and the distortion currents ( W c h , Table 10), determined after the optimization of the operation of the capacitors, i.e.:
W c ( 2 ) = W c a + W c r + W c u + W c h  
The copper losses for efficient transformers ( W c ( 3 ) ) have been calculated based on the following expression:
W c ( 3 ) = W c ( 2 )   r c c r c c
where r c c is the short-circuit resistance of the 1600 kVA Ormazabal transformer (Table 4) and r c c is the short-circuit resistance of the analyzed efficient transformers (Table 11).
The total losses of each transformer have been obtained by adding their copper losses ( W c ( 1 ) ,   W c ( 2 ) or W c ( 3 ) ) to the core losses of each transformer (Table 4 and Table 11).
The values of carbon dioxide emissions (Table 13) have been determined by multiplying the total energy lost for each transformation and operation of the capacitor banks, indicated in Table 12, by the emissions factor for the year 2019, in Spain, 0.241 kg CO2/kWh.
Observing the total energy losses, indicated in Table 12, and the carbon dioxide emissions, in Table 13, it follows that the most suitable replacement transformer for the actual 1600 kVA must be an efficient transformer with a nominal power of 1000 kVA, since it is the one with the lowest total losses (Table 12) and carbon dioxide emissions (Table 13). Compared with the 1600 kVA inefficient transformer, annual energy savings of 19,037.95 kWh and annual savings in carbon dioxide emissions of 4588.14 kg are obtained.

4.3. Economic Effects of Improving the Sustainability of the Transformation House

The economic costs derived from the operation of each transformer are obtained by multiplying the value of its total energy losses (in the copper and in the core), for each hourly period (P1, P2, P3, P4, P5 and P6) and type of day (A, B, B1, C and D), according to Table 3, by the energy prices in each hourly period (Table 1). The effects of the increase in electricity prices from January 2020 to January 2022 have been considered in the study.
The economic costs corresponding to the total losses of the inefficient transformer of 1600 kVA, without optimizing the operation of the capacitor bank Q c 2 , are indicated in the fourth column of Table 14. Likewise, the economic costs due to the total energy losses of the inefficient transformer of 1600 kVA and of the efficient replacement transformer of 1000 kVA, when the operation of the capacitor bank Q c 2 has been optimized, are indicated in the sixth and eighth columns, respectively, of Table 14.
The third, fifth and seventh columns of Table 14 indicate the energy lost daily, in kWh, for each transformer at peak hours (P1-A, P2-B, P3-B1, P4-C), at low hours (P2-A, P3-B, P4-B1, P5-C), off-peak hours on working days (P6(4)) and 24 h a day on holidays (P6(5)), with the times indicated in Table 3 for each type of day of the year (A, B, B1, C and D). The daily values of the energy losses in the transformer have been obtained by adding the consumption at peak hours (9–14 h and 18–22 h), flat (8–9 h, 14–18 h and 22–24 h) and valley (0–8 h, on working days and 24 h on holidays). These hours are the same throughout the year, but the price of energy in each of these hours has a different value, depending on the type of day of the year (Table 1).
The results indicated in Table 14 show that improving the sustainability of the transformation house, optimizing the operation of the capacitor bank Q c 2 and replacing the inefficient 1600 kVA transformer with an efficient 1000 kVA transformer, allows savings of 158.76 EUR/year, at 2020 energy prices. However, at energy prices of the beginning of the year 2022, these savings amount to the sum of 1536.75 EUR/year. The savings that would have been obtained without the replacement of the inefficient transformer, of 1600 kVA, reducing only its copper losses, would only be 13.53 EUR/year, at 2020 prices, and 206 EUR/year, at prices of principles of the year 2022. To the previous savings, in economic costs of the losses in the transformer, it would be necessary to add the savings in penalties for capacitive reactive energy, which amount to 44,158.83 EUR/year (Table 6), after the optimization of the operation of the bank of capacitors Q c 2 .

4.4. Summary of Benefits derived from the Improvement of the Sustainability of the Transformation House

The application of the procedure for improving the sustainability of the transformation center used in the application example has allowed the energy, environmental and economic savings indicated in Table 15 to be achieved.
Reducing only the copper losses, without replacing the transformer with a more efficient one, by optimizing the operation of the capacitor bank Q c 2 , the benefits obtained are as follows (Table 15):
  • Losses caused by reactive and distortion currents have been considerably reduced, achieving energy loss savings in the transformer of 2896.37 kWh/year and savings in carbon dioxide emissions of 698 kg/year;
  • Savings in economic costs derived directly from this energy consumption are very modest and amount to only 206 EUR/year, but the savings in penalties for capacitive reactive energy are very high, at 44,158.83 EUR/year;
In addition, if an efficient 1000 kVA transformer replaces the inefficient 1600 kVA transformer, the benefits derived from the full application of the procedure to improve the sustainability of the transformation house are as follows (Table 15):
  • Savings in energy losses of 19,037.95 kWh/year (64.4%) and savings in carbon dioxide emissions of 4588.14 kg/year (64.4%);
  • Decrease indirect costs of energy losses by 1536.75 EUR/year (58.11%) and savings from penalties for capacitive consumption by 44,158.83 EUR/year (100%).

5. Conclusions

In this paper, the economic, energy and environmental effects resulting from applying the proposed procedure to improve the sustainability of the transformation houses of the low-voltage distribution networks have been analyzed.
Reducing reactive currents, either through the use of suitable compensation devices or by optimizing the operation of existing ones, is usually a technique that achieves a greater reduction of copper losses in distribution transformers, greater than imbalance compensation and harmonic filtering.
However, the energy savings and reduced CO2 emissions resulting from minimizing copper losses in older inefficient transformers are very small compared to the savings that can be achieved by reducing core losses, after replacing those transformers with other efficient ones. The combined utilization of current reduction techniques (copper losses) and the use of efficient transformers (core losses) in transformation houses allow for savings of between 55% and 70% in energy consumption and CO2 emissions in transformation houses with old transformers. However, only between 10% and 20% of these savings are due to the application of copper loss reduction techniques.
The decrease in economic costs, resulting from the application of the proposed procedure to improve the sustainability of transformation houses, is more modest than its energy and environmental effects, especially if only actions are applied to reduce copper losses, such as can be seen in Table 15. However, the current energy shortage means that these cost savings can reach interesting amounts. The savings in penalties for capacitive consumptions are insignificant if the reactive compensators have been well chosen. Otherwise, optimizing the operation of the reactive compensation devices allows significant savings to be achieved through penalties, as seen in the application example (Table 15).
The results in reducing CO2 emissions and economic savings obtained in this paper can be extended to each country, simply by using the CO2 emission factor and the energy prices of the corresponding country.
The procedure described in this paper is being applied to the monitoring of the transformation houses of the distribution network of a small city in collaboration with the electricity company Eléctrica de Vinalesa S.L.U. It is expected that the development of this project will lead to new lines of research that we will describe in future papers.

Author Contributions

Conceptualization, V.L.-M.; methodology, V.L.-M. and E.P.-L.; validation, E.P.-L., C.A-.M. and L.M.-C.; formal analysis, V.L.-M., J.C.-M. and A.L.-V.; investigation, A.L.-V. and J.C.-M.; resources, L.M.-C. and C.A.-M.; writing—original draft preparation, E.P.-L. and A.L.-V.; writing—review and editing, C.A.-M., L.M.-C. and J.C.-M.; supervision, V.L.-M.; funding acquisition, E.P.-L. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Generalitat Valenciana (grant number GV/2021/149) and the H2020 project SMEmPower (grant number 847132). The APC was funded by Generalitat Valenciana.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

Nomenclature

Acronyms
FEBilled Energy
TDATransmission & Distribution Access
PFPower Factor
RCAPReactive CAPacitive, penalty for capacitive reactive power consumptions
THD%Total Harmonic Distortion, in percent
Greek symbols
α p angle of the S u i p component of the vector unbalanced power that measures active power imbalances
α q angle of the S u i q component of the vector unbalanced power that measures reactive power imbalances
Superscripts
Superscript (1)actual operation of capacitor banks in the transformation house
Superscript (2)optimized operation of capacitor banks
Superscript (3)optimized operation of capacitor banks and changing actual transformers by efficient ones
Superscript (4)number of working days in the annual period analyzed
Superscript (5)number of holidays in the annual period analyzed
Superscript (6)costs, in euros, calculated according to 2020 energy prices
Superscript (7)costs, in euros, calculated according to 2022 energy prices

References

  1. Godina, R.; Rodrigues, E.M.G.; Matias, J.C.O.; Catalão, J.P.S. Effect of Loads and Other Key Factors on Oil-Transformer Ageing: Sustainability Benefits and Challenges. Energies 2015, 8, 12147–12186. [Google Scholar] [CrossRef] [Green Version]
  2. Yahaya, M.S.; Azis, N.; Selva, A.M.; Ab Kadir, M.Z.A.; Jasni, J.; Hairi, M.H.; Ghazali, Y.Z.Y.; Talib, M.A. Effect of Pre-Determined Maintenance Repair Rates on the Health Index State Distribution and Performance Condition Curve Based on the Markov Prediction Model for Sustainable Transformers Asset Management Strategies. Sustainability 2018, 10, 3399. [Google Scholar] [CrossRef] [Green Version]
  3. Sun, C.; Mi, Z.; Ren, H.; Jing, Z.; Lu, J.; Watts, D. Multi-Dimensional Indexes for the Sustainability Evaluation of an Active Distribution Network. Energies 2019, 12, 369. [Google Scholar] [CrossRef] [Green Version]
  4. Hunziker, C.; Lemann, J.; Keller, T.; Heim, T.; Schulz, N. Sustainability assessment of novel transformer technologies in distribution grid applications. Sustain. Energy Grids Netw. 2020, 21, 100314. [Google Scholar] [CrossRef]
  5. Olivares, J.; Liu, Y.; Cañedo, J.; Escarela-Perez, R.; Driesen, J.; Moreno, P. Reducing Losses in Distribution Transformers. IEEE Trans Power Deliv. 2003, 18, 821–825. [Google Scholar] [CrossRef]
  6. Olivares-Galvan, J.C.; Georgilakis, P.S.; Ocon-Valdez, P. A review of transformer losses. Electr. Power Compon. Syst. 2009, 37, 1046–1062. [Google Scholar] [CrossRef]
  7. Al-Badi, A.H.; Elmoudi, A.; Metwally, I.; Al-Wahaibi, A.; Al-Ajmi, H.; Al-Bulushi, M. Losses Reduction in Distribution Transformers. In Proceedings of the International Multi-Conference of Engineers and Scientists 2011, Vol II, IMCES 2011, Hong Kong, China, 16–18 March 2011. [Google Scholar]
  8. Firmin, J.; Vagapov, Y. Analysis of Reducing Electrical Losses in Parallel Transmission/Distribution Transformers. In Proceedings of the IEEE Conference of Russian Young Researchers in Electrical and Electronic Engineering, St. Petersburg, Russia, 26–29 January 2021. [Google Scholar] [CrossRef]
  9. Tapan Kumar, S.; Prithwiraj, P. Smart Transformer Condition Monitoring and Diagnosis. In Transformer Ageing: Monitoring and Estimation Techniques; Wiley-IEEE Press: Piscataway, NJ, USA, 2017; ISBN 9781119239963. [Google Scholar]
  10. Lezhniuk, P.D.; Rubanenko, O.E.; Rubanenko, O.O. Determination of Optimal Transformation Ratios of Power System Transformers in Conditions of Incomplete Information Regarding the Values of Diagnostic Parameters. Fuzzy Logic Chapter. 2019. [Google Scholar] [CrossRef] [Green Version]
  11. Bouroussis, C.A.; Vokas, G.A.; Topalis, F.V. Policies and Measures Fostering Energy-Efficient Distribution Transformers. Report from the EUIEE Project “Strategies for Development and Diffusion of Energy-Efficient Distribution Transformers—SEEDT”, Project No. EIE/05/056/SI2.419632. Wuppertal Institute for Climate, Environment, Energy and SEEDT Partners. 2008. Available online: https://www.ceer.eu/documents/104400/-/-/7aed48f1-ccdb-e8d4-1932-98cdf421936c (accessed on 15 March 2022).
  12. European Cooper Institute. Coppers Contribution to a Low Carbon Future. A Plan to Decarbonize Europe by 25 Percent. 2018. Available online: https://copperalliance.sk/uploads/2018/05/coppers-contribution-to-a-low-carbon-future-a-plan-to-decarbonise-europe-by-25-percent.pdf (accessed on 1 March 2022).
  13. U4E. Accelerating the Global Adoption of Energy-Efficient Transformers; UN Environment, Economy Division, Energy & Climate Branch: Paris, France, 2017. [Google Scholar]
  14. Energy Efficient Distribution Transformers. 2017. Available online: https://leonardo-energy.pl/wp-content/uploads/2017/08/Energy-efficient-distribution-transformers.pdf (accessed on 15 March 2022).
  15. Siemens, A.G. Transformers—Power Engineering Guide, 7th ed.; Siemens Energy Sector: Erlangen, Germany, 2014. [Google Scholar]
  16. Garcia, D.; Valencia, J.; Hausman, G.U.S. Department of Energy’s 2016 Transformer Efficiency Changes and Impact on Inrush Current for Low Voltage Dry-Type Transformers. EATON. 2016. Available online: www.eaton.com (accessed on 15 March 2022).
  17. Energy Efficient Distribution Transformers. HPS—Hammond Power Solutions Inc. Available online: www.hammondpowersolutions.com (accessed on 15 March 2022).
  18. Energy Efficient Transformers: European Minimum Energy Performance Regulation (MEPS). Available online: www.abb.com/transformers (accessed on 15 March 2022).
  19. Directive 2009/125/EC of the European Parliament and of the Council of 21 October 2009 Establishing a Framework for the Setting of Eco-Design Requirements for Energy-Related Products. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=celex%3A32009L0125 (accessed on 15 March 2022).
  20. Commission Regulation (EU) No 548/2014 of 21 May 2014 on Implementing Directive 2009/125/EC of the European Parliament and of the Council with Regard to Small, Medium and Large Power Transformers. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/PDF/?uri=CELEX:32014R0548&from=EN (accessed on 15 March 2022).
  21. Commission Regulation (EU) 2019/1783 of 1 October 2019 amending Regulation (EU) No 548/2014 on Implementing Directive 2009/125/EC of the European Parliament and of the Council with Regard to Small, Medium and Large Power Transformers. Available online: https://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX%3A32019R1783 (accessed on 15 March 2022).
  22. ANSI. ANSI C57.12.20-1997; American National Standard for Transformers—Standard for Overhead Type Distribution Transformers, 500 kVA and Smaller: High Voltage 34500 Volts and Below: Low Voltage, 7970/13800Y Volts and Below. ANSI: New York, NY, USA, 2002; pp. 1–51.
  23. IEC 60076-7; Loading Guide for Oil-immersed Power Transformers. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2007.
  24. A2.27 W.G.; Recommendations for Condition Monitoring and Condition Assessment Facilities for Transformer. CIGRE: Paris, France, 2008.
  25. IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators. In IEEE Std C57.91-2011 (Revision of IEEE Std C57.91-1995); IEEE: New York, NY, USA, 2012; pp. 1–123.
  26. CFR Title 10 Chapter II Part 431, Energy Efficiency Program for Certain Commercial and Industrial Equipment, Appendix A of Subpart K-Distribution Transformers. US Regulations. 2016. Available online: https://www.ecfr.gov/current/title-10/chapter-II/subchapter-D/part-431/subpart-K?toc=1 (accessed on 15 March 2022).
  27. NEMA Premium® Efficiency Transformer Program. Available online: http://www.nema.org/Technical/Pages/NEMA-Premium-Efficiency-Transformers-Program.aspx (accessed on 15 March 2022).
  28. IEC TS 60076-20:2017; Power Transformers—Part 20: Energy efficiency. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2017. Available online: https://cdn.standards.iteh.ai/samples/18643/38c24f902a05425aa8607a40a339c92c/IEC-TS-60076-20-2017.pdf (accessed on 15 March 2022).
  29. Baggini, A. Overview of IEC/TS 60076-20 Ed. 1.0: Power Transformers—Part 20: Energy Efficiency. In Proceedings of the Workshop on Reducing Losses in Power Distribution through Improved Efficiency of Distribution Transformers, Jeju, Korea, 28 March 2017. [Google Scholar]
  30. Almeida, A.; Santos, B.F.; Martins, F.M.L. Energy-efficient distribution transformers in Europe: Impact of Ecodesign regulation. Energy Effic. 2015, 9, 401–424. [Google Scholar] [CrossRef]
  31. Tran, Q.T.; Davies, K.; Roose, L.; Wiriyakitikun, P.; Janjampop, J.; Riva Sanseverino, E.; Zizzo, G. A Review of Health Assessment Techniques for Distribution Transformers in Smart Distribution Grids. Appl. Sci. 2020, 10, 8115. [Google Scholar] [CrossRef]
  32. León-Martínez, V.; Andrada-Monrós, C.; Molina-Cañamero, L.; Cano-Martínez, J.; Peñalvo-López, E. Decarbonization of Distribution Transformers based on Current Reduction: Economic and Environmental Impacts. Energies 2021, 14, 7207. [Google Scholar] [CrossRef]
  33. León-Martínez, V.; Montañana-Romeu, J. Formulations for the Apparent and Unbalanced Power Vectors in Three-Phase Sinusoidal Systems. Electr. Power Syst. Res. 2018, 160, 37–43. [Google Scholar] [CrossRef] [Green Version]
  34. Sustainability Report 2020. Red Eléctrica, Spanish Operator. 2021. Available online: https://www.ree.es/es/publicaciones/informe-sostenibilidad-2020 (accessed on 15 March 2022).
  35. Circular 3/2020, of 15 January of the National Markets and Competition Commission, which Establishes the Methodology for Calculating Electricity Transmission and Distribution Tolls. Spanish Official State Bulletin (BOE), N° 21, 24 January 2020; pp. 6953–6980. Available online: https://www.boe.es (accessed on 15 March 2022).
  36. New Penalties for Capacitive Reactive Energy. 2020. Available online: www.casel.es (accessed on 15 March 2022).
  37. IEC Standard 60076-1:2011; Power Transformers—Part 1: General. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2011.
  38. Jeon, S.-J.; Willems, J.L. Reactive power compensation in a multi-line system under sinusoidal unbalanced conditions. Int. J. Circuit Theory Appl. 2010, 39, 211–224. [Google Scholar] [CrossRef]
  39. Graña-López, M.A.; García-Diez, A.; Filgueira-Vizoso, A.; Chouza-Gestoso, J.D.; Masdías-Bonome, A. Study of the Sustainability of Electrical Power Systems: Analysis of the Causes that Generate Reactive Power. Sustainability 2019, 11, 7202. [Google Scholar] [CrossRef] [Green Version]
  40. Blasco, P.A.; Montoya-Mira, R.; Díez, J.M.; Montoya, R.; Reig, M.J. Compensation of Reactive Power and Unbalanced Power in Three-Phase Three-Wire Systems Connected to an Infinite Power Network. Appl. Sci. 2020, 10, 113. [Google Scholar] [CrossRef] [Green Version]
  41. Montoya-Mira, R.; Blasco, P.A.; Díez, J.M.; Montoya, R.; Reig, M.J. Unbalanced and Reactive Currents Compensation in Three-Phase Four Wire Sinusoidal Power Systems. Appl. Sci 2020, 10, 1764. [Google Scholar] [CrossRef] [Green Version]
  42. Coman, C.M.; Florescu, A.; Oancea, C.D. Improving the Efficiency and Sustainability of Power Systems Using Distributed Power Factor Correction Methods. Sustainability 2020, 12, 3134. [Google Scholar] [CrossRef] [Green Version]
Figure 1. Organization chart of the procedure for improving the sustainability of transformation houses.
Figure 1. Organization chart of the procedure for improving the sustainability of transformation houses.
Applsci 12 04204 g001
Figure 2. Imbalances throughout a day in the distribution transformer of an industrial area, due to (a) active loads ( α p ), and (b) reactive loads ( α q ).
Figure 2. Imbalances throughout a day in the distribution transformer of an industrial area, due to (a) active loads ( α p ), and (b) reactive loads ( α q ).
Applsci 12 04204 g002
Figure 3. Loss calculator screen from the analyzer Fluke 435 Series II.
Figure 3. Loss calculator screen from the analyzer Fluke 435 Series II.
Applsci 12 04204 g003
Figure 4. Active ( P ) and reactive ( Q ) powers delivered by the transformer on working days, as well as the reactive powers ( Q ) supplied without capacitor banks. (Negative sign indicates capacitive reactive powers).
Figure 4. Active ( P ) and reactive ( Q ) powers delivered by the transformer on working days, as well as the reactive powers ( Q ) supplied without capacitor banks. (Negative sign indicates capacitive reactive powers).
Applsci 12 04204 g004
Figure 5. Active ( P ) and reactive ( Q ) powers delivered by the transformer during holidays, as well as the reactive powers ( Q ) supplied without capacitor banks. (Negative sign indicates capacitive reactive powers).
Figure 5. Active ( P ) and reactive ( Q ) powers delivered by the transformer during holidays, as well as the reactive powers ( Q ) supplied without capacitor banks. (Negative sign indicates capacitive reactive powers).
Applsci 12 04204 g005
Figure 6. Transformer power losses in working days due to (a) active currents ( P c a ); (b) reactive currents with capacitors ( P c r ); and (c) reactive currents without capacitors ( P c r ).
Figure 6. Transformer power losses in working days due to (a) active currents ( P c a ); (b) reactive currents with capacitors ( P c r ); and (c) reactive currents without capacitors ( P c r ).
Applsci 12 04204 g006
Figure 7. Transformer power losses in holidays due to (a) active currents ( P c a ); (b) reactive currents with capacitors ( P c r ) and (c) reactive currents without capacitors ( P c r ).
Figure 7. Transformer power losses in holidays due to (a) active currents ( P c a ); (b) reactive currents with capacitors ( P c r ) and (c) reactive currents without capacitors ( P c r ).
Applsci 12 04204 g007
Figure 8. Transformer power losses, in working days, caused by (a) unbalanced currents ( P c u ) and (b) distorted currents ( P c h ).
Figure 8. Transformer power losses, in working days, caused by (a) unbalanced currents ( P c u ) and (b) distorted currents ( P c h ).
Applsci 12 04204 g008
Figure 9. Transformer power losses, during holidays, caused by (a) unbalanced currents ( P c u ) and (b) distorted currents ( P c h ).
Figure 9. Transformer power losses, during holidays, caused by (a) unbalanced currents ( P c u ) and (b) distorted currents ( P c h ).
Applsci 12 04204 g009
Figure 10. Transformer power factor on (a) working days and (b) holidays. (Positive values indicate inductive PF, whereas negative values signify capacitive PF).
Figure 10. Transformer power factor on (a) working days and (b) holidays. (Positive values indicate inductive PF, whereas negative values signify capacitive PF).
Applsci 12 04204 g010
Figure 11. Transformer reactive powers, in kVAR, after applying actions for optimizing the operation of capacitor bank Q c 2 : (a) working days, and (b) holidays.
Figure 11. Transformer reactive powers, in kVAR, after applying actions for optimizing the operation of capacitor bank Q c 2 : (a) working days, and (b) holidays.
Applsci 12 04204 g011
Figure 12. Transformer power losses due to reactive currents ( P c r ) after applying actions for optimizing the operation of the capacitor bank Q c 2 : (a) working days, and (b) holidays.
Figure 12. Transformer power losses due to reactive currents ( P c r ) after applying actions for optimizing the operation of the capacitor bank Q c 2 : (a) working days, and (b) holidays.
Applsci 12 04204 g012
Figure 13. A-phase voltage and current waveforms registered in the secondary of the transformer in periods of (a) small power consumptions and (b) high power consumptions.
Figure 13. A-phase voltage and current waveforms registered in the secondary of the transformer in periods of (a) small power consumptions and (b) high power consumptions.
Applsci 12 04204 g013
Table 1. Energy prices in Spain ( T e p ), in EUR/kWh, for each hourly period of the 6.1 TDA toll.
Table 1. Energy prices in Spain ( T e p ), in EUR/kWh, for each hourly period of the 6.1 TDA toll.
YearHourly Periods
P1P2P3P4P5P6
20200.0329500.0244070.0131800.0065900.0042240.002636
20220.1338620.1156440.0970660.086470.0726770.065821
Increment (%)406.26473.81736.461312.141720.572497.00
Table 2. Voltage and power limits corresponding to each transmission and distribution toll.
Table 2. Voltage and power limits corresponding to each transmission and distribution toll.
Transmission and Distribution Toll
2.0 TDA3.0 TDA6.1 TDA6.2 TDA6.3 TDA6.4 TDA
Voltage (kV) V 1 V 1 1 < V < 30 30 V < 72.5 72.5 V < 145 V 145
Power (kW) 15 > 15
Table 3. Hourly billing periods according to the type of day.
Table 3. Hourly billing periods according to the type of day.
Hourly PeriodType of DAY
ABB1CD
P19 h–14 h
18–22 h
P28–9 h
14–18 h
22–0 h
9–14 h
18–22 h
P3 8–9 h
14–18 h
22–0 h
9–14 h
18–22
h
P4 8–9 h
14–18 h
22–0 h
9–14 h
18–22 h
P5 8–9 h
14–18 h
22–0 h
P60–8 h0–8 h0–8 h0–8 hAll day hours
Table 4. Nominal features of Ormazabal distribution transformers.
Table 4. Nominal features of Ormazabal distribution transformers.
Rated Power (kVA)Copper Losses (W)Core losses
(W)
Short-Circuit
Resistance (Ω)
160017,00026000.011708
Table 5. Annual energy losses ( W c r ) and CO2 emissions caused by reactive currents in the operation of the transformation house.
Table 5. Annual energy losses ( W c r ) and CO2 emissions caused by reactive currents in the operation of the transformation house.
Operation with Actual Capacitor BanksOperation with No Capacitor Banks
Energy Losses (kWh/year)CO2 Emissions
(kg/year)
Energy Losses (kWh/year)CO2 Emissions (kg/year)
Working days (251)1322.77318.743737.39900.63
Holidays (114)1772.70427.21113.9227.45
Table 6. Measured and penalized capacitive energies each day and annual penalizations.
Table 6. Measured and penalized capacitive energies each day and annual penalizations.
Type of DayPenalization for Capacitive Energy
Penalization PeriodMeasured
Capacitive
Energy, W q (kvar-h/day)
Penalized
Capacitive
Energy, Δ W q (kvar-h/day)
Annual
Penalization (RCAP) (Euros)
Working days (251)0–8 h1511.17324.534072.93
Holidays (114)24 h7249.437032.6140,085.90
Table 7. Annual energy losses and CO2 emissions caused by unbalanced ( W c u ) and distorted ( W c h ) currents in the transformer of the transformation house.
Table 7. Annual energy losses and CO2 emissions caused by unbalanced ( W c u ) and distorted ( W c h ) currents in the transformer of the transformation house.
Type of DayImbalanceDistortion
Energy Losses (kWh/year)CO2 Emissions
(kg/year)
Energy Losses (kWh/year)CO2 Emissions
(kg/year)
Working days20.194.86669.3716.72
Holidays1.970.47555.5213.38
Table 8. Power factor and reactive energies each day and annual penalizations resulting from applying the above actions on the second capacitor bank ( Q c 2 ).
Table 8. Power factor and reactive energies each day and annual penalizations resulting from applying the above actions on the second capacitor bank ( Q c 2 ).
Type of DayPower FactorTotal Reactive Consumptions Per Day, W q
(kvar-h)
Penalized
Capacitive
Energy W q
(kvar-h/day)
Annual
Penalization (RCAP) (Euros)
Working days0.99773 (ind)394.5100
Holidays0.99998 (cap)6.799800
Table 9. Annual energy losses ( W c r ) and CO2 emissions caused by reactive currents and savings after optimizing the operation of the capacitor bank Q c 2 .
Table 9. Annual energy losses ( W c r ) and CO2 emissions caused by reactive currents and savings after optimizing the operation of the capacitor bank Q c 2 .
Losses and EmissionsSavings
Energy Losses (kWh/Year)CO2 Emissions
(kg/Year)
Energy Losses (kWh/Year)CO2 Emissions (kg/Year)
Working days (251 days/year)272.7465.731050.03253.01
Holidays
(114 days/year)
2.650.641770.05426.57
Table 10. Annual energy losses ( W c h ) and CO2 emissions caused by distorted currents and savings after the optimization in the operation of the capacitor bank Q c 2 .
Table 10. Annual energy losses ( W c h ) and CO2 emissions caused by distorted currents and savings after the optimization in the operation of the capacitor bank Q c 2 .
Type of DayLosses and EmissionsSavings
Energy Losses (kWh/year)CO2 Emissions
(kg/year)
Energy Losses (kWh/year)CO2 Emissions (kg/year)
Working days (251)34.6858.3634.6858.36
Holidays (114)13.933.34541.5910.035
Table 11. Nominal features of 24 kV efficient distribution transformers according to Commission Regulation (EU) No 548/2014.
Table 11. Nominal features of 24 kV efficient distribution transformers according to Commission Regulation (EU) No 548/2014.
Power (kVA)Copper Losses (W)Core Losses (W)Short-Circuit
Resistance (Ω)
160012,00010800.000826447
100076006930.00134064
80060005850.001653704
63046004500.00204438
Table 12. Annual copper losses ( W c ( 1 ) , W c ( 2 ) and W c ( 3 ) ) and total losses (copper + core losses): (1) current operation of capacitors; (2) by optimizing the operation of capacitors; and (3) using efficient transformers and optimizing the operation of capacitor banks.
Table 12. Annual copper losses ( W c ( 1 ) , W c ( 2 ) and W c ( 3 ) ) and total losses (copper + core losses): (1) current operation of capacitors; (2) by optimizing the operation of capacitors; and (3) using efficient transformers and optimizing the operation of capacitor banks.
TransformerTotal Copper Losses (kwh/year)Total Losses (kwh/year)
Working Days (251)Holidays
(114)
Working Days (251)Holidays
(114)
Total
(365)
Ormazabal
1600 kVA (1)
4909.541872.9820,571.948986.5729,558.52
Ormazabal
1600 kVA (2)
3824.8461.3119,487.247174.9126,662.15
Efficient
1600 kVA (3)
2699.8943.289205.812998.1612,203.96
Efficient
1000 kVA (3)
4379.6870.208554.321966.2510,520.57
Efficient
800 kVA (3)
5402.4286.598926.461687.1610,613.62
Efficient
630 kVA (3)
6678.71107.059389.511338.2510,727.76
Table 13. Annual carbon dioxide emissions, in kg/year: (1) current operation; (2) optimizing operation of capacitors; and (3) using efficient transformers and optimizing the operation of capacitor banks.
Table 13. Annual carbon dioxide emissions, in kg/year: (1) current operation; (2) optimizing operation of capacitors; and (3) using efficient transformers and optimizing the operation of capacitor banks.
TransformerWorking Days (251)Holidays (114)Total (365)
Ormazabal 1600 kVA (1)4957.842165.767123.60
Ormazabal 1600 kVA (2)4696.421729.156425.57
Efficient
1600 kVA (3)
2218.60722.562941.16
Efficient
1000 kVA (3)
2061.59473.872535.46
Efficient
800 kVA (3)
2151.27406.602557.87
Efficient
630 kVA (3)
2262.87322.522585.39
Table 14. Daily energies and annual costs for three analyzed transformers: 1600 kVA (1) with no improvements, 1600 kVA (2) with capacitor bank improvements and 1000 kVA (3) efficient transformer, on working days (4) and holidays (5), corresponding to 2020 (6) and 2022 (7) energy prices.
Table 14. Daily energies and annual costs for three analyzed transformers: 1600 kVA (1) with no improvements, 1600 kVA (2) with capacitor bank improvements and 1000 kVA (3) efficient transformer, on working days (4) and holidays (5), corresponding to 2020 (6) and 2022 (7) energy prices.
Type of Day
(nº Days)
Period1600 kVA (1)1600 kVA (2)1000 kVA (3)
Energy
kWh/Day
Costs
(€/Year)
Energy
kWh/Day
Costs
(€/Year)
Energy
kWh/Day
Costs
(€/Year)
A (81)P130.5063129.96 (6)
560,79 (7)
29.6519126.00 (6)
543.53 (7)
13.395857.80 (6)
249.7 (7)
P224.555523.702111.1513
B (43)P230.506345.93 (6)
254.19 (7)
29.651944.55 (6)
246.38 (7)
13.395820.38 (6)
113.16 (7)
P324.555523.702111.1513
B1 (66)P330.506337.22 (6)
335.57 (7)
29.651936.10 (6)
325.23 (7)
13.395816.50 (6)
149.46 (7)
P424.555523.702111.1513
C (61)P430.506318.59 (6)
269.76 (7)
29.651918.03 (6)
269.76 (7)
13.39588.26 (6)
120.09 (7)
P524.555523.702111.1513
D
251 (4) +114 (5)
P6 (4)26.898141.49 (6)
1035.9 (7)
24.290234.98 (6)
873.56 (7)
9.540411.49 (6)
157.62 (7)
P6 (5)78.829662.937817.2478
TOTALALL 273.19 (6)
2456.2 (7)
259.66 (6)
2250.2 (7)
114.43 (6)
919.45 (7)
Table 15. Summary of energy, emissions and economic savings in the industrial transformation center: (1) Optimizing only the operation of the capacitor banks and (2) replacing the inefficient transformer with an efficient one, with optimization of the capacitors.
Table 15. Summary of energy, emissions and economic savings in the industrial transformation center: (1) Optimizing only the operation of the capacitor banks and (2) replacing the inefficient transformer with an efficient one, with optimization of the capacitors.
Energy and Environmental
Savings
Economic Savings
(at Prices from Early 2022)
Energy (kWh/year)CO2 Emissions (kg/year)By Energy
Consumptions (€/year)
Reactive
Penalties (€/year)
No transformer replacement (1)2896.37698.0020644,158.83
With transformer replacement (2)19,037.954588.141536.7544,158.83
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

León-Martínez, V.; Peñalvo-López, E.; Andrada-Monrós, C.; Cano-Martínez, J.; León-Vinet, A.; Molina-Cañamero, L. Procedure for Improving the Energy, Environmental and Economic Sustainability of Transformation Houses. Appl. Sci. 2022, 12, 4204. https://0-doi-org.brum.beds.ac.uk/10.3390/app12094204

AMA Style

León-Martínez V, Peñalvo-López E, Andrada-Monrós C, Cano-Martínez J, León-Vinet A, Molina-Cañamero L. Procedure for Improving the Energy, Environmental and Economic Sustainability of Transformation Houses. Applied Sciences. 2022; 12(9):4204. https://0-doi-org.brum.beds.ac.uk/10.3390/app12094204

Chicago/Turabian Style

León-Martínez, Vicente, Elisa Peñalvo-López, Clara Andrada-Monrós, Jorge Cano-Martínez, Amparo León-Vinet, and Laura Molina-Cañamero. 2022. "Procedure for Improving the Energy, Environmental and Economic Sustainability of Transformation Houses" Applied Sciences 12, no. 9: 4204. https://0-doi-org.brum.beds.ac.uk/10.3390/app12094204

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop